Viatran 350 Manuale utente

1
98MANAL350 Rev.E10/10/14
MODEL 350
SANITARY PRESSURE TRANSMITTER
INSTALLATION MANUAL
3829 Forest Parkway, Suite 500
Wheatfield, NY 14120
Toll Free: 1-800-688-0030
International: 716-629-3800
Fax: 716-693-9162
www.viatran.com

2
98MANAL350 Rev. E10/10/14
PRODUCT OVERVIEW
All information contained in this document is representative of a standard Model 350. If the product you ordered has special
requirements or modifications, refer to the Laser Marked information on the product and your purchase order for possible alteration
to the product’s configuration. Failure to verify product configuration before installation may cause permanent product damage and
in most cases, void the manufacturer’s product warranty. If you are unsure or have questions about your product, please contact
our Application Engineers for assistance.
Remove and retain all instruction manuals and performance certificates that are shipped with the product. These documents
provide important information on the product’s calibration, operation, safety precautions, recommended maintenance, re-calibration
requirements, repair service instructions and warranty information. These documents are updated from time to time as changes to
the product occur and should be reviewed at receipt so that proper and safe installation can occur.
BASIC OPERATION
The Model 350 has been pre-set at the factory for the required output and is referenced to absolute zero (full vacuum). Once
factory set, the product should perform as indicated by the performance certificate and product labeling. In all cases the zero and
span cannot be externally adjusted, hence any deviation from the factory settings would indicate damage to the sensor, electronics
(model dependent), or both. On sealed units, output will go positive with positive pressure applied to the pressure port. For
absolutes, the pressure port must have a full vacuum applied to reach the absolute zero point. After the full vacuum is applied, the
unit will begin to read positive pressure changes as less and less of a vacuum is evident at the pressure port.
INSTALLATION DATA - VIATRAN MODEL 350
Note: The drawing below is for informational purposes only and is not to scale. All dimensions are
nominal, in inches and for reference purposes only.
Tri-Clover Fitting Size “A” Dia. Viatran Size Code
1 1/2” 2.00 HA
2” 2.53 HB
2 1/2” 3.06 HC
Cherry Burrell “I” Line “A” Dia. Viatran Size Code
1 1/2” 2.00 SB
2” 2.64 HL
2 1/2” 3.31 HM
Output:
4-20 mA
Sensor Construction:
Bonded Foil Strain Gage
Wetted Parts:
316SS Cladded or Non-Cladded
Electrical Mating Connection:
Acceptable 18AWG wire termination
connection 1/2” NPT (M)

3
98MANAL350 Rev. E10/10/14
Connection Diagram:
Electrical Connections:
Red: + Signal
Black: - Signal
Green Wire: Case Ground
Note: If the unit is certified for hazardous locations as Intrinsically Safe, use the enclosed connection diagram.
INSTALLATION REQUIREMENTS & CAUTIONS
1. Care should be taken when removing the product with a packing knife or other sharp instrument. Functional damage will occur
if the knife slices the connection wiring or sensing diaphragm.
2. Each transmitter is supplied with a protective cover that should be on the sensing area at all times when the transmitter is not
installed.
3. Internal damage may occur if the transmitter receives a serious shock due to being dropped or struck by a foreign object.
4. Never stand the Model 350 Transmitter up or place it on a rough surface without a protective cover on the sensing area (cap,
boot, clean rubber mat, soft cloth, or foam).
5. Cleaning in place is the recommended process that should be performed as the system or process permits.
6. When shipped in quantities, units should be packaged individually to eliminate possible damage.
7. All electrical & pressure connections should be compatible with the model specifications as outlined in the product installation
datasheet.
8. Installation should occur only after electrical (input power) and line pressure is verified as being off and at zero.
9. The product’s internal electrical circuitry is isolated from case ground. It is not recommended that the case or ground of the unit
be connected to the input, output or calibrate pins of the product or wiring system. Ground loops and line noise will affect the
product’s performance.
10. At no time should an object be pressed against the sensing area to deflect the sensor (to test or simulate pressure), as on
some models permanent damage to the sensing diaphragm may occur.
11. This product cannot be used in sterilization systems asdescribed in the 3A Sanitary Standard 74-06, Section E1.9
12. During product installation, the customer shall supply and verify that all o-rings, gaskets, or seals meet orexceed the
requirements ofthe 3A Sanitary Standard 74-06.
ACCESSORIES - OPTIONAL EQUIPMENT
White Polypropylene Conduit Connection Box .......................................................... 004033.002
Polypropylene Conduit Connection Box with 8 Ft Cable Assy. ................................. 003667.003
Hinged Tri-Clamp - Size - 1.5 ” .................................................................................. 041513MHHM
Gasket (Buna-N) - Size - 1.5 ” ....................................................................................04140MP-U0
Gasket(Teflon) - Size - 1.5 ” ....................................................................................... 04140MP-GI
Hinged Tri-Clamp - Size - 2.0 ” .................................................................................. 042013MHHM
Gasket (Buna-N) - Size - 2.0 ” .................................................................................... 04240MP-U0
Gasket (Teflon) - Size - 2.0 ” ...................................................................................... 04240MP-GI
Hinged Tri-Clamp - Size - 2.5 ” .................................................................................. 042513MHHM
Gasket (Buna-N) - Size- 2.5 ” .....................................................................................04340MP-U0
Gasket(Teflon) - Size - 2.5 ” ........................................................................................04340MP-GI
Digital Indicator (Direct Mount) ………………..................…………..……....………… Consult Factory

4
98MANAL350 Rev. E10/10/14
MAINTENANCE AND REPAIR
All Viatran transmitters have been designed to function free from routine or scheduled maintenance. Simple cleaning of the
electrical connector, pressure port threads and pressure cavity on an as needed basis will provide many years of satisfactory
performance. Protecting the product from continued exposure to moisture or fluids at the electrical connection, breather area
(model dependent) will eliminate premature internal failure of the product. Generally any time the product is removed from service
the connector and pressure port threads should be cleaned and the pressure cavity flushed with a 316SS compatible cleaner to
prevent media buildup. During the cleaning process only a soft, lint-free cloth is recommended. Never use a coarse or stiff bristle
brush to clean media from the diaphragm surface.
It is suggested that the calibration be verified on a usage dependent schedule. If the product is in continuous service 7 days a
week, then calibration verification may be necessary every 6 to 8 months. If the product is in a lab test environment a more lenient
verification schedule would be appropriate. In all instances the performance of the product will depend on the individual application
or process in which it is installed. More continued usage would require a shorter period between calibration verification and product
maintenance.
If a product is perceived to be exhibiting problems, it can be returned to Viatran for analysis and/or repair. It is suggested that only
Viatran personnel attempt repair of the product. Any damage resulting from customer disassembly would result in a loss of
coverage under the warranty policy. All Viatran products are able to be repaired at minimal cost if simple cleaning and precautions
are taken in the handling and application of the product.
Older products returned for repair are updated to current specifications unless the repair cost would outweigh the cost of a new
replacement model. Products returned for repair should include information on the person to contact for repair quote approval, the
individual to contact if Viatran’s technical staff requires additional information during analysis, and a brief description of the problem
associated with the product’s failure.
WARRANTY
Viatran Corporation warrants that its products shall be free from defective workmanship and/or material for a period of twelve (12)
months from the date of shipment, provided that Viatran’s obligation hereunder shall be limited to correcting any defective
workmanship and/or replacing any defective material f.o.b. factory. No allowance will be made for any expense incurred for
correcting any defective workmanship and/or material without written consent by Viatran. This warranty is in lieu of all other
warranties expressed or implied.
REPAIR INSTRUCTIONS
Viatran’s Transmitters are designed to be easily repaired and recalibrated if necessary. If a failure occurs, the transmitter should be
returned to the factory for inspection and testing. Please contact the Customer Support Department at 1-800-688-0030, for a return
tracking number and/or a repair cost estimate. A nominal inspection fee is charged on all units returned to the factory which are not
subsequently repaired.
3829 Forest Parkway, Suite 500
Wheatfield, NY 14120
Toll Free: 1-800-688-0030
International: 716-629-3800
Fax: 716-693-9162
www.viatran.com
solutions@viatran.com
Indice
Altri manuali Viatran Trasmettitore

Viatran
Viatran 544 Manuale di installazione e d'uso

Viatran
Viatran 509 Manuale di installazione e d'uso

Viatran
Viatran 118 Manuale di installazione e d'uso

Viatran
Viatran 246 Manuale di installazione e d'uso

Viatran
Viatran 574 Manuale di installazione e d'uso

Viatran
Viatran 510 Manuale di installazione e d'uso

Viatran
Viatran 517 Manuale di installazione e d'uso

Viatran
Viatran 553 Manuale di installazione e d'uso

Viatran
Viatran 379 Manuale di installazione e d'uso

Viatran
Viatran IDP10-A Manuale per l'uso e la cura