Transport
F1245 should be transported and stored vertically in a dry
place. When being moved into a building, F1245 may be
leant back 45 °. Note! Can be tail heavy.
R
0
R
0
Pulling out the cooling module
To simplify transport and service, the heat pump can be
separated by pulling the cooling module out from the cabin-
et.
See page 66 for instructions about the separation.
Assembly
႑Position the heat pump on a firm base that can bear its
weight, preferably on a concrete floor or foundation. Use
the heat pump’s adjustable feet to obtain a horizontal and
stable set-up.
30 - 50 mm
႑The area where the heat pump is located must be
equipped with floor drainage.
႑Install with its back to an outside wall, ideally in a room
where noise does not matter, in order to eliminate noise
problems. If this is not possible, avoid placing it against a
wall behind a bedroom or other room where noise may
be a problem.
႑Wherever the unit is located, walls to sound sensitive
rooms should be fitted with sound insulation.
႑Route pipes so they are not fixed to an internal wall that
backs on to a bedroom or living room.
Installation area
Leave a space of 800 mm in front of the heat pump. Approx
50 mm free space is required in order to open the side
hatches. The hatches do not need to be opened during ser-
vice, all service on F1245 can be carried out from the front.
Leave space between the heat pump and wall behind (and
any routing of supply cables and pipes) to reduce the risk
reproduction of any vibration.
(50) (50)
* A normal installation needs 300 - 400 mm (any side) for connec-
tion equipment, i.e. level vessel, valves and electrical equipment.
5Chapter 2 | Delivery and handlingNIBE™ F1245
2 Delivery and handling