Panasonic EBL512 Manuale utente

EBL512 G3
Fire alarm solutions
DAILY USER'S
MANUAL
www.panasonic-re-security.com

EBL512 G3 - FIRE ALARM SOLUTIONS DAILY USER'S MANUAL
2
Table of Contents
1. INTRODUCTION 3
2. DESCRIPTION OF THE FRONT 4
2.1. LED INDICATORS 5
2.2. PUSH BUTTONS 6
2.3. DISPLAY 6
3. ACCESS LEVELS 7
4. LOG ON TO THE CONTROL UNIT (C.I.E.) 8
4.1. HOW TO LOG ON 8
5. NAVIGATION / GENERAL PROCEDURES 9
5.1. PRINTER 9
6. PERFORM MONTHLY TEST (H1) 10
7. DISABLE OR RE-ENABLE (H2) 10
7.1. SUB MENU LIST (B1 – B6) 11
8. SET CALENDER AND CLOCK (H3) 12
9. PRESENT SYSTEM STATUS (H4) 12
9.1. SUB MENU LIST (U1 – U8) 12
10. FAULT ACKNOWLEDGE (H6) 13
11. PERFORM ZONE TEST (H7) 14
12. INTERLOCKING OUTPUTS AND INPUTS (H9) 15
12.1. SUB MENU LIST (C1 – C3) 15
13. CHANGE PASSWORD (H10) 15

EBL512 G3 - FIRE ALARM SOLUTIONS DAILY USER'S MANUAL
3
1. INTRODUCTION
This document is intended to be used for the daily duties like disablements / re-enablement’s, zone tests, and so on in the EBL512
G3 system.
Due to continual development and improvement different S/W versions can be found.
The document describes the main menus and the sub menus valid for access level "Building ofcer".

EBL512 G3 - FIRE ALARM SOLUTIONS DAILY USER'S MANUAL
4
2. DESCRIPTION OF THE FRONT
Menu Next zone Re-enable Evacuate
2
3
4
5
6
7
8
9
10
28
27
26
17
18
21
11 12 13 14 15
16
29
30313233
22
35
34
343434
20 1919
1
25-

EBL512 G3 - FIRE ALARM SOLUTIONS DAILY USER'S MANUAL
5
2.1. LED INDICATORS
See reference picture on page 4.
1Fire Fire alarms
2Extinguishing Output(s) for extinguishing equipment activated
3Ventilation Output(s) for re/smoke ventilation equipment activated
4Fire brigade tx Output "Fire alarm" for re brigade tx (routing equipment) activated
5Operation Steady light: c.i.e. is powered via the rectier and/or the battery.
Flashing light: c.i.e start up, and if loops are disconnected at start up, until the loops are re-connected.
6Alarms queued
More than one alarm point / zone have activated re alarm.
Use push button "Alarms queued" (21) to scroll amongst the alarm points (zone-address) or the soft key
"Next zone" (23) to scroll amongst the zones.
7System fault
EBL512 G3 is not running because of:
S/W fault
CPU fault
Memory fault
No contact between main board and MMI board
C.i.e. restart (fault code ≠ 00 / 03 /25 / 50 / 53).
8General fault Fault(s) in the system.
9Alarm devices
Steady light: Output(s) type "Alarm device" are disabled.
Flashing light: Output(s) type "Alarm device" have generated fault(s).
This is also valid when the c.i.e. has no "contact" with a unit with such an output, for example 4487, 4479,
and so on.
10 Fault tx activated
Not acknowledged fault(s):
Output "Fault condition" for fault tx (routing equipment) is activated.
Test of routing equipment in progress (see menu H1).
11 Test mode Zones are in "test mode" (see menu H7).
12 General disablements Disablement(s) in the system.
13 Fire brigade tx
(Fault/Disablements)
Steady light: Output(s) for "Routing equipment" disabled via menu H2 / B5 or via open door.
Flashing light: Routing equipment power supply outputs or supervised outputs of type "Routing equip-
ment" have generated fault(s) or the c.i.e. has lost contact with a unit with such an output.
14 Fire brigade tx delay The Alert Annunciation function is enabled.

EBL512 G3 - FIRE ALARM SOLUTIONS DAILY USER'S MANUAL
6
15 DEL Used to clear / delete all visible entry elds.
16 ESC Used to stop input of data or to step upwards in the menu system.
17 Key pad Numeric key pad for the digits 0-9.
18 Enter Used to accept / select a menu or input of data. Also used to acknowledge fault signal and service signal.
19 Left / right keys Used to move the cursor in a menu.
20 Up / down keys Used to scroll between the menus.
21 Alarms queued Used when LEDs "Alarms queued" are lit. Scroll through the queued alarm points or zone addresses.
NOTE! To scroll/browse through the queued zones, use the soft key "Next zone" (23).
22 - 25 Soft keys The function is shown in the display above the soft key. The function of a soft key may vary. If nothing is
shown above the key in the display, the key has no function for the moment.
26 Reset Used to reset: Fire alarms, co-incidence alarms.
NOTE! Has to be pressed for > 0.5 sec.
27 Silence alarm devices Used to silence alarm devices / sounders. If “silence alarm devices” is activated, it is indicated by a
symbol in the display, see (35).
28 Silence buzzer Used to silence the buzzer in the c.i.e. when it is sounding.
2.2. PUSH BUTTONS
See reference picture on page 4.
29 The door is open in any c.i.e. (not valid for 5055) in the system.
30 Loss of mains in any c.i.e. or external power supply unit in the system. The unit is currently power supplied via batteries.
31
Service signal. The week average sensor value is over the service level, or detector is outdated, for one or more analog smoke detectors in the system.
Menu H4/U5 (Symbol ashing): The system is in service mode:
• A COM loop is disconnected
• A COM loop is in service mode
• A Zone line input is disconnected
• Check loop, Autogenerate loop or Auto-addressing function etc. is in progress
32 The c.i.e. is set into “Sensitive fault detection mode” via menu H5/A2.
33 One or more “Technical warnings” are generated in the system.
34 The functions of the soft keys will vary depending on the situation, convention and language.
35 “Silenced Alarm devices” is indicated by this symbol.
2.3. DISPLAY
See reference picture on page 4.

EBL512 G3 - FIRE ALARM SOLUTIONS DAILY USER'S MANUAL
7
3. ACCESS LEVELS
Level “Building ofcer” is described in this document.
INFORMATION ONLY
H4 Present system status
H6 Display faults
H9 Interlocking outputs and inputs
H10 Change password
BUILDING OFFICER
H1 Perform monthly test
H2 Disable or re-enable
H3 Set calendar and clock
H4 Present system status
H6 Fault acknowledge
H7 Perform zone test
H9 Interlocking outputs and inputs
H10 Change password
SERVICE PERSONNEL
H1 Perform monthly test
H2 Disable or re-enable
H3 Set calendar and clock
H4 Present system status
H5 Service
H6 FAULT Acknowledge
H7 Perform zone test
H8 Maintenance
H9 Interlocking outputs and inputs
H10 Change password

EBL512 G3 - FIRE ALARM SOLUTIONS DAILY USER'S MANUAL
8
4. LOG ON TO THE CONTROL UNIT (C.I.E.)
USER NAME
Up to ten users, 0 to 9, may be programmed. By default at delivery, three users are available:
• 0 = Information only
• 1 = Building ofcer
• 2 = Service personnel
PASSWORD
Each User has a Password for an access level, for example. "Information only", "Building ofcer" or "Service personnel".
4.1. HOW TO LOG ON
a) Open the door. Press the soft key Menu .
b) On the keypad, press 0, 1, 2 - - 8 or 9 to select a user. Press .
c) Type the password for that user. (Six digits. * * * * * *)
After typing a correct password, a main menu list with the available menus will be displayed.
For "0", Information only, no password is required.

EBL512 G3 - FIRE ALARM SOLUTIONS DAILY USER'S MANUAL
9
5. NAVIGATION / GENERAL PROCEDURES
• Scroll in lists or menus with .
• Press to toggle between different choices.
• Press soft key to toggle between different functions.
• Press to select / accept.
• Press the digits on the numeric pad to choose a menu or enter data.
• A successful disablement is indicated by a beep and a "√". It will also be shown in the Re-enable list.
• A not successful disablement is indicated by another beep and a "X".
• To leave a menu press ESC.
• To leave the menu system, press the soft key Escape menu .
• To logout, close the door.
Quick jump can be used within each menu, for example press "6" for a quick jump to menu H6.
You will be automatically logged out 15 minutes after the last action, and directly when you close the door. A new login is then
required. If you leave the menu system without closing the door, you have access to the menu system again only by using the soft
key "Menu". A new login is not required.
After pressing the soft key "Abort printing" it will change back to "Print" but the printing might continue
for a few seconds.
5.1. PRINTER
If a printer is available the soft key "Print" is shown and can be used to start a print-out.
During printing the same soft key might change to "Abort printing".

EBL512 G3 - FIRE ALARM SOLUTIONS DAILY USER'S MANUAL
10
6. PERFORM MONTHLY TEST (H1)
a) Log on to the c.i.e.
b) Menu H1 is selected. Press .
c) Press . The c.i.e. buzzer sounds, all the dots in the display are shown and all LEDs on the front are turned on. If the
c.i.e. has a printer it has made a print out: ABC..........Z abc.........z.
d) Press . Up to four zones can be set in test mode. Use the keypad to type the zone numbers.
e) Press .
f) Perform the test.
g) To end the test, press .
Some national regulations also require a routine test of the routing equipment.
If the routing equipment shall not be tested, the monthly test is completed. Press .
If the routing equipment shall be tested, press to highlight YES and press .
Started test is indicated by LED "Fault tx activated" and after 30 seconds also LED "Fire brigade tx".
After 60 seconds in total, the routing equipment test is ended and the LEDs are turned off. Press .
7. DISABLE OR RE-ENABLE (H2)
a) Log on to the c.i.e.
b) Navigate to menu H2.
c) Press . A sub menu list (B1 – B6) will be displayed.
Altri manuali per EBL512
5
Indice
Altri manuali Panasonic Allarme antincendio

Panasonic
Panasonic EBL512 Manuale utente

Panasonic
Panasonic MEW01091 Manuale utente

Panasonic
Panasonic EBL128 Manuale tecnico

Panasonic
Panasonic EBL512 G3 5000 Manuale utente

Panasonic
Panasonic 4479 Manuale utente

Panasonic
Panasonic EBL512 Manuale utente

Panasonic
Panasonic EBL128 Manuale utente
Panasonic
Panasonic Firetracker FT1020G3 CIE Manuale utente
Panasonic
Panasonic Firetracker FT1020G3 CIE Manuale del proprietario

Panasonic
Panasonic 3314 Manuale utente





















