Advanced Axis AX Series Manuale utente

www.advancedco.com
Conventional Zone Module
Installation & Operation Manual

www.advancedco.com2
Table of Contents Page
1INTRODUCTION...................................................................................................................................................3
2INSTALLATION....................................................................................................................................................4
2.1MOUNTING .....................................................................................................................................................4
2.1.1AX-CZM Module with Hardware ..............................................................................................................4
2.1.2AX-009 Enclosure Mounting ....................................................................................................................5
2.1.3AX-CZM Module Mounting in AX-009 Enclosure.....................................................................................6
2.2DIP SWITCH PROGRAMMING ...........................................................................................................................8
2.3AX-CZM MODULE OPERATING MODES ...........................................................................................................9
2.3.1Class B Mode of Operation......................................................................................................................9
2.3.2Class A Mode of Operation......................................................................................................................9
2.4AX-CZM MODULE WIRING .............................................................................................................................9
2.4.1Class A Conventional Zone Wiring ........................................................................................................10
2.4.2Class B Conventional Zone Wiring ........................................................................................................10
2.4.3AX-CZM 24 VDC Power Wiring .............................................................................................................11
2.4.4AX-CZM Reset Input Wiring...................................................................................................................11
2.4.5AX-CZM Host Panel Monitoring Wiring..................................................................................................12
2.4.6Multiple AX-CZM Module Power and Reset Wiring ...............................................................................13
2.4.7Typical Host Panel Monitoring/Control of the AX-CZM Module.............................................................14
3DETECTOR COMPATIBILITY ...........................................................................................................................15
4MODULE SPECIFICATIONS .............................................................................................................................17
Note: Prefix “C” equals Canadian Conventional Zone Module (CAX-CZM)

www.advancedco.com
www.advancedco.com 3
1 Introduction
The AX-CZM (CAX-CZM Canadian ULC version) is Advanced’s conventional zone module that can be monitored
and controlled by any ANSI/UL 864 or ULC S527 Listed fire alarm control panel (Host FACP”). The module
provides monitoring of up to eigth (8) Class B, with programmable end-of-line, or four (4) Class A conventional
zones, and has three Form C relay contacts for signalling an alarm, trouble and, if required, earth/ground fault
condition on a per module basis.
The AX-CZM module gets powered from either the HOST FACP or a regulated, power limited 24 VDC power supply
Listed for Fire Protection Signaling.
Note: The power supply power to the AX-CZM module must be a regulated, power limited 24 VDC power
supply Listed for Fire Protection Signaling.
The AX-CZM module makes use of the Advanced Software Monitoring And Real Time Power Management
(SMART-PM) techniques in order to minimize current requirements under alarm conditions across multiple zones.
This SMART-PM technology results in lower power consumption, and increased fire alarm control panel battery life.
Figure 1
–
A
X-CZM Module

www.advancedco.com4
2 Installation
2.1 Mounting
2.1.1 AX-CZM Module with Hardware
The AX-CZM module is supplied with a terminal designation strip and hardware for mounting in an Advanced AX-
009 enclosure (see figure 2).
Note: The AX-009 enclosure can support two (2) AX-CZM modules (see figure 7).
The AX-CZM module must be earth/grounded; this is normally achieved via the screws used to secure
the module to the enclosure and the enclosure being earth/grounded. Should this not be the case, a
dedicated earth/ground must be provided.
Figure 2 – AX-CZM Module, Terminal Designation Strip and Hardware
AX-
CZM
Terminal
Designation
Strip
Hardware
6 – Hex Standoffs
4 – Screws
Must be
Grounded

www.advancedco.com
www.advancedco.com 5
2.1.2 AX-009 Enclosure Mounting
The AX-009 enclosure can be mounted utilizing the provided three mounting holes or it can be mounted to a single
or double gang electrical box. Refer to the below diagram for enclosure dimensions. When mounting the AX-009
enclosure to the wall use appropriate hardware to secure properly.
When mounting ensure that there is sufficient space to allow the cover to be removed / opened after installation. If
the cover is completely removed, remember to reconnect the earth/ground wire prior to replacing the cover.
Note: The AX-009 enclosure includes seven 7/8” knockouts (4 on top / 3 on bottom) and one 5/8” knockout
(on bottom) for conduit connection.
Figure 3 – AX-009 Enclosure Mounting

www.advancedco.com6
2.1.3 AX-CZM Module Mounting in AX-009 Enclosure
1. Screw the four (4) provided hex standoffs on to the four (4) mounting studs of the AX-009 enclosure as
indicated below.
2. Place the AX-CZM module over the four (4) installed hex standoffs and secure with two (2) screws and
two (2) Hex standoffs (see figure 5).
3. Place the terminal designation strip over the two (2) previously installed Hex standoffs and secure with
the remaining two (2) screws (see figure 6).
Note: The terminal designation strip is printed on both sides, with one indicating Class B wiring
and the other indicating Class A wiring designations. Based on wiring requirements, place the
correct wiring designation facing out.
ON
1
TX
RX
HB
COM N/C N/O COM N/ C N/O COM N/ C N/O
0V 24V
I/P MON
A PBUS B
REL1 / FIRE REL2 / TROUBLE REL3 / EA RTH
Figure 5
–
A
X-CZM Module Mounting
Figure 4 – AX-CZM Module Standoff Mounting

www.advancedco.com
www.advancedco.com 7
4. If a second AX-CZM module is required secure the second AX-CZM module to the right-side mounting
studs in the same manner as was explained with the left-side AX-CZM module (see figure 7).
+ - + -
ZON E 1 ZON E 2
+ - + -
ZON E 1 ZON E 2
+ - + -
ZON E 1 ZON E 2
+ - + -
ZON E 1 ZO N E 2
CLASS B ZONE MONITOR
ALLCIRCUITS ARE POWER LIMITED
ON
1
ON = PBUS MODULE
ON= CLASS A/ OFF =CLASS B
ON= EARTHMONITOR ACTIVE
ADDRESS
SETUP
ON
1
TX
RX
HB
COM N/C N/ O COM N/ C N/O COM N/ C N/O
0V 24V
I/P MON
A PBUS B
REL1/ FIRE REL2/ TROUBLE REL3 / EARTH
+ - + -
ZON E 1 ZON E 2
+ - + -
ZON E 1 ZON E 2
+ - + -
ZON E 1 ZON E 2
+ - + -
ZON E 1 ZO N E 2
CLA SS B ZONE MONITOR
ALLCIRCUITS ARE POWER LIMITED
ON
1
ON = PBUS MODULE
ON= CLASS A/ OFF =CLASS B
ON = E A R TH M ON ITO R A C TI VE
ADDRESS
SETUP
ON
1
TX
RX
HB
COM N/C N/ O COM N/ C N/O COM N/ C N/O
0V 24V
I/P MON
A PBUS B
REL1/ FIRE REL2 / TROUBLE REL3 / EARTH
Figure 7 – Two (2) AX-CZM Modules Mounted in an AX-009 Enclosure
ON
1
TX
RX
HB
COM N/C N/ O COM N/ C N/O COM N/ C N/O
0V 24V
I/P MON
A PB US B
RE L1 / FIRE R E L2 / TROU BLE R E L3 / EA RTH
Figure 6
–
Terminal Designation Strip Mounting

www.advancedco.com8
2.2 DIP Switch Programming
Each AX-CZM module has four DIP switch settings for programming module functionalities. The AX-CZM module
can be setup as eight (8) Class B or four (4) Class A conventional zones, configured for local earth/ground fault
monitoring, if the host panel’s power supply does not provide earth/ground fault detection capabilities, and can be
configured for either 3.9K, 4.7K or 6.8K Class B end-of-line (EOL) monitoring.
AX-CZM Module Default Dip Switch Settings = All OFF:
Segment 7 OFF: Earth/ground fault monitoring is performed by host panel’s power supply. If AX-CZM local
earth/ground fault monitoring is required, slide DIP switch segment 7 to the ON position.
Note: If multiple AX-CZM modules require earth/ground fault monitoring and they are receiving power from
a common power supply source only one (1) of the AX-CZM modules should be set to AX-CZM local
earth/ground fault monitoring. In addition, if an AX-CZM module is performing earth/ground fault
monitoring the earth/ground fault reference impedance is 75K.
Segment 6 OFF: Class B wiring for all conventional zones. If Class A wiring is required, slide DIP switch
segment 6 to the ON position.
Segment 3 – 5 OFF: Unused dip switch segments, position has no relevance, leave in the OFF position.
Segment 1 – 2 OFF: Class B end-of-line (EOL) value 6.8K. If a 4.7K or 3.9K Class B end-of-line is required, set
DIP switch 1 and 2 as indicated below:
DIP 1 DIP 2 Setting
0 (OFF) 0 (OFF) 6.8K (Default)
1 (ON) 0 (OFF) 4.7K
0 (OFF) 1 (ON) 3.9K
1 (ON) 1 (ON) Unused (6.8K)

www.advancedco.com
www.advancedco.com 9
2.3 AX-CZM Module Operating Modes
The AX-CZM module zone circuits are preset to the following operating modes:
2.3.1 Class B Mode of Operation
Zone # Latching Input Alarm Verification Short Circuit = Alarm
1
2
3
4
5 * Non-Latching
6 * Non-Latching
7
8
2.3.2 Class A Mode of Operation
Zone # Latching Input Alarm Verification Short Circuit = Alarm
1
2
3
4 * Non-Latching
* Note: These preconfigured “Non-Latching” zone circuits are not permitted by ANSI/UL864 or ULC S527.
These zones should be considered Not Connected.
2.4 AX-CZM Module Wiring
This equipment is constructed with static sensitive components. Observe anti-static
precautions at all times when handling printed circuit boards. Wear an anti-static
earth/ground strap connected to enclosure earth/ground point.
The AX-CZM module must be earth/grounded; this is normally achieved via the screws used to secure
the module to the enclosure and the enclosure being earth/grounded. Should this not be the case, a
dedicated earth/ground must be provided.
The AX-CZM module offers eight (8) Class B or four (4) Class A conventional zones, and three (3) Form C, relay
outputs (Alarm, Trouble and Earth/Ground Fault). In addition, the AX-CZM module has a resettable input for
resetting latched zone alarm conditions.
ATTENTION
OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC
SENSITIVE DEVICES
Must be
Grounded

www.advancedco.com10
2.4.1 Class A Conventional Zone Wiring
1. Wire out-going conventional zone circuit wiring to “Zone 1, 2, 3 or 4, OUT + and –“. Wire incoming
conventional zone circuit wiring to “Zone 1, 2, 3 or 4, IN + and –“(see figure 8).
2.4.2 Class B Conventional Zone Wiring
1. Wire out-going conventional zone circuit wiring to “Zone 1, 2, 3, 4, 5, 6, 7 or 8, OUT + and –“, and install
a 6.8K end-of-line (EOL) resistor (4.7K or 3.9K based on DIP switch 1 and 2 setting) at the last device
(see figure 9).
Figure 8 – AX-CZM Class A Module Wiring
Figure 9 – AX-CZM Class B Module Wiring
Questo manuale è adatto per i seguenti modelli
2
Indice
Altri manuali Advanced Unità di controllo
Manuali Unità di controllo popolari di altre marche

Festo
Festo Compact Performance CP-FB6-E Manuale elenco delle parti

Elo TouchSystems
Elo TouchSystems DMS-SA19P-EXTME Manuale utente

JS Automation
JS Automation MPC3034A Manuale utente

JAUDT
JAUDT SW GII 6406 Series Guida rapida

Spektrum
Spektrum Air Module System Manuale utente

BOC Edwards
BOC Edwards Q Series Manuale utente