TMT162
8Endress+Hauser
Resource Block
Transducer Block Sensor 1
Transducer Block Sensor 2
Transducer Block Display
Transducer Block Adv. Diag.
Function Block AI1
Function Block AI2
Function Block AI3
Function Block AI4
Function Block AI5
Function Block AI6
Function Block PID
Function Block ISEL
Permanent
Pre-instantiated
Pre-instantiated
Pre-instantiated
Pre-instantiated
35 ms (pre-instantiated)
35 ms (pre-instantiated)
35 ms (pre-instantiated)
35 ms (not instantiated)
35 ms (not instantiated)
35 ms (not instantiated)
100 ms
35 ms
Extended
Manufacturer-specific
Manufacturer-specific
Manufacturer-specific
Manufacturer-specific
Extended
Extended
Extended
Extended
Extended
Extended
Standard
Standard
Short description of blocks
Resource Block The Resource Block contains all the data to uniquely identify and
characterize the device. It corresponds to an electronic nameplate for the
device. In addition to parameters required for operation of the device at the
Fieldbus, the Resource Block provides information such as order code,
device ID, hardware revision, software revision, device release etc.
Transducer Block "Sensor 1" and "Sensor 2" The field transmitter Transducer Blocks contain all the measuring and
device-specific parameters relating to the measurement of the input
variables.
Display Transducer The "Display" Transducer Block parameters enable configuration of the
display.
Advanced Diagnostic All parameters for self-monitoring and diagnostics are grouped in this
Transducer Block.
Analog Input (AI) In the AI function block, the process variables from the Transducer Blocks
are processed for the subsequent automation functions in the control
system (e.g. scaling, limit value processing).
PID This function block contains input channel processing, proportional-
integral-differential control (PID) and analog output channel processing.
Basic closed-control loops, control loops with feedforward control, cascade
control and cascade control with limiting can all be performed.
Input Selector (ISEL) The block for signal selection (Input Selector Block - ISEL) allows you to
select up to four inputs and generates an output based on the configured
action.
PROFIBUS®PA
Profile version 3.01
Supported functions Amendment 2 "Condensed status and diagnostic messages"
Amendment 2 "Identification and Maintenance Functions"
Manufacturer-specific ID.: 1549 (Hex)
Device or bus address 126 (default)
The device or bus address is set either using the configuration software, e.g.
FieldCare or with the DIP switches on the electronics compartment see
page 15.
GSD files Sources of GSD files and device drivers:
• GSD file: www.endress.com (→Download →Software)
• Profile GSD file: www.profibus.com
• FieldCare/DTM: www.endress.com (→Automation →Fieldbus →
Fieldbus device integration)
• SIMATIC PDM: www.endress.com (→Automation →Fieldbus →
Fieldbus device integration) or www.fielddevices.com
Write lock Write lock activated using hardware setting (DIP switch)
Cyclic data exchange
Output data Display value
Input data Process temperature, internal reference temperature
FOUNDATION Fieldbus™