SEAWIN Electricals 10A Series Manuale utente

KNX/EIB BUS
POWER ACTUATORS
Product Manual
1
10A Series FCU Actuator
Version: Ver2.1
MF0110
MF0210

KNX/EIB BUS
POWER ACTUATORS
Product Manual
2
Contents
1 Summary ............................................................................................................................................................................................................... 3
2 Product and Feature Overview ...................................................................................................................................................................... 3
3 Specification ......................................................................................................................................................................................................... 3
4 Dimensional and wiring diagrams ............................................................................................................................................................... 4
5 Product Operating Instructions..................................................................................................................................................................... 5
6 Parameter setting and communication object description ................................................................................................................. 6
6.1 Switch setting function parameters ................................................................................................................................................. 6
6.2 I/O contact interface parameter setting ...................................................................................................................................... 9
6.2.1 Switch model .............................................................................................................................................................................. 10
6.2.2 Blind model ................................................................................................................................................................................. 11
6.2.3 Blind Position model ................................................................................................................................................................ 11
6.2.4 Bimming ....................................................................................................................................................................................... 11
6.2.5 Dimming position ..................................................................................................................................................................... 11
6.2.6 Scene ............................................................................................................................................................................................. 12
6.3 Equipment situation ......................................................................................................................................................................... 12
6.4 Communication object description ............................................................................................................................................... 13
7 Safe use and maintenance ............................................................................................................................................................................ 15
8 Contact ..........................................................................................................................................................................错误!未定义书签。

KNX/EIB BUS
POWER ACTUATORS
Product Manual
3
1
1. Summary
This manual provides you with detailed technical information on the 10A Series FCU Actuator, including installation and
programming details, and explains how to use the 10A Series FCU Actuator based on practical examples. For easy
installation into distribution boxes, the 10A Series FCU Actuator Modules are designed as modular mounting devices
that can be mounted on 35mm DIN rails.
10A series FCU is used to control fan coil units, such as air conditioners, etc., with magnetic hold function.
Installed as a system with other loads via EIB/KNX bus.
The entire system is set up and operated using the engineering design tool software ETS.
2. Product and Feature Overview
The 10A Series FCU actuator are modular installation devices. Connect to the EIB / KNX system through the EIB bus
terminal block, and use the engineering design tool software ETS software (version ETS4.0 or later) to assign physical
addresses and set parameters.
The maximum load current output by each 10A series FCU actuator is 10A, especially when multiple fans are connected
in parallel, the load that can be carried will be reduced. Although the power remains unchanged, the instantaneous
inrush current will increase, which is easy to cause the relay contacts are melted, so it is advisable to use 1/5 or 1/6 of the
maximum current.
The fan coil execution module has manual control buttons, and the LED lights on the buttons indicate the on/off status
of each circuit; the fan coil execution module has 4 dry contact input interfaces, which can input switches, curtains,
dimming, scenes, etc. Control instruction.
Function description:
(1) Control 4-pipe and 2-pipe fan coil units;
(2) With manual switch control;
(3) The relay has a magnetic hold function;
(4) Delay on/off function;
(5) Heating and cooling can be output according to automatic or manual control, with heating and cooling interlocking
function;
(6) The wind speed can be controlled automatically or manually in three types of high, medium and low, with the
function of wind speed interlocking;
(7) Selection function of relay switch state after bus power failure and voltage recovery;
(8) The local wind speed and valve status can be reported;
(9) The 10A FCU actuator has an I/O contact input interface, which can input control commands such as switches,
curtains, dimming, and scenes; it can directly link fire emergency lighting;
(10) I/O wiring communication distance: less than 10m.
3. Specification

KNX/EIB BUS
POWER ACTUATORS
Product Manual
4
Bus voltage 21-30 VDC via KNX bus
Quiescent Current ≤ 12mA
Recharging current ≤ 20mA
Static power ≤360mW
Charging power consumption ≤ 600mW
Main output Each circuit 250VAC (50/60Hz), Max 10A (resistive load)
2-way heating and cooling valve control, 3-way wind speed control
Size(Lx W x H) 145mm x 90mm x 64mm
Weight(approx.) 0.33KG(1way)、0.46KG(2ways)
Shell Material PA66
Installation method DIN rail installation
Working temperature -5°C…+45°C
Storage temperature -25°C…+55°C
Transportation temperature -25°C…+70°C
Relative humidity max 90%
4. Dimensional and wiring diagram
4.1 MF0110
Dimension wiring diagrams
4.1 MF0210
Dimension wiring diagrams

KNX/EIB BUS
POWER ACTUATORS
Product Manual
5
5. Product Operating Instructions
5.1 MF0110
Description: Heating valves, cooling valves and low (Lo), medium (Me) and high (Hi) terminals for adjusting
the wind speed: one in and one out, the aperture can be connected to φ4 wires;
Description: Manual operation buttons, namely: cooling, heating, wind speed low, medium and high buttons
(when the function button is turned on, the indicator light on the button is on, and when it is off, the indicator
light is off);
Description: Dry contact input terminals;
Description: programming button, short press the button to enter programming mode;
Description: Programming indicator light, when the indicator light is red, the device is in the programming
state, when the device is programmed or working normally, the indicator light is off;
Description: KNX terminal block, KNX bus connection, the red wire is connected to "+", and the black wire is
connected to "-";
Note: Status is the status indicator of the device power supply. When the indicator is green, the bus power
supply status of the device is normal;
Note: This button has no effect temporarily;

KNX/EIB BUS
POWER ACTUATORS
Product Manual
6
5.2 MF0210
Description: Heating valves, cooling valves and low (Lo), medium (Me) and high (Hi) terminals for adjusting
the wind speed: one in and one out, the aperture can be connected to φ4 wires;
Description: Manual operation buttons, namely: cooling, heating, wind speed low, medium and high buttons
(when the function button is turned on, the indicator light on the button is on, and when it is off, the indicator
light is off);
Description: Dry contact input terminals;
Description: programming button, short press the button to enter programming mode;
Description: Programming indicator light, when the indicator light is red, the device is in the programming
state, when the device is programmed or working normally, the indicator light is off;
Description: KNX terminal block, KNX bus connection, the red wire is connected to "+", and the black wire is
connected to "-";
Note: Status is the status indicator of the device power supply. When the indicator is green, the bus power
supply status of the device is normal;
Explanation: Manual is the device switching button, press the button, the indicator light on the button will
light up red, and the fan 1 device can be manually controlled, and then press the button, the indicator light on
the button will be orange, and the fan 2 device can be manually controlled.
6. Parameter setting and communication object description
6.1 Switch setting function parameters
The following takes ETS5 as an example to set parameters in ETS5 Note: In the following introduction, Channel X or
X represents the output of the corresponding channel.
1) Open the parameter setting interface of the 10A series FCU actuator in ETS5, as shown in Figure 6.1.1. The
parameter "Channel X" represents the output of the corresponding channel. The parameter "Field control"

KNX/EIB BUS
POWER ACTUATORS
Product Manual
7
represents the field control function. When the "off" command is sent, the relay state of each channel is saved and
turned off. When the "on" command is sent, the last saved relay state is called. (Note: The "off" command cannot be
sent twice in a row, because the current state is saved when the "off" command is sent for the first time, but the first
send is saved when the "off" command is sent for the second time" off” command, overwriting the state of the
scene saved for the first time).
Optional: Disable & Enable
When selecting the first fan, select "Enabled" in Channel 1—Channel 5, and select "Disabled" for other items; when
selecting the second fan, select "Enabled" in Channel 6—Channel 10, and select "Disabled" for other items.
"Disabled"; if you select 2 channels of fans at the same time, select "Enabled" in Channel 1—Channel 10, and select
"Disabled" in other items. In addition, the 10A fan coil execution module has 4 dry contact input interfaces. (Here,
take the selection of the fan coil execution module with 1 fan as an example)
Pic 6.1.1
2) After the setting is completed, the interface is shown in Figure 6.1.2, and there are 6 options in the red box as
shown.
Pic 6.1.2

KNX/EIB BUS
POWER ACTUATORS
Product Manual
8
3)Click the options in the red box above to set the parameters of each loop respectively. Take Channel A as an
example below, as shown in pic 6.13
Pic 6.1.3
4) The parameter "Operating mode" is divided into three modes: Normal mode, Time mode and Cycle mode. The
10A FCU actuator only uses one normal mode.
5) Channel 1 is cooling (Cool), Channel 2 is heating (Heat), Channel 1 and Channel 2 are set to interlock group 1;
Channel 3 is strong wind (Lo), and Channel 4 is medium wind (ME), Channel 5 is low wind (HI), Channel 3, Channel 4
and Channel 5 are set to interlock group 2.
Normal model
Channel 1 Describe
On delay
Delay opening of the relay (optional: disable, 1, 2...15 seconds); for example: select "5
seconds", when sending the "ON" command, the corresponding circuit will execute the
relay opening after 5s.
Off delay
Delay off of the relay (optional: disable, 1, 2...15 seconds); for example: select "5 seconds",
when sending the "OFF" command, the corresponding circuit will execute the relay off
after 5s.
preferred position at bus
failure
Indicates the state of the corresponding circuit of the relay after power failure, options
are: on, off, unchanged;
preferred position at bus
recovery
Indicates the state of the corresponding circuit of the relay after the voltage is restored,
the options are: on, off, unchanged;

KNX/EIB BUS
POWER ACTUATORS
Product Manual
9
Status response
Status feedback, options: No (no feedback), Yes (with feedback), when "Yes" is selected,
the "Transmission of status" parameter will appear, options: using read request only (state
feedback is available when a request is issued), on change in status (the status change
will have status feedback immediately), always on operation (as long as there is a control
command issued, there will be status feedback);
"Invert status feedback" indicates the function of feedback inversion. The options are: No,
Yes. When "Yes" is selected, the feedback will be off when the relay is on, and the
feedback will be on when the relay is off.
8-bit scene control Scene control function, not enabled yet, select: Disable
Interlocking group Execute the switch interlock function. Options: none (not enabled), group 1 (group 1),
group 2 (group 2), group 3 (group 3), group 4 (group 4), group 12 (group 12)
Pic 6.1.4
6.2 I/O contact interface parameter setting
1) Click "Universal Interface" as shown in Figure 6.2.1, Universal Interface A-D are set to enable, and four dry
contact interfaces will be enabled。
Pic 6.2.1
2)After the setting is completed, four IO interfaces of Interface A-D will appear on the right side, click each dry
contact interface to set its parameters. Take Universal Interface A as an example below, as shown in Pic 6.22

KNX/EIB BUS
POWER ACTUATORS
Product Manual
10
Pic 6.2.2
3)The parameter "function mode" is divided into 6 modes:Switch, Blind, Blind Position, Dimming, Dimming
Position, Scene.
6.2.1 Switch model
Specification Description
Switch mode
Indicates the action of the corresponding loop control when the dry contact is triggered,
the options are: on, off, toggle, user define; when user define is selected, the following
parameters appear: (1 )Reaction on closing the contact indicates the reaction when the dry
contact is closed, options: on, off, no reaction; (2) Reaction on opening the contact
indicates the reaction when the dry contact is released , options: on, off, no reaction; (3)
cyclic transmission of object represents the object to be sent cyclically, options: no (none),
if "switch"=ON (when the relay is on), if "switch"=OFF (when the relay is off), always
(always). When selecting if "switch"=ON, if "switch"=OFF or always, the parameters appear:
transmission cycle time: base and Time factor [1-255] (the two parameters here represent
the time of the cycle transmission interval, this Time = transmission cycle time: base value
× Time factor [1-255] value).
debounce time Indicates the time of debounce, optional: 10ms、20ms……100ms