APG RST-5003 Manuale utente

APG
R
Doc #9004240
Rev A1, 05/2016
RST-5003 Control Module
User Manual
Web Enabled Series

ii Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Table of Contents
Introduction ................................................................................................................ iii
Warranty and Warranty Restrictions.................................................................... iv
Chapter 1: Specications and Options..................................................................... 1
Dimensions ........................................................................................................................................1
Specications ................................................................................................................................... 2
Model Number Congurator.......................................................................................................... 3
System Wiring Diagrams ............................................................................................................3-5
Chapter 2: Installation and Removal Procedures and Notes..............................6
Tools Needed..................................................................................................................................... 6
Connection Notes............................................................................................................................. 6
Electrical Installation ..................................................................................................................... 6
Software Setup ............................................................................................................................ 7-11
Removal Instructions ....................................................................................................................11
Chapter 3: Programming with Modbus TCP/IP...................................................12
Modbus Polling via Ethernet with Modbus TCP/IP...........................................................12-13
RST-5003 Generic Modbus Register List................................................................................... 13
Modbus Programming of Individual Sensors.......................................................................... 14
Chapter 4: RST-5003 Embedded Web Server........................................................14
Accessing the RST-5003 Embedded Web Server .................................................................... 14
Navigating the RST-5003 Embedded Web Server ..............................................................14-15
4-20 mA Sensor Input Conguration Submenus.............................................................. 16-29
Modbus Sensor Conguration Registers............................................................................ 30-32
RST-5003 Utility Menus ......................................................................................................... 33-36
Chapter 5: Maintenance ...........................................................................................37
General Care.................................................................................................................................... 37
Repair and Returns........................................................................................................................ 37

iii
Introduction
Thank you for purchasing an RST-5003 Web Enabled Control Module from APG. We appreciate your
business! Please take a few minutes to familiarize yourself with your RST-5003 and this manual.
The RST-5003 Web Enabled Control Module oers a wide degree of integrated, exible, remote and local
control and monitoring for your system. The RST-5003 can control up to 10 APG Modbus sensors--any
combination of level, pressure, magnetostrictive and ultrasonic--along with one 4-20 mA sensor, and two
input or output relay terminals. All readings are available for control and monitoring via TCP/IP for local
or remote network access. The RST-5003 also had exible power options: it can use either POE or an
independent 12-28 VDC power source.
Reading your label
Every APG controller comes with a label that includes the controller’s model number, part number, and
serial number. The RST-5003 label also indicates the default IP address, subnet mask, and mac address.
Please ensure that the model number on your label matches your order.

iv Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Warranty and Warranty Restrictions
This product is covered by APG’s waranty to be free from defects in material and workmanship under
normal use and service of the product for 24 months. For a full explanation of our Warranty, please visit
https://www.apgsensors.com/about-us/terms-conditions. Contact Technical Support to recieve a Return
Material Authorization before shipping your product back.
Scan the QR code below to read the full explanation of our Warranty on your tablet or smartphone.

1
Chapter 1: Specications and Options
• Dimensions
2
4
V
BG
N
D
A
7/8” 4”
4 1/2”

2Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Communications
Digital Output Ethernet TCP/IP Modbus
Ethernet TCP/IP to internal web page
Ethernet TCP/IP to APG-provided website
0-2 Isolated Solid State Relays
Inputs RS-485 Modbus
4-20 mA
0-2 Discrete Switches
Electrical
Operational Supply Voltage (at sensor) 48 VDC via POE (requires injector or switch)
12-28 VDC
Current Draw 40 mA @ 48 VDC
Power Rating 2.0 W Max
Issolated SSRs 120V, 120 mA Max
Accuracy
Resolution 12 bit
Environmental
Operating Temperature -40 to 60°C (-40 to 140°F)
Materials of Construction
Housing Polyamide
Mounting
33 mm Din-Rail
Compatible APG Modbus Senors
Ultrasonic MNU
Magnetostrictive MPX-E1, MPX-R1
Pressure PT-400-L5, PT-400-L31, PT-500-L5, PT-500-L31
Controllers DCR-1006A, MND
• Specications

3
• Model Number Congurator
Model Number: RST - _____
A
A. Model
□ 5003 2 relay outputs
□5013 1 relay output, 1 switch input
□5113 2 switch inputs
External 12-28 VDC Source Wiring
• System Wiring Diagrams
To Network
Connection
Input for supply
voltage when
using a non-POE
power source
To 12-28 VDC
Power Source
2
4
V
4
2
0
G
N
D
G
N
D
RST-5003

4Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
POE (Power over Ethernet) Wiring
POWER
LAN + DC LAN
To Network Connection
To AC
power POE
Power
Injector
Provides 24 VDC
to supply a 4-20 mA
device when the RST
is powered via POE.
2
4
V
4
2
0
G
N
D
G
N
D
RST-5003
NOTE: A POE-enabled
Ethernet switch eliminates
the need for a POE Power
Injector.
2
4
V
B
G
N
D
A
(Ethernet Port)
270 Ω
terminating
resistor at
last sensor
Sensor 3
V+
A
B
GND
Trunk Line
Sensor 1
V+
A
B
GND
Sensor 2
V+
A
B
GND
Use shielded cable
Sensor Line Drops
Equivalent 270 Ω
terminating resistor
internal to RST-5003
Note: Terminating resistor size recommended
based on input resistance of RST-5003. Length
of cable and overall impedence of network may
necessitate a dierent size resistor.
Modbus Sensor Daisy-chain Wiring

5
System Overview - RST-5003 with Modbus and 4-20 mA sensors and Internet Connection
Network / Internet Connection
Computer
on
Local
Network
Computer
on
Internet
MNU Ultrasonic Sensors MP Magnetostrictive Float Level Sensors
4-20 mA Input
(2) Solid State Relays
Modbus
Input
Connection
to
Internet
Server Hosting
Website and
Logged Data
4-20 mA Type Level Sensor
RST-5003

6Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Chapter 2: Installation and Removal Procedures and Notes
• Connection Notes
• Up to 10 Modbus sensors can be connected to the RST-5003 in any combination.
• Only one 4-20 mA sensor can be connected to the RST-5003.
• You do not need any tools to install your RST-5003. Please consult each sensor’s user manual for any
sensor installation notes and instructions.
• Tools Needed
• Connect any 4-20 mA sensor, relays, or switched inputs rst.
• Connect RST to Ethernet/network.
• Connect independant 12-28 VDC supply if not using POE.
• Connect and set up one Modbus sensor at a time.
• Electrical Installation
NOTE: For any APG sensor user manual, please visit http://apgsensors.com/support.
IMPORTANT: Each Modbus sensor must be connected to the network individually and
assigned a unique Sensor Number before the next sensor can be added.
IMPORTANT: Multiple Modbus sensors added to the network simultaneously are all
assigned the same Modbus address/sensor number: 1. Sensors MUST be added to the
network individually.
Altri manuali per RST-5003
1
Indice
Altri manuali APG Unità di controllo
Manuali Unità di controllo popolari di altre marche

Festo
Festo Compact Performance CP-FB6-E Manuale elenco delle parti

Elo TouchSystems
Elo TouchSystems DMS-SA19P-EXTME Manuale utente

JS Automation
JS Automation MPC3034A Manuale utente

JAUDT
JAUDT SW GII 6406 Series Guida rapida

Spektrum
Spektrum Air Module System Manuale utente

BOC Edwards
BOC Edwards Q Series Manuale utente