18 19
ELMON relay 32-242
Safety Relay
English
Figure 1: Connecon of mulple sensors; in this example: safety contact edge
8.4 Connecng control circuits
The control circuit to be monitored for Channel 1 is to be connected to the terminal pair 4, 5and the corre-
sponding control circuit for Channel 2 is to be connected to the terminal pair 6, 7.
Thecontrolcircuitsmustbeprotectedbyacorrespondingcircuitbreakerdependingontheratedcurrentor
theratedcurrentinthecontrolcircuitsmustbelimitedtothemaximumvaluebyothermeans.
Therelaycontactmayonlyswitchextralowvoltages(30V).Theswitchingoflowvoltages(230V)
is not permissible.
9. Commissioning and performance tesng
Aeralltheelectricalcontactshavebeenconnectedandthesupplyvoltageswitchedon,theplant/machinery
mustbetestedforproperfunconing.
Followingsuccessfulcommissioningthesafetyoutputs4, 5and 6, 7areacvated(relaycontacts“closed”).
Acvangtheannunciatorresultsinopeningtherelaycontacts.
Thesafetysystemmustbetestedbyqualiedstaatappropriateintervals.Thetesngmustbecomprehen-
siblydocumentedatallmes.Therequirementsoftheplant/machinerymanufacturermustbeobserved
and adhered to.
10. Error diagnosis
Ifthewiringandconnecngupofthesupplyvoltageiscorrect,onlythegreenLEDPowershouldlightup.Ifthe
redLEDlightsupthereisafaultinthesystem,whichcanbeisolatedwiththeaidoftheLED.
* Ifthefaultisnotinthewiring,thefunconingoftheelectronicsmaybecheckedbyngan8.2kΩ
resistancetotheannunciatorinputontherelay.Iftheelectronicsthenworkproperly,theannunciator
mustbetestedwithanohmmeter.Forthistheconneconbetweentheannunciatorandtherelaymust
bedisconnectedandconnectedtoanohmmeter.Withaninacvatedannunciatortheresistanceshould
be8.2kΩ±500Ω.Iftheannunciatorisacvated,theresistanceshouldnotexceed500Ω.
11. Decommissioning and disposal
ProductsmanufacturedbyASOareintendedexclusivelyforcommercialuse(B2B).Attheendoftheirservice
theproductsshouldbedisposedofinaccordancewiththelocal,regionalandnaonalregulaons.ASOwill
bepleasedtocollecttheproductsfordisposalinaccordancewiththeregulaons.
LED Error Error correcon
green LED
Power
does not light up
Supply voltage absent,
toolow
orwronglyconnected.
Testconneconsandsupplyvoltage:
- 24 V AC/DC to terminals 8 9, tolerancerange:±10%
green LED
Power
ashescyclically(pulse)
Internalfaultisshownbythe
number of pulses. See -> Signal displays
red LED
Channel 1 / Channel 2
lights up
The relevant sensor
isrecognisedasacvated.
-Checkconneconsoftherelevantsensors
(pinchedwiring,brilewiringetc.)
-Checksensor*
red LED
Channel 1 / Channel 2
ashesrapidly
Sensorcircuitbroken,
sensor not connected,
connected incorrectly or faulty
-Checkconneconsoftherelevantsensors
(pinchedwiring,brilewiringetc.)
-Checksensor*