SJE Rhombus Installer Friendly Series Manuale utente

22650 County Highway 6
P.O. Box 1708
Detroit Lakes, Minnesota 56502 USA
1-888-DIAL-SJE (1-888-342-5753)
Phone: 218-847-1317
Fax: 218-847-4617
E--mail: customer.ser[email protected]
Website: www.sjerhombus.com
©SJE-Rhombus
Printed in USA
1022888D • Rev 12/14
Manufactured by:
Warranty void if panel is modified.
Call factory with servicing questions:
1-800-RHOMBUS
(1-800-746-6287)
This control panel must be installed and serviced by a licensed
electrician in accordance with the National Electric Code NFPA-70, state
and local electrical codes.
All conduit running from the sump or tank to the control panel must be
sealedwithconduitsealanttopreventmoistureorgasesfromenteringthepanel.
NEMA 4X enclosures are for indoor or outdoor use, primarily to provide a
degreeofprotectionagainstcorrosion,windblowndustand rain, splashing water
and hose-directed water. Cable connectors must be liquid-tight in NEMA 4X
enclosures.
This Installer Friendly Series®(IFS) control panel was designed to control
pump(s). The controller records pump status, number of cycles, elapsed run
time, current float status, and float error counts.
Mounting the Control Panel
Note:Thecontrolpanelshould not be mounted in alocation that may be subject
to submersion.
1. Determine mounting location for panel. If distance exceeds the length of
either the float cables or the pump power cables, splicing will be required.
Foroutdoororwetinstallation,werecommendtheuseofanSJE-Rhombus®
liquid-tight junction box with liquid-tight connectors to make required con-
nections. You must use conduit sealant to prevent moisture or gases
from entering the panel.
2. Mount control panel with mounting devices furnished.
3. Determine conduit entrance locations on control panel. Check local codes
and schematic for the number of power circuits required. (Float cables
require separate conduit from power and pump cables.)
Note: Be sure the proper power supply voltage, amperage, and phase meet the
requirements of the pump motor(s) being installed. If in doubt, see the pump
identification plate for voltage/phase requirements.
4. Drill proper size holes for type of connectors being used.
Note: Ifusingconduit,besurethatitisofadequatesizetopullthepumpcable(s)
through.
5. Attach cable connectors and/or conduit connectors to control panel.
FOR INSTALLATION REQUIRING
A SPLICE, FOLLOW STEPS 6-10;
FOR INSTALLATION WITHOUT A
SPLICE, GO TO STEP 11.
6. Determine location for mounting junction box according to local code
requirements. Do not mount the junction box inside the sump or basin.
7. Mount junction box to proper support.
8. Run conduit to junction box. Drill proper size holes for the type of conduit
used.
Installation
Installer Friendly Series®
SJE-Rhombus®Type IFS
Installation Instructions and Operation/Troubleshooting Manual

9. Identify and label each wire before pulling through conduit
into control panel and junction box. Make wire splice
connections at junction box.
10. Firmly tighten all fittings on junction box.
11. If a junction box is not required, pull cables through conduit
into control panel.
12. Connect pump wires per wiring diagram or schematic
and float wires to the proper terminals as shown on the
schematic.
13. Connect pump, control, and alarm incoming power
conductors to proper position on terminals. See schematic
for terminal connections.
VERIFY CORRECT OPERATION OF CONTROL
PANEL AFTER INSTALLATION IS COMPLETE.
Installation of Floats
CAUTION: If control switch cables are not wired and mounted
in the correct order, the pump system will not function properly.
Control switches need to run in separate conduit from pump
and power lines.
WARNING: Turn off all power before installing pump wires
in pump chamber. Failure to do so could result in serious
or fatal electrical shock.
1. Determine your normal operating level and desired float
configuration, as illustrated in Figures 2-5.
2. Mountfloatswitchesat appropriate levels.Besurethatfloats
have free range of motion without touching each other or
other equipment in the basin.
3. For mounting clamp installation: place the cord into the
clampasshowninFigure 1.Locatetheclampat the desired
activation level and secure the clamp to the discharge pipe
as shown in Figure 1.
NOTE: Do not install cord under hose clamp.
4. Tighten the hose clamp using a screwdriver. Over tightening
may result in damage to the plastic clamp. Make sure the
float cable is not allowed to touch the excess hose clamp
band during operation.
NOTE: All hose clamp components are made of 18-8
stainless steel material. See your SJE-Rhombus®supplier
for replacements.
5. If using an optional redundant off float, mount slightly below
the timer enable float.
6. The alarm float can be positioned anywhere that the alarm
level is desired.
Installation Instructions
Figure 3
Simplex Demand
Figure 4
Duplex Demand 3 Float Figure 5
Duplex Demand 4 Float
Figure 1
Figure 2
Simplex/Duplex Timed Dose

Operations
The Installer Friendly Series®(IFS) control panel uses float
switches to continuously monitor and control the liquid level in
the tank.
Hand Operation - The stop/redundant off float must be
raised to put panel in HAND operation. To override the stop/
redundant off float, press and hold the HAND button.The pump
runs until the HAND button is released. The panel then returns
to the AUTO mode. If the stop/redundant off float is raised and
the panel is placed in the HAND mode, and left in the HAND
mode, the pump continues to run until the stop/redundant off
float lowers. The panel then returns to theAUTO mode.
Off Operation - The panel is in the OFF mode.
Auto Operation - In time dose (t-dose) mode, when the
panelis intheAUTOmode,the timercontrolspump ON andOFF
time as long as the low level float is raised. In demand (d-dose)
mode, the stop and start floats control the pump.
Alarm Count - Shown on display as “AL-Ctr”, counts the
numberof times thealarmis activated. Note:Alarmcounterdoes
notinclude testingoperationsin thetotalcount. Highalarm,floats
out of sequence & auxiliary alarm add to count.
Green Control and Alarm Power Indicators -
(mounted on interior circuit board) Illuminates when control
power and alarm power is present. If the control fuse needs
replacing, the panel sounds an alarm.
Display - Will turn off after one minute of non-use.
Float Indicators - Illuminates if the float is raised. If the
float is out of sequence, the panel goes into alarm mode and
display shows “FE” float error.
Timer Override Float - Overrides the OFF time and pump
will run for full dose ON time. (timed dose only, optional)
Float Error Count - Shown on the display as “FE-Ct”.
Counts the number of times floats are out of sequence.
Timer Override Count -Shownonthedisplayas“tO-Ct”.
Counts the number of times the timer override float is activated.
(timed dose only)
Time left in “On” time cycle - Shown on the display
as “t-On”. Counts down the time left in the “On” cycle. (timed
dose only)
Time left in “Off” time cycle - Shown on the display
as “t-OFF”. Counts down the time left in the “Off” cycle. (timed
dose only)
Auxiliary alarm count-Shown on the display as “AL1Ctr”
or “AL2Ctr”.
Countsoptionalauxiliary alarm counts for single phase models.
Counts Pump 1 and Pump 2 fail counts for three phase models
and single phase models with overloads.
Viewing Panel Settings
With control power supplied to panel:
Press button. The display will show t-dOSE for timed
dose applications, or d-dOSE for demand applications.
NEXT
NEXT
NEXT
NEXT
NEXT
NEXT
NEXT
NEXT
NEXT
Program Timer On & Off Times
With control power supplied to panel:
Press and hold button for 3 seconds until Prog is dis-
played.
The display will flash On , then the time in hh:mm:ss.
Setting pump ON (follow Section A)
Section A
Press button to display time in hh:mm:ss.
Press button until desired digit flashes
Press button until desired time is achieved.
Repeat process pressing and buttons until
desired time is reached.
Press button to save.
NEXT
UP
SET
NEXT UP
SET
SET
NEXT
NEXT
NEXT
Press button. The display will show Et 1 count in
hh:mm.
Press button. The display will show CC 1 count.
Press button. The display will show AL1Ctr count.
Cycle count for DuoAlarm 1 option for single phase models. OR
Cycle count for Pump 1 Fail for three phase models and single
phase models with overloads.
Press button. The display will show Et 2 count
(pump 2) in hh:mm. (duplex panels only)
Press button. The display will show CC 2 count.
(pump 2) (duplex panels only)
Press button. The display will show AL2Ctr count.
Cycle count for DuoAlarm 2 option for single phase models. OR
Cycle count for Pump 2 Fail for three phase models and single
phase models with overloads.
Press button. The display will show AL-Ctr alarm
count.
Press button. The display will show FE-Ct float
error count.
Press button. The display will show tO-Ct timer
override count. (timed dose mode only)
Press button, The display will flash On , then the
ON time in hh:mm:ss. (timed dose mode only)
Press button. The display will flash OFF , then the
OFF time in hh:mm:ss. (timed dose mode only)
Press button. The display will flash either t-On or
t-OFF , then the time left in the ON or OFF cycle.
(timed dose mode only)
NEXT

Press and hold button for 3 seconds until run is
displayed.
Timer programming is complete.
Program Pump Sequence
Program Pump sequence “Alt”, “2-1” or “1-2” (duplex only)
With control power supplied to panel:
Press and hold button for 3 seconds until Prog is
displayed.
Press button until ALtErn flashes with either
ALt , 2-1 , or 1-2 flashing.
Press button to display ALt , 2-1 , 1-2 .
Press button until desired sequence is achieved.
Press and hold button for 3 seconds until run is
displayed.
Pump sequence programming is complete.
SET
Setting pump OFF times
Press button. The display will flash OFF and show
the OFF time in hh:mm:ss. Repeat the instructions in
Section A to set OFF times.
NEXT
SET
UP
SET
NEXT
SET
Selecting Time Dose or Demand Dose
-Panels in the field
To set the panel to either Timed Dose or Demand Dose in
the field:
1. Turn the control/alarm power off to the control panel.
2. Turn the pump power off to the control panel.
3. Place a small screwdriver or pen into the slot in the
label on the inner door marked “DEMAND DOSE
TIMED DOSE”.
Move the dip switch (up) for demand dose
Move the dip switch (down) for Timed dose
4. Turn the control/alarm power on to the control panel.
After the display goes blank press the “NEXT” switch.
The display will show d-dose for demand dose.
The display will show t-dose for timed dose.
WARNING: Changing the dip switch positions will
change the operation of the panel.
WARNING: If changing to timed dose, be sure to set
the off and on times.
5. Turn on the pump power after all the settings are
changed.
6. WARNING: Check the panel for correct operation
before leaving the site.
Operations
Float Controls
1. Check the floats during their entire range of operation.
Clean, adjust, replace and repair damaged floats.
2. Measure the float resistance to determine if the float is
operating properly.
To measure float resistance:
a. Isolate the float by disconnecting one or both of the float
leads from the float terminals.
b. Place one ohmmeter lead on one of the float wires, and the
other ohmmeter lead on the other float wire.
c. Set the ohmmeter dial to read ohms and place on the R X
1 scale. With the float in the “off” position, the scale should
read infinity (high resistance), if not replace the float.
With the float in the “on” position, the scale should read close to
zero, if not replace the float. Readings may vary depending
on the accuracy of the measuring device.
Fuse
To check the continuity of the fuse, pull the fuse out of the
fuse holder. With the ohmmeter on the R X 1 scale, measure
resistance. A reading of infinity (high resistance) indicates a
blown fuse that must be replaced with a fuse of the same type,
voltage, and amp rating.
Alarm Light
With power on, hold the test/normal/silence switch in the “test”
position. The alarm light should turn on. If not, replace the light
with that of the same type.
Alarm Horn
With power on, hold the test/normal/silence switch in the “test”
position.The alarm horn shouldturnon. If not, replace the horn
with that of the same type.
Troubleshooting

SJE-RHOMBUS®warrants to the original consumer that this
product shall be free of manufacturing defects for five years after
thedate ofconsumer purchase. Duringthat timeperiod andsubject
to the conditions set forth below, SJE-RHOMBUS®will repair or
replace, for the original consumer, any component which proves
to be defective due to defective materials or workmanship of SJE-
RHOMBUS®.
ELECTRICAL WIRING AND SERVICING OF THIS PRODUCT
MUST BE PERFORMED BY A LICENSED ELECTRICIAN.
THIS WARRANTY DOES NOT APPLY: (A) to damage due to
lightning or conditions beyond the control of SJE-RHOMBUS®; (B)
to defects or malfunctions resulting from failure to properly install,
operate or maintain the unit in accordance with printed instructions
provided; (C) to failures resulting from abuse, misuse, accident, or
negligence; (D) to units which are not installed in accordance with
applicable local codes, ordinances, or accepted trade practices,
and(E) to units repairedand/or modified without prior authorization
from SJE-RHOMBUS®.
Somestatesdo notallow limitationson how longan impliedwarranty
lasts, so the above limitation may not apply to you. Some states do
not allow the exclusion or limitation of incidental or consequential
damages,so the abovelimitation or exclusionmay not applyto you.
Thiswarranty gives you specific legalrights, and youmay also have
other rights which vary from state to state.
TO OBTAIN WARRANTY SERVICE: The consumer shall assume
allresponsibility andexpense forremoval, reinstallation, and freight.
Any item to be repaired or replaced under this warranty must be
returned to SJE-RHOMBUS®, or such place as designated by
SJE-RHOMBUS®.
ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR
FITNESS ARE LIMITED TO THE DURATION OF THIS WRITTEN
WARRANTY. SJE-RHOMBUS®SHALL NOT, IN ANY MANNER,
BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL
DAMAGES AS A RESULT OF A BREACH OF THIS WRITTEN
WARRANTY OR ANY IMPLIED WARRANTY.
SJE-Rhombus®Five-Year Limited Warranty
NOTICE!
Products returned must be cleaned, sanitized, or decontaminated as necessary prior to shipment to ensure that employees
will not be exposed to health hazards in handling said material. All applicable laws and regulations shall apply.
NOTES: __________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________

NOTES: __________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
22650 County Highway 6
P.O. Box 1708
Detroit Lakes, Minnesota 56502 USA
1-888-DIAL-SJE (1-888-342-5753)
Phone: 218-847-1317
Fax: 218-847-4617
Altri manuali per Installer Friendly Series
2
Questo manuale è adatto per i seguenti modelli
1
Indice
Altri manuali SJE Rhombus Pannello di controllo

SJE Rhombus
SJE Rhombus Three Phase Duplex Manuale utente

SJE Rhombus
SJE Rhombus 123 Manuale utente

SJE Rhombus
SJE Rhombus WellZone Manuale utente

SJE Rhombus
SJE Rhombus VS21-10.0-N3RD Manuale utente

SJE Rhombus
SJE Rhombus 124 Manuale utente

SJE Rhombus
SJE Rhombus 115 Manuale operativo e di manutenzione

SJE Rhombus
SJE Rhombus Installer Friendly Series Manuale utente

SJE Rhombus
SJE Rhombus TimeZone Guida alla risoluzione dei problemi

SJE Rhombus
SJE Rhombus 112 Manuale operativo e di manutenzione

SJE Rhombus
SJE Rhombus NEMA 4X Manuale utente