VAMP VAMP 135 Guida rapida

VAMP 135
Over-, under-, residual voltage and
frequency relay
Operation and configuration
instructions
Technical description

VAMP 135 Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP Ltd
2
VAMP 24h support phone : +358 (0)20 53 3264
VM135.EN008

VAMP Ltd Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP 135
VM135.EN008 VAMP 24h support phone : +358 (0)20 53 3264
3
Table of Content
1 General 4
1.1. Relay features......................................................................4
1.2. Operating safety .................................................................5
2 User interface 6
2.1. General.................................................................................6
2.2. Local panel ..........................................................................6
2.2.1. Display .........................................................................
2.2.2. Key pad.......................................................................
2.2.3. Indicators ....................................................................8
3 Local panel operations 9
3.1. Navigation in the menus....................................................9
3.1.1. Function menu table...............................................11
3.1.2. Basic menu structure of protection functions .....12
3.2. Operating levels ................................................................12
3.2.1. Opening operating levels ......................................13
3.2.2. Changing of passwords..........................................13
4 Operating measures 14
4.1. Measured data .................................................................14
4.2. Operation indicators ........................................................15
4.3. Reading of event register ................................................16
4.4. Forced control (Force) .....................................................1
4.5. Setting range limits............................................................18
4.6. Adjusting display contrast and scroll speed .................18
4. . Setting date and time ......................................................18
5 Configuration and parameter setting 19
5.1. Principle of parameter setting ........................................20
5.2. Enabling and disabling protection functions (ENABLE)
.............................................................................................21
5.3. Setting protection function parameters........................21
5.4. Scaling of measuring transformers .................................21
5.5. Configuring digital outputs DOUT...................................22
5.6. Configuring blocking matrix BLOCKING........................22
5. . Configuring the digital input DIGITAL IN ........................22
5.8. Configuring communication protocols COM ..............22
5.9. Analog output mA OUTPUT .............................................24
5.10. Disturbance recorder menu RECORDER ......................24
5.11. Service menu SERVICE.....................................................25
6 PC software 26
6.1. PC user interface...............................................................26
6.1.1. Using the VAMPSET program..................................26
6.2. Remote control connections ..........................................26
7 Commissioning configuration 27
.1. Factory settings..................................................................2
.1.1. Configuration during commissioning....................2
.1.2. Configuration examples.........................................28

VAMP 135 Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP Ltd
4
VAMP 24h support phone : +358 (0)20 53 3264
VM135.EN008
1 General
This part of the manual describes the general functions of the
over-, under-, residual voltage and frequency relay VAMP 13
and includes the relay operation instructions. It also includes
instructions on parameterization and configuration of the relay
and instructions on changing of settings.
The second part of the publication includes detailed protection
function descriptions as well as application examples and
technical data sheets.
The Mounting and Commissioning Instructions are published
in a separate publication, with the code VMMC.EN0xx.
1 1 Relay features
The over-, under-, residual voltage and frequency relay VAMP
13 is ideal for power plant, utility and industrial applications.
It features the following protection functions:
•
Three overvoltage stages
•
Three undervoltage stages
•
Two residual overvoltage stages
•
Two overfrequency stages
•
Two underfrequency stages
•
Circuit breaker failure protection
The VAMP 13 relay can be connected to the system to be
protected using three alternative modes, which are selected
during commissioning. The following modes can be selected:
Line, Line+U
0
and Phase. For more detailed information, see
Chapter 2.2 in this manual and Chapter . in the Technical
description part of this manual.
The VAMP 13 relay is equipped with a voltage measuring
transducer. The output signal of the transducer can be wired to
an external meter or a local automation system. Further VAMP
13 includes a disturbance recorder.
The relay communicates with other systems using common
protocols, such as the Modbus RTU, Profibus DP, Modbus/TCP,
IEC-103 and it can be connected to the fibre-optic SPA bus.

VAMP Ltd Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP 135
VM135.EN008 VAMP 24h support phone : +358 (0)20 53 3264
5
1 2 Operating safety
The terminals on the rear panel of the relay may
carry dangerous voltages, although the auxiliary
voltage is switched off. A live current transformer
secondary circuit must not be opened.
Disconnecting a live circuit may cause dangerous
Disconnecting a live circuit may cause dangerous Disconnecting a live circuit may cause dangerous
Disconnecting a live circuit may cause dangerous
voltages!
voltages!voltages!
voltages! Any operational measurements must be
carried out according to national and local handling
directives and instructions.
Carefully read through the relay operation instructions before
any relay operational measures are carried out.

VAMP 135 Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP Ltd
6
VAMP 24h support phone : +358 (0)20 53 3264
VM135.EN008
2 User interface
2 1 General
The VAMP 13 relay can be controlled in three ways:
•
Locally with the push-buttons on the relay front panel
•
Locally with a PC connected to the serial port on the relay
front panel
•
Via the remote control port on the relay rear panel.
2 2 Local panel
Figure 2.2-1 below shows the location of the components of the
local user interface on the front panel of the relay.
Power
Error
Alarm
Trip
VY 058A
Over- and Undervoltage Relay
31
2
4
VAMP 135
Figure 2.2-1. Relay front panel.
1. Alpha-numerical LED display
2. Key pad
3. LED indicators
4. RS 232 serial communication port for a PC

VAMP Ltd Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP 135
VM135.EN008 VAMP 24h support phone : +358 (0)20 53 3264
2 2 1 Display
The VAMP 13 relay is provided with a clear 10 character
alphanumerical LED display, which normally shows a scrolling
text.
Use the SERVICE/Setup/Bright menu to set the brightness of
the display. The display is dimmed after a preset time.
Use the SERVICE/Setup/ScrolDelay menu to set the scrolling
speed of the display text.
2 2 2 Key pad
Use the key pad and the display to navigate through the menus
and to set the required parameters. The keypad comprises the
following keys:
LEFT, RIGHT, UP, DOWN and the ENTER key.
Figure 2.2.2-1. Components of the key pad.
1. Enter and confirmation key (ENTER)
2. UP/DOWN [INCREASE/DECREASE] arrow keys
(UP/DOWN)
3. LEFT/RIGHT arrow keys [for selection of digit position]
(LEFT/RIGHT)

VAMP 135 Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP Ltd
8
VAMP 24h support phone : +358 (0)20 53 3264
VM135.EN008
2 2 3 Indicators
The relay front panel holds 4 LED indicators:
toimintamerkit
Figure 2.2.3-1. Relay operation indicators.
Relay operation indicators:
Power on
Power onPower on
Power on
auxiliary voltage switched on
Error
ErrorError
Error
self-supervision fault, the self-supervision output relay
operates in parallel with the indicator
Alarm
AlarmAlarm
Alarm
starting of protection stage
Trip
TripTrip
Trip
tripping of protection stage

VAMP Ltd Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP 135
VM135.EN008 VAMP 24h support phone : +358 (0)20 53 3264
9
3 Local panel operations
The local panel can be used to read measured values, set
parameters and configure relay functions. However, please note
that some of the parameters can only be set by means of a PC
connected to the local communication port. Further, some
parameters are factory set.
3 1 Navigation in the menus
All setting, resetting, etc. functions are carried out via menu
functions:
1. Use UP and DOWN arrow keys to move up and down in the
main menu. The active menu is the one seen in the display.
The menu names are shown with their full length or
abbreviated, e.g. U STATUS = status display for the
different voltage stages.
2. Use the RIGHT key to move to the function level of the
required menu, e.g. U> Stat.
Use the LEFT key to cancel the selection.
3. Use the RIGHT key to move to the parameter level of the
selected function, e.g. SCntr.
Use the UP and DOWN keys to scroll through the other
parameters on the same function level.
4. Confirm the selection of setting state of the requested
parameter by pushing ENTER and by entering the
password corresponding to the setting level.
. Push LEFT for at least 2 s to exit from the setting state of a
parameter without changing the setting value or,
6. Push ENTER to confirm and store the parameter setting.

VAMP 135 Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP Ltd
10
VAMP 24h support phone : +358 (0)20 53 3264
VM135.EN008
MAIN MENU SUBMENUS
menurakenne_100sarja
Figure 3.1-1. The principle of the menu structure and navigation in the
menus.