Diff:QD711
Death:QD712
5CH D705 D713 Y705 QD705
6CH D706 D714 Y706 QD706
7CH D707 D715 Y707 QD707
Description:
Start signal(Y):when Y is 0, close P D control, when be 1 , start P D control
Parameter P:Proportion parameter, mainly reflex system’s difference, carry on control as soon as
difference occurs to improve the system’s no difference degree.
Parameter I: ntegral parameter. Mainly used to remove whisht, improve the system’s no difference
degree.
Parameter D:Differential parameter, mainly used to control signal’s changing trend,minish system’s
shake.
Control bound Diff: n the assigned bound, carry on P D control. Beyond the bound, no P D control.
Dead area Death:When the current P D control value compares with the preceding P D control value. f
the difference between them is less than the set dead bound’s value, the module will
abnegate the current P D control value, send the preceding P D control value to the
PLC main unit.
Each parameter’s reference value:Kp=20~100;Ki=5~20;Kd=200~700;D FF=100~200
3.Setting of working mode
1)Expansion’s 0CH~3CH channels have two modes to select: current 0~20mA 、4~20mA , 4CH~7CH
channels have two modes to select, voltage 0~5V 、0~10V. Set via special FLASH data register FC inside
PLC. See the following table:
Module Channel’s D
0CH~3CH 4CH~7CH
1# module FD8250 FD8251
2# module FD8258 FD8259
3# module FD8266 FD8267
4# module FD8274 FD8275
5# module FD8282 FD8283
6# module FD8290 FD8291
7# module FD8298 FD8299
Note:As showed in the preceding table, each register set 4 channels’ mode, each register has 16 bits. From
low bit to high bit, every 4 bits separately set 4 channels’ mode.
Each bit’s definition is showed in the following table:
The following, we take module 1 as example to describe the setting format:
Register FD8250:
Take 1# module as example:
FD8250 H O O O O
0CH
1CH
2CH
3CH
FD8251 H O O O O
4CH
5CH
6CH
7CH