5. Data Report
The device will immediately send a version packet report along with an uplink packet including
temperature, humidity, voltage and PM2.5 value.
The device sends data in the default configuration before any configuration is done.
ReportMaxTime:
RA0716 / RA0716Y is 180s
R72616 is 900s (subject to factory settings)
Value must be greater than ReportMinTime
≧
ReportType count *ReportMinTime + 10 ,units: seconds
ReportMinTime: 30s;
ReportChange: 0;
ReportType count = 1;
Note:
(1) The device report interval will be programmed base on the default firmware which may vary.
(2) The interval between two reports must be the Maxtime
(3) ReportChange is not supported by RA0716_R72616_RA0716Y (Invalid configuration)
(4) Report cycle will be based on ReportMaxTime period when sending data packet (beginning to
the end of the first data as a period).
(5) Data packet: temperature,humidity,voltage and PM2.5
(6) It would take about 35 seconds for the PM2.5 sensor to sample and process the collected PM2.5
value after being powered
(7) The device also supports Cayenne's TxPeriod cycle configuration instructions. Therefore, the
device can also perform a report according to the cycle time of the TxPeriod value; and
whether the report period is ReportMaxTime or TxPeriod will be depending on which cycle
time is configured last time;
(8) It would take about 35 seconds for the PM2.5 sensor to sample and process the collected PM2.5
value if you were to manually trigger the device by pressing the button, please be patient.
The device reported data parsing please refer to
Netvox LoraWAN Application Command document and Netvox Lora Command Resolver
http://www.netvox.com.cn:8888/page/index