7
Commissioning
2.2.2 Direct connection between the PC and the E-RMA
LAN
One option for using your generator with E-RMA LAN module is to make a
direct connection between your generator and your PC. In this case you
should connect the E-RMA LAN module directly to your PC or your laptop.
Proceed as described in the following.
NOTICE!
You must configure your local network on the PC as follows in order to be
able to use the direct connection between the E-RMA LAN and the PC:
► IP address: 192.168.1.10
► Subnet mask: 255.255.255.0
► Gateway IP: 192.168.1.1
NOTICE!
When all of the settings have been entered successfully, you should then
deactivate Engineer mode to prevent any incorrect settings from being en-
tered.
► Now proceed as explained in Chapter 2.2.1 Activating “Engineer” mode. Now
return to User mode again instead of using Engineer mode.
Conditions Integrated and switched on E-RMA LAN module
Network has been configured on your PC
1. Press the Page button.
2. Now select the “Password” option
in the menu.
3. Set up the controller password and
the access code to 0.
This password was previously con-
figured in the factory.
4. Return to the menu and then select
the “CommsSettings” option.
5. Press Enter to confirm and open
the next menu.
6. Use the arrow keys to go to the “IB-
Lite IP Adrr” option.
7. Now check its IP address.
The default setting should be
192.168.1.254. If this is not the
case, change the IP address ac-
cordingly.
8. Now go to the IBLite DHCP and
then the AirGate options in the
same menu.
9. These two menu options must be
DISABLED.