Maintenance
We advise that the below is carried out annually as failure to do so may
result in invalidation of warranty. Shut off the water supply to both hot
and cold inlets, before commencing any maintenance work below.
Thermostatic cartridge
To clean the filters, you must first
remove the cartridge from the
housing.
Removing the Cartridge
1. Shut off the water supply to
both inlets at the isolating valves.
Ensure the thermostatic valve has
been successfully isolated.
2. Using a suitably flat tool remove
the screw cover, unscrew and
remove the temperature handle
and pull off the metallic shroud
housing and spacer ring (g 1).
Remove the ceramic/chrome
temperature ring allowing access
to the valve (g 2).
3. Using pliers if required gently
remove temperature stop ring
(essential) (g 2).
4. Turn shower on to check
isolation, please ensure that your
body/hands are not under the flow
of water as there is a potential for
delivery of hot water.
5. Using a 32mm box spanner
unscrew and remove the valve
securing nut then carefully pull
out the thermostatic cartridge
(g 3).
Note: Ensure care is taken as a
small amount of residual water
may escape when removing the
cartridge.
Fig. 2
Fig. 3
Temperature
ring
Securing
nut
Stop ring
Cartridge
Step
Locating
slot
Handle
Screw
cover
Lock
washer
Screw
Spring
washer
Shroud
Spacer ring
Indicator
Fig. 1
Maintenance
Fig. 5
Fig. 4
6. Clean the cartridge filters by
rinsing them under running water
to remove any debris.
7. If there is limescale deposits
then it is recommended to
immerse the cartridge for a few
minutes in 50% white vinegar
+ 50% hot water, brush the
filters gently and then rinse
under running water to clean all
particles. If this is not effective, a
replacement cartridge should be
fitted.
8. Before reassembling the
cartridge, clean its housing with a
wet cloth and grease the O-rings
using a suitable silicone grease.
Insert the thermostatic cartridge
into the body aligning the slot in
the body with the grub screw
(g 4).
9. Screw the securing nut on
and tighten using a box spanner,
careful not to overtighten.
10. Replace the temperature stop
ring on the cartridge with the cold
step located at 7 o’clock (g 5).
11. Turn the water supply on.
12. Check the water temperature to ensure correct commissioning.
See previous section.
13. Replace the ceramic/chrome temperature ring, spacer ring and
shroud with the temperature indicator located at 12 o'clock without
turning the spline of the thermostatic cartridge.
Screw the temperature handle in place using the washers and screw,
replace the screw cover.
O-ring
Locating slot
O-ring
O-ring
Stop ring
Step