Data Aire idap Manuale di istruzioni


Data Aire, Inc. reserves the right to make design changes for the purpose
of product improvement or to withdraw any design without notice.

Table of Contents
I. Introduction.......................................................................................................................4
A. Overview................................................................................................................4
B. Features.................................................................................................................4
C. Applications............................................................................................................4
II. Installation and Setup Procedures....................................................................................4
A. Installation..............................................................................................................4
B. Set-up IP Address In idap Card for Ethernet Connection ......................................4
C. Program IP Address on idap Card Using Display Panel Keypad...........................7
III.CongureidapCardonStart-up.......................................................................................8
A. Program Location, Unit name, Model and Cooling Type. ......................................8
B. CongureaNewIPaddress(Ifnecessary). ..........................................................9
C. CongureEmailonAlarmNotication .................................................................10
D. Set Date and Time ...............................................................................................11
E. ChangingUserNameandPassword...................................................................11
IV. System Monitoring and Control ......................................................................................12
A. View System Status.............................................................................................13
B. View Alarm Message. ..........................................................................................13
C. View Logs, Graphs and Download Log Files.......................................................14
D. View Available Memory of the Card .....................................................................16
E. ViewNetworkIPAddressoftheCard..................................................................16
F. Idap Software Version..........................................................................................17
G. Change Setpoints and Deadbands......................................................................17
H. SystemON/OFFControl......................................................................................18
V. Troubleshooting ..............................................................................................................20

4
I. Introduction
A. Overview
TheDataAireidapCardisanEthernetnetworkcardwithbrowserbasedapplicationsoftwarein-
stalledonthecardallowingastandarddesktoporlaptopPCtocommunicatewiththedap4micro-
processor controller using an open web browser application such as Windows Internet Explorer,
Mozilla Firefox or Google Chrome. The idap card supplies web-management capability by means of
anEthernetnetworkinterfaceformonitoringandcontrolofDataAireprecisioncoolingsystems.The
interface combines a number of features in this strategic monitoring and control product.
B. Features
• Connectionto10MbpsEthernetnetwork
• Webserverforrealtimemonitoringofawiderangeofprecisioncoolingsystemsoperating
parameterssuchasreturnaircondition,dischargeaircondition(optional),systemstatus,
equipment runtimes and alarms.
• Remotemodicationoftheprecisioncoolingsystemsoperationalparametersettingssuchas
temperatureandhumiditysetpoint,systemON/OFFcontrol
• Continuousmonitoringofalarms
• Loggerandgraphs
• Emailalarmnoticationstoallowimmediateactionasaresultofamalfunction.Alsoemail
logger and graphs.
• SupportSNMPv1,v2,BACnetIPandModbusTCP/IPprotocolsforBMS(BuildingMonitoring
System)orBAS(BuildingAutomationSystem)interface.
C. Applications
• Smalldatacenter
• Computerrooms,networkaccessspacesorserverclosets
• Telecommunicationsfacilities
• Medicalequipmentcontrolcenters
• Othersensitiveelectronicapplications
II. Installation and Setup Procedures
A. Installation
1. TurnunitpowerOFF.RemovethecoverofBMScardslotondap4controllerorserialcard
1 slot if it is a Mini dap4 controller.
2. InserttheidapcardtotheBMScard(serialcard1onMinidap4)
3. Install the idap card cover that comes with the card.
B. Set-up IP Address In idap Card for Ethernet Connection
1. Afterinstallingtheidapcardintothedap4controller,turnthedap4backON,gotoMenuG-
NetworkCongandprogramBMSPORT1to“BACnetTCP/IP”protocol,BMSPORT2must
besettoN/A(defaultsetting).
2. To set-up the idap card you will need a laptop or PC with Windows XP or Windows 7 operat-
ing system and a CAT-5 crossover cable between the PC and the dap4 are required. Con-
necttotheidapcardandcongurethecardIPaddress.Seedetailedstepsbelow.

5
3. All idap cards are set up for a DHCP server as default. Follow step 4 to step 12 to enter a
static IP address if it requires.
4. Perform a factory reboot of the card by shutting OFF the
power to the dap4 controller. While pressing and hold-
ingtheResetbuttonoftheidapcard;powerthedap4
controllerbackON.ThestatusLEDwillblinkredand
green rapidly for couple seconds, continue to hold the
Reset button and wait approximately 20 seconds until
thestatusLEDbeginstoslowlyblinkred.Aftertherst
redblink,releasetheResetbutton.ThestatusLEDcon-
tinuestoblink2moretimesfortotalof3redblinks.After
releasingtheResetbutton,waitapproximatelyanother50seconds;andthecardwillnow
defaulttothefactorydefaultIPaddress.ThisdefaultIPaddressonlyworksafterafactory
reboot.Ifdap4isreset,thecardwillgobacktotheIPaddressthatisprogrammedonthe
card.
5. The factory default IP address for the idap card is as follows. IP address – 172.16.0.1
Net Mask – 255.255.0.0 Once you perform the factory reboot on the idap card, you must
nowcongureyourPCIPaddressto172.16.0.*(*anyvalueotherthen1)inordertoconnect
directly to the idap card. Ping the card IP address to verify the connection.
6. After your PC or laptop connects to the idap card, open the Windows Internet Explorer and
enterthecard’sIPaddress(172.16.0.1.)toaccesstheEthernetcardcongurationpage.
7. Whenyougettothewebsiteclickon“GotoAdministrationArea.”Thefollowingpromptwill
be displayed on your PC’s Screen, enter User name: admin, and Password: fadmin. These
are the default User name and Password. They can be changed, see Changing User name
and Password section III-E for details.
8. Afterenteringthecorrectinformationtologontotheidapcard,youwillbetakentothefol-
lowing screen.

6
9.Clickthe“Conguration:tabontheleft.Thenclickonthe“Network”tabacrossthetopofthe
screen. The IP address page will appear.
10.YoumaynowenterorchangetheIPaddress(ifapplicable)byenteringtheIPunderEth0IP
addressMainboxandNetMaskmainbox.ThedefaultsettingisDHCP
11.ClickSubmitafterenteringtheIPaddress.
12.Itwilltakeapproximately5minutesfortheIPaddresschangetotakeeffect.Theidapcard
mayhavetobemanuallyrebootedbycyclingthedap4powerONandOFFiftherebootcom-
mand does not respond. Wait for one minute after the card has been restarted then access

7
thecardusingnewIPaddress.Repeatsteps4to12toconnecttothecardandverifytheIP
address if you cannot connect to the card, use a new IP address. Ping the idap card IP ad-
dress to verify the connection.
C. Program IP Address on idap Card Using dap4 Display Panel Keypad
Note: This procedure applies to dap4 controller with BIOS version 5.18 or later and idap card
withrmwareversionA1.5.0B1.2.4orlater.dap4BIOSversionnumbercanbeviewedon
dap4 menu F - Information.
1.ToprogramtheIPaddresstotheidapcardusingthedap4displaykeypad,simplypressand
holdtheALARMandENTERkeyssimultaneouslyforonesecond,thefollowingscreenwill
appear:
>SYSTEMINFORMATION
LOG DATA
OTHERINFORMATION
FLASH/USBMEMORY
2. UseSelectdownkey(i)tomovethecursortoOTHERINFORMATIONandpressEnter.
This screen will appear:
>IDNUMBERINFO
PCOWEB/NETCONFIG
MEMORIESSTATUS
3. UseSelectdownkey(i)thenEnterkeytoselectPCOWEB/NETCONFIG,thefollowing
screen will appear:
>PCOWEB settings
PCONETsettings
4. PressEnterkeytoselectPCOWEBsettingsoption.Thefollowingscreenwillappear:
DHCP:ON
IPAddress:
---.---.---.---
5. UseEnterkeytomovethecursorthenusethearrowkeystomakechange.Ifyouselect
DHCPON,youcannotenterastaticIPaddress.SelectOFFonDHCPifyouwanttoentera
static address.
6. PressSelectdownkey(i)togotonextpagetoenterNetMaskandGatewayaddressthen
gotothenextpagetoenterDNS1andDNS2addressifnot,pressSelectdown(i)keytogo
to next page.
7. You may enter a BACnet device instance number if BACnet connection required otherwise
pressSelectdownkey(i)togotothenextpage,thescreenwillappear:
PCONETCONFIGENABLE
UpdatepCOweb?NO
8. UseSelectdownkey(i)toselectYESthenpressEnterkeytoconrmthechange.
These screens will show:
PCOwebCONFIGENABLE
Please wait for end of update
Then
PCOwebCONFIGENABLE
Updatecomplete-RebootpCOnettoapplynewsettings

8
9. Restartthedap4toreboottheidapcardandwaitforaboutoneminuteforthedap4andidap
card to complete their reboot process.
10.Connect to idap card using the new IP address. Ping the idap card IP address to verify the
connection.
III. Congure idap Card on Start-up
After establishing the Ethernet connection to the card, open a web browser such as Internet Ex-
plorer(Version10ornewer),MozillaFirefoxorGoogleChrometobrowsethecard.Clickon“Goto
AdministrationArea.”Thefollowingscreenwillappear:
Enter factory default user name admin and factory default password fadminthenclickLogIn.
The System status page will appear with data.
A. Program Location, Unit name, Model and Cooling Type.
Click“Conguration”ontheleftsidetaskbarofthepage,andthenselect“General.”Thefollowing
screen will appear:

9
Enter unit location, unit name that you want to the card to display on the location and unit name on
thelefthandofthemainsystemstatuspage.Nextselecttheoororceilingmodelonmodeltype
checkboxthenselectcoolingtype:DXisforcompressoronlyunit,CWischilledwatercoolingonly
unit and ES is for DX and CW combination unit. These selections will alter the data that displays on
the main System status page. For instance if you select DX cooling type, the CW valve data will not
display. If you select CW the compressor data will not display.
After entering this information, Press F5 on your computer to save and refresh this page, your loca-
tion and unit name will start to appear on your System status page.
B. Congure a New IP address (If necessary).
TochangeIPaddressclickthe“Network,”thisscreenwillappear
EnterthenewIPaddresswhere“Eth0”isonthescreenabove.Thenclick“Submit”buttononthe
bottom of the page. The card should reboot and the new IP address can be used to access the card.
If the card does not automatically reboot, manually reboot the card by resetting the dap4 then use
the new IP address to access the card. If the card is not accessible after changing the IP address,
use factory reboot mentioned in section II-B above to access the card and verify the IP address.

10
C. Congure Email on Alarm Notication
Toconguretheidapcardtoautomaticallysendoutemailsonanalarmevent,clickon“Events
andEmail”menubaronthelefthandsideofthemainSystemstatuspage.Thefollowingscreen
will appear:
The default settings for sending out emails on alarm are shown above. If you do not want a email
sentoutonaparticularalarmmerelyuncheck(clickingonthecheckmarkbox)theevent and send
email boxes in the same row as the alarm description. Email subject and message are easily modi-
edbysimplyclickingintheboxandtypingyourmessage.Toenter/modifyemailrecipients’,click
ontheemailstabthenselect,“Viewandmodifyeventsrecipients,”thefollowingscreenwilldisplay:
Indice
Altri manuali Data Aire Scheda di rete
Manuali Scheda di rete popolari di altre marche

Buffalo
Buffalo AirStation WLI-PCM-L11GP Manuale utente

National Instruments
National Instruments NI 9234 Manuale utente

Hama
Hama 49276 Manuale utente

Linksys
Linksys WCF54G - Wireless-G Compact Flash Card Manuale operativo

Compaq
Compaq Wireless LAN 100 Manuale utente

Bose
Bose PowerMatch Dante Manuale utente