DD Compound Vac Checker Manuale utente

Vac Checkerâ
Digital Vacuum Gauge
Instruction manual

Content
Content
1Safety and waste disposal .......................................................................... 3
1.1 About this document .............................................................................. 3
1.2 Safety .................................................................................................... 3
1.3 Waste disposal ...................................................................................... 4
2Technical data.............................................................................................. 5
3Description of the instrument..................................................................... 7
3.1 Use ........................................................................................................ 7
3.2 Instrument overview............................................................................... 7
3.3 Displays overview .................................................................................. 8
3.4 Control keys overview............................................................................ 9
4Operation.................................................................................................... 10
4.1 Connecting........................................................................................... 10
4.2 Switching instrument on and off........................................................... 10
4.3 Switching background illumination on and off ...................................... 10
4.4 Setting units and AutoOff..................................................................... 11
4.5 Displaying temperature values............................................................. 14
4.6 Field calibration.................................................................................... 14
4.7 Calibration with reference vacuum gauge............................................ 15
5Maintenance............................................................................................... 16
5.1 Changing batteries............................................................................... 16
5.2 Cleaning the instrument....................................................................... 16
6Tips and assistance .................................................................................. 18
6.1 Questions and answers ....................................................................... 18

1Safety and waste disposal
3
1 Safety and waste disposal
1.1 About this document
·The instruction manual is an integral part of the instrument.
·Keep this document throughout the entire operating life of the instrument.
·Always use the complete original instruction manual.
·Please read this instruction manual through carefully and familiarise yourself
with the product before putting it to use.
·Pay particular attention to the safety instructions and warning advice in order
to prevent injury and damage to the product.
1.2 Safety
General safety instructions
·Only operate this instrument in the proper manner, for its intended purpose
and within the parameters specified in the technical data.
·Do not apply any force to open the instrument.
·Do not operate the instrument if there are signs of damage at the housing,
mains unit or connected cables.
·Always comply with the locally valid safety regulations when carrying out
measurements. Dangers may also arise from objects to be measured or the
measuring environment.
·Do not store the product together with solvents.
·Do not use any desiccants.
·Only perform maintenance and repair work on this instrument that is
described in this documentation. Follow the prescribed steps exactly.
·Use only original spare parts from Testo.

1Safety and waste disposal
4
Batteries
·Improper use of batteries may cause the batteries to be destroyed, or lead to
injury due to current surges, fire or escaping chemicals.
·Only use the batteries supplied in accordance with the instructions in the
instruction manual.
·Do not short-circuit the batteries.
·Do not take the batteries apart and do not modify them.
·Do not expose the batteries to heavy impacts, water, fire or temperatures in
excess of 60 °C.
·Do not store the batteries in the proximity of metal objects.
·Do not use any leaky or damaged batteries.
·In the event of contact with battery acid: rinse affected areas thoroughly with
water, and if necessary consult a doctor.
·Take batteries out of the instrument immediately if they are not functioning
properly or if they show signs of overheating.
·Remove all batteries from the instrument if it is to remain unused for a longer
period.
Warnings
Always pay attention to any information denoted by the following warnings.
Implement the precautionary measures specified!
Display
Explanation
WARNING
Indicates possible serious injury.
CAUTION
Indicates possible minor injury.
ATTENTION
Indicates possible damage to equipment.
1.3 Waste disposal
·Dispose of faulty rechargeable batteries and spent batteries in accordance
with the valid legal specifications.
·At the end of its useful life, dispose of the instrument via separate collection
for electro- and electronic devices. Please observe local regulations
concerning waste disposal. Or alternatively return the product to
DD-Compound for disposal.

2Technical data
5
2 Technical data
Feature
Values
Absolute pressure sensor
(absolute)
max. 6 bar (87 psi)
ATTENTION
Pressure exceeded.
Destruction of the absolute pressure
sensor!
-
Do not exceed the maximum value.
Vacuum measuring range
1100 - 0 mbar / 825080 - 0 micron
Sensor overload (relative)
5 bar / 72 psi
Vacuum resolution
0.01 hPa / 10 micron
Vacuum accuracy
(at 22
°C, after field calibration,
confidence level
95%)
- 0 to 1.33 hPa / 0 to 1000 micron: up to
±10 micron
-
0 to 200 hPa / 0 to 150000 micron:
±0.3% FS = ±0.6 hPa
-
200 to 1100 hPa / 150000 to 825080
micron:
±0.3% FS = ±3.3 hPa
Operating temperature
-20 to 50 °C / -4 to 122 °F
Storage temperature
-20 to 50 °C / -4 to 122 °F
Temperature measuring range
-20 to 50 °C / -4 to 122 °F
Temperature resolution
0.1 °C / 0.1 °F
Battery life
2400 h (2x AA) (approx. 130 h with background
illumination activated)
Protection class
IP 42
Parameter
mmHG, Torr, mbar, hPa, micron, inH2O, inHg.
Pa
Measuring cycle
0.5 sec
Sensor
1× absolute pressure sensor
Connections
- 2× 7/16" UNF
- 1x MiniDIN
Warranty
2 years

2Technical data
6
Setting values alarm treshold
Unit
Setting range
Resolution
mbar / hPa
0 - 7,5
0,05
micron
0 - 7500
50

3Description of the instrument
7
3 Description of the instrument
3.1 Use
The Vac Checkerâis a digital vacuum gauge for the precise measurement of
extremely small pressures in the vacuum range. This allows you to monitor the
evacuation (usually during commissioning) of refrigeration systems and heat
pumps.
With the Vac Checkerâ, you can therefore measure the current pressure in a
refrigeration system, and thus gather information about the degree of
dehumidification and the removal of foreign matter (oils, foreign gases, etc.).
A vacuum gauge is always used in conjunction with a vacuum pump (generates
the vacuum). A manifold (analogue or digital) is also often used in order to
obtain controlled access to the refrigeration system.
3.2 Instrument overview
Element
Function
1
MiniDIN probe socket
Cable connection for connecting to the testo 570.
2
Display
Displays instrument status icons, measuring units
and measuring values.
3
Control keys
Instrument operation.
4
Connections 7/16" UNF,
brass
Connection of refrigerant hoses, vacuum pump,
manifold
s, etc.

3Description of the instrument
8
5
Hook
Suspension device
6
Battery compartment
Contains two AA batteries.
3.3 Displays overview
Element
Function
1
Icon [ ]
Displays the remaining battery capacity.
>75%
>50%
>25%
<10%
2
Icon [
]
An alarm threshold is set.
3
Temperature display
- selected, currently measured temperature
-
Measurement parameter:
TH2O = evaporation temperature of water
Tamb = ambient temperature
Dt = temperature difference between
evaporation temperature of water and ambient
temperature
- unit set (°C, °F)
4
Slave Mode
Appears when the Vac Checkerâ, is connected to
a testo 570 via a connecting cable and the
testo
570 is in Evacuation mode.

3Description of the instrument
9
5
Pressure display
Displays the currently measured pressure, the
measurement parameter and the unit set (mmHG,
Torr, mbar, hPa, micron, inH2O, inHg
).
3.4 Control keys overview
Element
Function
1
- Switches to the settings.
- Switches between the set-up options.
2
Switches the display illumination on or off.
3
Switches the instrument on or off.
4
- Switches between the temperature displays.
- Navigates in the Set menu.

4Operation
10
4 Operation
4.1 Connecting
Always use refrigerant hoses that are specifically intended for
evacuations.
1
- Remove sealing caps.
- Connect the
Vac Checkerâ,
to the
circuit.
4.2 Switching instrument on and off
1
- Press
.
ê
The instrument switches on or off.
4.3 Switching background illumination on
and off
1
- Switch the instrument on.
- Press
.
ê
The background illumination switches
on or off.
Indice
Manuali Apparecchiature di prova popolari di altre marche

SMART
SMART KANAAD SBT XTREME 3G Series Manuale utente

Agilent Technologies
Agilent Technologies BERT Serial Manuale utente

Agilent Technologies
Agilent Technologies N3280A Manuale utente

Vernier
Vernier Go Direct Voltage Manuale utente

Lifeloc
Lifeloc R.A.D.A.R. Manuale utente

Fluke
Fluke T5-600 Istruzioni per l'uso e l'installazione