Metrix 5550 Manuale di istruzioni

5550 & 5550G MECHANICAL VIBRATION SWITCHES
User Guide / Installaon Manual
DOC# 1231558 • REV C (November 2017)
1180
1180
MODEL 5550
MODEL 5550G
The 5550 and 5550G mechanical vibraon
switches provide vibraon protecon for
low- to medium-speed machinery. An inera
sensive mechanism acvates a snap-acon
switch with SPDT output contacts if the vi-
braon exceeds an adjustable setpoint. The
5550 mechanical vibraon switch contacts
can be used to acvate an alarm or iniate
equipment shutdown. The housing is weath-
erproof with an oponal hazardous area
rang. Electrical (remote) reset with start-up
me delay and a second set of SPDT output
contacts to accommodate DPDT needs
(e.g. separate trip and trip light circuits) are
available.
The 5550G uses idencal internal mecha-
nisms, but carries an IECEX rang ideal for
IIC gas group applicaons.

Doc# 1231558 • REV C (November 2017) Page 2 of 20
1. PRINCIPLES OF OPERATION
1.1 Overview
Model 5550 and 5550G Mechanical Vibraon Switches oer basic protecon against gross
changes in structural seismic acceleraon. The two units are idencal internally and dier
only in their enclosure style and external access to adjustments. The 5550G is used for haz-
ardous area applicaons requiring gas group IIC approvals, but has no externally accessible
adjustments. The 5550 has externally available setpoint adjustment and reset facilies, and
can be used for applicaons up to gas group IIB + hydrogen. Refer to hazardous area instal-
laon manuals M8905 (model 5550) and 100356 (model 5550G) for addional informaon.
The operang mechanism is purely mechanical and
consists of a tension spring aached to a pivong
plate on an over-center fulcrum – magnets are not
employed. Normally, this plate is in an untripped
posion (Figure 1A). However, in the presence of
sucient seismic acceleraon (whether vibratory
or impact), the trip plate will pivot beyond this
over-center posion, snapping to a stable tripped
posion (Figure 1B) where it contacts an internal
micro-switch relay, changing the state of the relay.
This relay is available for external wiring connec-
ons where on/o changes in electrical connuity
can be used to trip the machine and/or annunci-
ate excessive vibraon.
Once the switch has assumed its tripped posion,
it must be reset manually by means of the external
reset plunger (5550 only), or by means of a remote
electrical reset (standard on 5550G, oponal on
5550). The remote reset capability can also be
used as a startup delay to hold the switch in an
untripped state for as long as coil excitaon is sup-
plied – up to 30 seconds (the maximum duraon
is governed by a non-adjustable, factory-installed
thermistor circuit). The startup delay feature is useful during machinery startup when vibra-
on in excess of the normal trip seng may be temporarily incurred.
1.2 Typical Applicaon
The model 5550 and 5550G mechanical vibraon switches are typically used on cooling
tower fans and mounted such that loss of a blade will result in signicant structural accelera-
on at the switch mounng locaon (Figure 2).
The switch may be used on other types of machin-
ery as well, but care must be taken to ensure that
adequate change in acceleraon between “normal”
and “malfuncon” condions will exist at the switch’s
mounng locaon. The switch is not designed to reli-
ably trip for acceleraon levels below approximately
1 g (9.8 m/s2), or when less than 1 g exists between
a machine’s normal running vibraon levels and mal-
funcon vibraon levels. Figure 2: Typical 5550 installaon on
cooling tower fan support strut.
Figure 1A: 5550 mechanical switch trip
mechanism in untripped posion. Micro-
switch (red) is not actuated.
Figure 1B: 5550 mechanical switch trip
mechanism in tripped posion. Micro-
switch (red) is actuated.

Doc# 1231558 • REV C (November 2017) Page 3 of 20
1.3 Primary Variables Aecng 5550 Operaon
The required seismic acceleraon to move the 5550 or 5550G mechanical switch from its un-
tripped posion to its tripped posion is a funcon of three variables as detailed in secons
1.3.1 through 1.3.4.
1.3.1 Variable #1 – Spring Force Direcon
The movable trip plate mass inside the switch housing is
free to move on an essenally friconless pivot, and is
restrained in its untripped posion by a spring. By turning
the setpoint adjustment screw (Figure 3), changes are made
to the spring’s direcon, and to a much lesser extent, its
tension. Thus, the spring mechanism exerts an essenally
constant force on the trip plate and turning the setpoint ad-
justment screw changes the direcon of this force. Turning
the setpoint screw clockwise (CW) aligns the spring force
more fully in the untripped direcon (below the pivot – see
Figure 1), making it more dicult to trip the device. Turn-
ing the setpoint screw counter-clockwise (CCW) does the
opposite, making it easier to trip the device.
SETPOINT
ADJUST
RESET PLUNGER
FIGURE 3: MODEL 5550 setpoint
adjustment and manual reset.
NOTE: Metrix Mechanical Vibraon Switches
are not intended for use on high-speed tur-
bomachinery or on machines where changes in
seismic acceleraon smaller than 1G must be
reliably detected. Instead, Metrix oers more
sophiscated electronic vibraon sensing soluons that
are beer suited for such applicaons.
NOTES:
1. Turning the screw too far in the counter clockwise (CCW) direcon will eventu-
ally pull the spring past the over-center locaon and cause the switch to snap
into the tripped posion without any external ineral excitaon. When adjusted
in this manner, the switch cannot be reset from its tripped posion. Also, the
nature of this over-center mechanism can cause it to be very unstable when adjusted too
close to its equilibrium locaon, resulng in false trips.
2. The setpoint adjustment screw on the model 5550G switch is not externally accessible.
The cover must be removed. Do not remove the cover while energized circuits are pres-
ent in hazardous areas
1.3.2 Variable #2 – Switch Orientaon
Depending on how the switch is oriented, gravity will act on the trip mechanism’s mov-
able mass to either add to or subtract from the spring force. For both model 5550 and
5550G switches, the switch orientaon is the direcon in which the cover faces. With the
switch oriented horizontally (Figure 4A), the eects of gravity will be negligible and only

Doc# 1231558 • REV C (November 2017) Page 4 of 20
FIGURE 4: Side views showing horizontal and vercal orientaons of 5550 switch
NOTE: Depending on how the setpoint is adjusted, sim-
ply turning the switch on its side or upside down may be
sucient to cause it to trip, due to the eects of gravity.
1.3.3 Variable #3 – Vibraon Forces Acng on the Switch
By shaking or impacng the switch along its sensive axis with sucient ineral force for
a sucient duraon and within its frequency response range, the trip plate mechanism
will overcome the combined forces of gravity (depending on orientaon) and spring ten-
sion, snapping from its untripped posion to its tripped posion.
2. INSTALLATION
the spring force will govern the trip plate’s behavior. With the switch oriented vercally
up (Figure 4B), gravity acts to keep the trip plate’s movable mass in the untripped posion,
and ineral excitaon must counteract both gravity and the spring force. With the switch
oriented vercally down (Figure 4C), gravity acts in the opposite direcon and opposes the
spring’s force. Thus, with the same setpoint adjustment, a switch facing up will require the
most excitaon to trip, a switch facing horizontally will require 1g less excitaon to trip, and
a switch facing down will require 2g less excitaon to trip.
WARNING: Before proceeding to wire and install model 5550 and 5550G switch-
es, read and thoroughly understand these instrucons. They are intended for
experienced personnel who require only basic installaon guidance, and assume
that the switch has already been selected and applied properly for the machinery at hand.
When installing the switches in hazardous atmospheres, refer to Metrix manuals M8905
(5550) and 100356 (5550G) for important safety informaon. All of these manuals, as
well as addional technical resources, are available on our website at www.metrixvibra-
on.com. You may also contact Metrix or its local representave for addional assistance,
using the informaon on the last page of this manual.
GRAVITY
SENSITIVE
AXIS
GRAVITY
SENSITIVE
AXIS
GRAVITY
SENSITIVE
AXIS
4A: Horizontal orientaon,
cover facing right
4B: Vercal orientaon,
cover facing up
4C: Vercal orientaon,
cover facing down

Doc# 1231558 • REV C (November 2017) Page 5 of 20
NOTE: When specifying units with 2g reset coil holding
strength simultaneously with a 24 VDC reset coil, do not install
the switch with a horizontal orientaon or upside down. The
reset coil lacks sucient holding force for anything other than
a vercal “face up” orientaon (Figure 4B).
2.1 Maintenance Convenience Versus Measurement Quality
While it is desirable to mount the switch in a locaon in which it can be easily serviced and
maintained, this should not be the dominant consideraon. The switch serves as a me-
chanical sensor and for it to provide suitable machinery protecon, it must be mounted in a
locaon and orientaon where the machine’s ineral forces during malfuncon condions
will be suitably large to trip the switch. Thus, locang the switch for opmal mechanical
sensing – rather than opmal serviceability – must always remain the primary consideraon.
However, in most circumstances, judicious choice of mounng locaon and switch orienta-
on can accommodate both requirements sasfactorily.
2.2 Sensive Axis
The switch is designed to respond to ineral forces only in the direcon of its sensive axis
(Figure 4). When care is not taken to mount the switch properly, relavely large ineral
forces can occur elsewhere on the machine that will not be transmied properly to the
switch, and/or will occur in a direcon perpendicular to the switch’s sensive axis. Both of
these condions can render the switch’s ability to trip less eecve or even ineecve.
2.3 Horizontal Orientaon
A horizontal orientaon of the switch means that it is mounted with its sensive axis per-
pendicular to the direcon of gravity (refer to Figure 4A). In this orientaon, the eects of
gravity on the switch’s trip mechanism are negligible and the trip point is governed almost
enrely by the spring. It is recommended that the switch be oriented horizontally because
most machines are less constrained (less s) in the horizontal direcon than in the vercal
direcon and will therefore vibrate more in the horizontal direcon.
2.4 Vercal Orientaon
A vercal orientaon of the switch means that it is mounted with its sensive axis parallel to
the direcon of gravity. It is not recommended that the switch be oriented vercally (except
as noted above) because most machines are more constrained (more s) in the vercal di-
recon than in the horizontal direcon, and will therefore vibrate less in the vercal direcon.
2.5 Horizontal Machines
Although Figures 5 and 6 both show horizontal switch orientaons, they are not equivalent.
In Figure 5, the sensive axis of the switch points directly at the machine’s sha; in Figure
6, it does not and instead is aimed at point P somewhere above the sha. Either mounng
orientaon can be eecve, but 5 is preferred.

Doc# 1231558 • REV C (November 2017) Page 6 of 20
SHAFT CENTERLINE
CONDUIT
5550 MOUNTING LOCATION
WITH CONDUIT FITTING
FACING DOWN
BASEPLATE
SHAFT Z AXIS
(AXIAL)
CONDUIT
END VIEW
SIDE VIEW
NOTE: A drain hole at low point is
recommended to allow accumulated
moisture to exit (except in
explosion-proof installations)
Shaft Radial YAxis
Shaft Radial XAxis
SHAFT CENTERLINE
SHAFT CENTERLINE
CONDUIT
5550 MOUNTING LOCATION
WITH CONDUIT FITTING
FACING DOWN
BASEPLATE
SHAFT Z AXIS
(AXIAL)
CONDUIT
END VIEW
SIDE VIEW
NOTE: A drain hole at low point is
recommended to allow accumulated
moisture to exit (except in
explosion-proof installations) SHAFT CENTERLINE
P
Shaft Radial YAxis
Shaft Radial XAxis
Figure 5: Horizontal machine showing horizontal 5550 mounng orientaon and preferred locaon.
Conduit ng faces down to allow drainage of any condensaon.
Figure 6: Horizontal machine showing horizontal 5550 mounng orientaon and alternate locaon.
Conduit ng faces down to allow drainage of any condensaon.
Figure 7 shows the same horizontal machine as in Figures 5 and 6, but with the switch ori-
ented vercally. As noted in Secon 2.4, a vercal orientaon of the switch is discouraged
because machines will generally experience less vibraon in the vercal direcon than in
the horizontal direcon, and the switch will be less eecve. Metrix does not recommend
installaon as shown in Figure 7 unless the machine truly experiences more vibraon in the
vercal direcon than in the horizontal direcon, or the 2g / 24V reset coil opon is being
used (see note in Secon 2.4).

Doc# 1231558 • REV C (November 2017) Page 7 of 20
Figure 7: Horizontal machine showing verctal 5550 mounng orientaon (not recommended).
SHAFT CENTERLINE
5550 MOUNTING LOCATION
BASEPLATE
SHAFT Z AXIS
(AXIAL)
CONDUIT
END VIEW
SIDE VIEW
Shaft Radial YAxis
Shaft Radial XAxis
SHAFT CENTERLINE
2.6 Vercal Machines
Figure 8 shows the preferred installaon for a vercal machine. The switch is mounted
horizontally and with its sensive axis poinng directly at the sha.
In contrast, Figure 7 shows the switch mounted vercally, which is not recommended.
Because most vercal machines (like horizontal machines) are rigidly xed by a baseplate
or other mounng that constrains them from vibrang in the vercal direcon, aligning the
switch’s sensive axis in the vercal direcon aligns it in the direcon of least vibraon.
Instead, mount the switch as shown in Figure 5 to ensure that radial (not axial) vibraon is
detected. Mount the switch as shown in Figure 7 only when the machine actually vibrates
more in the vercal than horizontal direcon, or when the 2 g /24 V reset coil opon is used
(see note in secon 2.4).
SHAFT CENTERLINE
CONDUIT
BASEPLATE
5550 MOUNTING LOCATION
WITH CONDUIT FITTING
FACING DOWN
BASEPLATE
SHAFT Z AXIS
(AXIAL)
CONDUIT
TOP VIEW
SIDE VIEW
NOTE: A drain hole at low point is
recommended to allow accumulated
moisture to exit (except in
explosion-proof installations)
Shaft Radial YAxis
Shaft Radial XAxis
Figure 8: Vercal Machine showing horizontal 5550 mounng orientaon and recommended locaon

Doc# 1231558 • REV C (November 2017) Page 8 of 20
2.7 Mounng Rotaon
The switch can be rotated about its sensive axis without aecng its operaon (Figure 9).
Thus, posions 9A, 9B, 9C, and 9D showing the model 5550 switch rotated at 12:00, 3:00,
6:00, and 9:00 posions respecvely do not aect the operaon of the switch and are pri-
marily a maer of preference and serviceability. However, when possible, it is recommend-
ed that conduit ngs be oriented facing down, helping to prevent moisture or condensa-
on accumulaon inside the device.
2.8 Axing The Switch To The Machine
Mount the switch securely to the machine using the 4-hole paern (5550) or 2-hole paern
(5550G) on the baseplate. It is extremely important that the device be rigidly aached
to the machine so that it reects machinery vibraon – not vibraon incurred by a loose
mounng, an insuciently s mounng bracket, or a bracket resonance. Also, the switch
should be mounted in a locaon where its own mass does not appreciably aect the natural
frequency(ies) of the member to which it is aached. When aaching to a support beam,
skid, or other member, thought should be given to the usefulness of the measurement and
what level of machinery damage must be present before sucient acceleraon will occur at
the measurement locaon. For addional applicaon assistance, consult the factory or your
nearest Metrix representave.
2.9 Wiring
The switch provides a single SPDT relay or oponal double SPDT relays, allowing use as a
DPDT device. When a reset / startup delay coil is specied (oponal on 5550; standard on
5550G), suitable wiring terminals are also available. Refer to Figure 10 for wiring terminal
assignments.
9A - 12:00 horizontal orientaon
9B - 3:00 horizontal orientaon
9C - 6:00 horizontal orientaon
9D - 9:00 horizontal orientaon (preferred)
Figure 9: Horizontal orientaons of 5550. 9D posion is strongly recommended
(conduit hole facing down) to allow drainage oof any accumulated condensaon.
GRAVITY

Doc# 1231558 • REV C (November 2017) Page 9 of 20
When wiring the device, observe the following:
2.9.1 Do not exceed switch contact rangs listed on the nameplate.
2.9.2 Comply with all applicable electrical codes.
2.9.3 Keep eld wiring away from the moving parts of the trip plate mechanism.
2.9.4 All power must be switched o before opening the enclosure in an explosive
atmosphere.
2.9.5 The switch must be electrically connected by means of a ameproof/dust cable
gland or stopping box cered to IEC60079-0:2011 (EN60079-0:2012), IEC60079-1:2007
(EN60079-1:2007), and IEC600079-31:2008 (EN60079-31:2009).
2.9.6 For ambient temperatures below -10°C, use eld
wiring suitable for the minimum ambient temperature.
2.9.7 Reinstall the cover by rst ensuring the o-ring
is in place and properly seated in the housing’s groove.
Place the cover on the unit and screw ght (model
5550G) or by torqueing the four cover bolts shown in
Figure 11 (model 5550 only) to 6-7 /lbs.
NOTE: It is not recommended
that wiring be connected to the
device unl aer verifying the
factory default setpoint in Secon
4.1 and performing the in-situ setpoint
adjustments in Secon 4.2. This will pre-
vent having to disconnect the wiring and
remove the device from its mounng loca-
on. It will also prevent unwanted trips
while inially adjusng the setpoint.
WARNING: Voltages present at
switch terminals can result in
serious injury or death. Always
de-energize these circuits prior
to installaon or maintenance and use
appropriate lock-out / tag-out proce-
dures where applicable.
CAUTION: If eld wiring is allowed to obstruct the
moving parts of the switch, it may prevent the trip
plate from operang correctly. Machinery protec-
on can be compromised and serious machinery damage
and/or personnel injury may result.
NOM
OPEN
COM
NOM
CLOSED
RESET COIL
CASE
RESET COIL
L(+)
N(-)
GRN
NOM
OPEN
COM
NOM
CLOSED
RESET COIL
CASE
RESET COIL
L(+)
N(-)
GRN
NOM
OPEN
COM
NOM
CLOSED
WIRING DIAGRAM
SPDT DPDT
DPDT CONTACTS AND RESET COIL OPTION
Figure 10: Wiring connecons
Figure 11: 5550 cover bolts locaon
2
1
3
4

Doc# 1231558 • REV C (November 2017) Page 10 of 20
2.10 Conduit: When aaching conduit, observe the following:
2.10.1 Avoid long runs of unsupported conduit that can transfer unwanted impacts or
vibraon of the conduit, rather than of the machine.
2.10.2 Always slope conduit away from the switch and generally orient such that accumu-
lated moisture or condensaon does not drain into the switch. For non-explosion proof
installaons, consider the use of an adequate number of J-traps or other drain mecha-
nisms at low points to preclude moisture from collecng in the switch or in the conduit.
When possible, mount the switch so that the conduit outlet faces down.
2.10.3 Units with NPT conduit holes (ordering opon E=1, 2, 3, 7) have ¾” NPT threads.
Units with metric conduit holes (ordering opon E=4, 6, and 8) have M20 x 1.5 threads.
Refer to Metrix datasheet # 1004461 for a complete list of ordering opons.
2.10.4 Use proper conduit seals and hole plugs meeng the environmental requirements
of the installaon to prevent ingress of moisture and dust.
2.11 Protecng Against Moisture Ingression
All installaons should observe the guidelines of 2.10. These are parcularly important
when the switch will be mounted in moist environments such as on cooling tower struc-
tures, evaporave fans, marine applicaons, or other installaons where the switch will be
exposed to rain, elevated humidity, hose-directed water, or any environmental condions
that might allow condensaon to form at or in the switch, associated wiring, and conduit.
2.11.1 Ensure the cover is properly ghtened
The importance or properly ghtening cover bolts (5550) or screw-type lid (5550G) per-
tains not just to sealing against ignion of a ammable atmosphere outside the switch,
but also to prevent dust or moisture ingression to the switch internals.
2.11.2 Examine Cable Insulaon for Nicks and Cuts
In some cases, properly rated cable may be installed without solid or exible conduit to
NOTE: The disposable plasc plugs that ship in each con-
duit hole provide only physical thread protecon during
shipping and handling. They are not designed for use as
permanent hole plugs and do not provide adequate environ-
mental protecon for the switch when installed in the eld.
CAUTION: Do not over-torque or under-torque
housing screws. Over torqueing can damage the
housing and compromise the seal. Under torque-
ing can permit moisture to weep into the switch. Either
condion can compromise switch operaon and/or present
an electrical shock hazard.
NOTE: Do not over-torque the cover bolts on the model 5550
switch. This could damage the housing and compromise the seal.