OVER & UNDER VOLTAGE CONTROL RELAY GKM-01 & GKM-11
Voltage control relays are designed to protect devices with
sensitive operating voltage values from failures that may be
caused by mains voltage.
General
Device Usage and Working Principle
Make the connections of the device in accordance with
connection scheme. Set the required settings of the device
according to the operating voltage values of the load. When
the device is energized, if the voltage values are normal
according to the set values, the relay gets activated and the
relay LED ( ) is turned on. When the voltage values go out of
the set values, the related fault LED is on, it waits until the
delay time (DT), after the time has elapsed, the relay gets
de-activated and the relay LED goes out. When the voltages
return to their normal values, the device waits until the reset
time (RT), after the time has elapsed the relay gets activated
and the relay LED is turned on.
Required Settings and Error Notifications
HV Control Knob: High Voltage Set Value, when the voltage rises above
this value, HV LED is on.
LV Control Knob: Low Voltage Set Value, when the voltage drops below
this value, LV LED is on.
DT Control Knob: Delay Time, is the time to wait before entering the
failure.
RT Control Knob: Reset Time, is the time to wait for the relay to pull when
the voltages return to normal.
Switch off the device and release from connections. Clean the trunk of device
with a swab. Don’t use any conductor or chemical might damage the device.
Make sure device works after cleaning.
Maintenance
Warnings
-Please use the device according to the manual.
-Don’t use the device in wet.
-Include a switch and circuit breaker in the assembly.
-Put the switch and circuit breaker nearby the device, operator can reach
easily.
-Mark the switch and circuit breaker as releasing connection for device.
Contact:
Led Notifications By Errors
No error. Voltages are normal.
It counting the delay time
for low voltage error.
Low voltage error.
Error Name
It counting the delay time
for high voltage error.
High voltage error.
LV LED HV LED LED
Led is Off : Led is On:
Technical Specifications
High Voltage :230V-300V + Off (GKM-11),
230V-270V (GKM-01)
MADE IN TURKEY
Document Number: DK-083-2
Low Voltage :150V-210V + Off (GKM-11),
150V-210V (GKM-01)
Delay Time :0,5 sec. - 20 sec.
Reset Time :0,5 sec. - 20 sec.
Operating Power :<6VA
Operating Temp. :-20°C.....+55°C
Display :3x LEDs
Connection Type :Assembled on the din rail.
Weight :<0,080 kg. (GKM-01),
<0,100 kg. (GKM-11)
Contact :5A 250VAC (Resistive Load)
Operating Altitude :<2000m
Cable Diameter :2,5mm²
Nominal Operating
Voltage
220V AC 50/60 Hz.
:
High Voltage Protection - To enter the error state: If the voltage, goes above the high voltage set
value, the HV LED is on, the device waits until the set delay time (DT), after the time has elapsed the
relay gets de-activated and the relay LED is off.
Low Voltage Protection - To enter the error state: If the voltage, goes below the low voltage set
value, the LV LED is on, the device waits until the set delay time (DT), after the time has
elapsed the relay gets de-activated and the relay LED is off.
High Voltage Protection - Exiting the error state: When voltage, lower than 5 volts of the set high
voltage set value, the device waits for the reset time (RT). After the time passes, the HV LED is off,
the relay gets activated and the relay LED is on.
Low Voltage Protection - Exiting the error state: When voltage is higher than 5 volts of the set high
voltage set value, the device waits for the reset time (RT). After the time passes, the LV LED is off,
the relay gets activated and the relay LED is on.
Protection Functions
Relay is Activated: 2 (COM) and 3 (NC) short circuit, 1 (NC) and 2 (COM)
open circuit.
Relay is De-activated: 2 (COM) and 1 (NC) short circuit, 3 (NC) and 2
(COM) open circuit.
Relay Activated/De-activated Status
The Low Voltage Protection function is deactivated when the
LV control knob is set to Off. (It's only on GKM-11.)
The Off stage is limited to 140V. If the voltage falls below
140V while in this stage, the relay is deactivated and the LV
Led is flashes.
The High Voltage Protection function is deactivated when the
HV control knob is set to Off. (It's only on GKM-11.)
Disable to Protection
Connection Diagram & Dimensions for GKM-11
N
2A
12 3
L N
L1
L2
L3
Load
45.4mm
69mm
91mm
35.4mm
28.1mm
49.4mm
17.8mm 65.4mm
15 mm
(Cabling
Distance)
Connection Diagram & Dimensions for GKM-01
Contactor
5mm
N
2A
L1
Load
L2
L3
Contactot
3
N21
L
35,6mm
6,35mm
90mm
94,6mm
34,5mm
49,25mm
57,75mm
45mm
65,8mm
35mm
19 mm
(Cabling distance)