5865 5
ELECTRICAL CONNECTIONS TO THE WIRING TERMINAL BLOCK
(to be carried out by the installer)
NOTICE
- Theelectricwiringcarriedoutbytheinstaller must bein compliancewiththerulesin forceintheCountry.
- Leads minimal section 1 mm2.
- Burners with non-stop operation. For safety reasons, this type of burner must be stopped every 24
hours of operation, by means of an hours-counter to be connected in series with the adjustment
devices.
FLAME MODULATION
The flame modulation is obtainable through the thermostat, controlling the second valve, connected
to the terminals 8 and 9.
FIXING OF THE ELECTRICAL WIRES
All the electrical wires, which are to be connected to the terminal block 4) (fig. 1) shall pass through
the fair leads 3) (fig. 1) as for this scheme.
1- Single phase supply : fair lead Pg 13.5
2- Adjustment thermostat : fair lead Pg 13.5
3- Safety thermostat : fair lead Pg 13.5
4- Gas train : fair lead Pg 13.5,
sheath ø 13
5-2nd stage thermostat : fair lead Pg 13.5
6 / 7 - Pre-sheared holes
Further prospective signals or controls can be connected to the burner wiring terminal board by
removing the metal weldnuts from the pre-sheared holes and inserting a commun fair lead for the
passage and the clamping of the leads.
NOTES
- Do not exchange the neutral wire with the phase (avoid the plug-pin connection).
- Carry out a safe earth connection.
- Check the stop of the burner, by opening the boiler thermostat and the burner lock-out, by
disconnecting the lead from the flame probe.
WARNING
When closing the burner on its slide-bars, pull towards the outside the high voltage cable and the
cable of the flame detection probe, till to little tension.
HRemote lock-out signal
MB Burner terminal strip
PG Minimum gas pressure swicth
TB Burner earth
TL Limit control device system
TR High-low mode load control system
TS Safety control device system
VS Gas safety shut off valve
V1 1° stage gas shut off valve
V2 2° stage gas shut off valve
D2660