EN / CZone® Contact 6 PLUS User & Installation Manual
2 DESIGN
• Make a list of all outputs to be wired to the Contact 6 PLUS and assign each of them to one of the 6 channels.
• Ensure all cables are appropriately rated for each assigned load.
• Output connector accepts cable gauges 24AWG – 8AWG (0.5 - 6mm).
• Ensure power supply cable to the Contact 6 PLUS is appropriately rated for the maximum continuous current
of all loads and is fused appropriately to protect the cable.
• Ensure continuous current draw of each connected load does not exceed maximum channel rating of 15A.
• Ensure the maximum continuous current of all loads does not exceed the 60A total module current.
• Install the appropriately rated fuses for each channel.
• Decide if you will add the Contact 6 PLUS to a NMEA2000 Network or install as a standalone system with the
CZone Smart Harness.
• Loads exceeding 15A will require paralleling 2 channels together or an external relay.
3 INSTALLATION
THINGS YOU NEED
• Electrical tools
• Wiring and fuses
• Contact 6 PLUS module
• CZone Waterproof Keypad (if required)
• CZone Smart Harness or NMEA2000 network cables
• 4 x 8G or 10G (4mm or 5mm) self-tapping screws or bolts for mounting the Contact 6 PLUS
ENVIRONMENT
Obey the following stipulations during installation:
• Ensure the Contact 6 PLUS is located in an easily accessible location and indicator LED’s are visible.
• Ensure there is enough clearance above the Contact 6 PLUS to allow the cover to be removed.
• Ensure there is at least 10mm clearance around the sides and top of the Contact 6 PLUS.
• Ensure the Contact 6 PLUS is mounted on a vertical flat surface.
• Ensure there is sufficient space for the wires to exit the product.