ENERVEX MEC 18 Istruzioni per l'installazione

ENERVEX
MEC 18 MECHANICAL EXHAUST CONTROL
3916010 06.16 Installation & Operating Manual
ENERVEX Inc.
1685 Bluegrass Lakes
Parkway
Alpharetta, GA 30004
USA
P: 770.587.3238
F: 770.587.4731
T: 800.255.2923
www.enervex.com
READ AND SAVE THESE INSTRUCTIONS!

2
3916010 06.16
The MEC 18 Mechanical Exhaust Control is ETL Listed in the U.S. and Canada: under file #302882A
Symbol Legend
The following terms are used throughout this manual to bring
attention to the presence of potential hazards, or to important
information concerning the product.
DANGER: Indicates an imminent hazardous
situation which, if not avoided, will result in death,
serious injury or substantial property damage.
WARNING: Indicates an imminent hazardous
situation which, if not avoided, may result in
personal injury or property damage.
How to use this manual
This installation manual does not contain any system design
documentation. System design documentation is available
from any authorized ENERVEX representative. Accessories,
fans, and variable frequency drives are not covered by
this manual. Please refer to these component’s individual
manuals.
TO REDUCE THE RISK OF FIRE,
ELECTRICAL SHOCK OR INJURY TO
PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit in the manner intended by the manufacturer.
If you have questions, contact the manufacturer at the
address or telephone number listed on the front of the
manual.
2. Before servicing or cleaning the unit, switch off at service
panel and lock service panel to prevent power from being
switched on accidentally.
3. Installation work and electrical wiring must be done by a
qualified person(s) in accordance with applicable codes
and standards.
4. Follow the appliance manufacturer’s guidelines and safety
standards such as those published by the National Fire
Protection Association (NFPA), and the American Society
for Heating, Refrigeration and Air Conditioning Engineers
(ASHRAE), and the local code authorities.
5. This unit must be grounded.

3
3916010 06.16
1. PRODUCT INFORMATION
1.1 Function................................................................. 4
1.2 Shipping ................................................................ 4
1.3 Warranty ................................................................ 4
2. SPECIFICATIONS AND DIMENSIONS
2.1 Dimensions and Capacities.................................... 5
3. MECHANICAL INSTALLATION
3.1 Location................................................................. 6
3.2 Mounting of Control ............................................... 6
3.3 Mounting of Transducer ......................................... 7
3.4 Mounting of Duct Probe......................................... 7
3.5 Connecting Transducer to Duct Probe ................... 7
4. ELECTRICAL INSTALLATION
4.1 General.................................................................. 8
4.2 Continuous Fan Operation ..................................... 9
4.3 Intermittent Fan Operation .......................................... 10
4.4 Connection to a Variable Frequency Drive .................. 12
4.5 Integrated with External PDS ...................................... 13
5. STARTUP AND CONFIGURATION
5.1 General.................................................................. 14
5.2 Setting Operatuing Pressure .................................. 15
6. MAINTENANCE AND TROUBLESHOOTING
6.1 Troubleshooting ..................................................... 16
Content

4
3916010 06.16
1. PRODUCT INFORMATION
1.1 FUNCTION
The ENERVEX MEC 18 is a Mechanical Exhaust Control used to
monitor and maintain a constant pressure in a duct system. This is
achieved by modulating the speed of a fan or ventilator. The MEC
18 can be used with ENERVEX Models EFH, RSV, BESB and BESF.
It can control the fan speed directly or via a Variable Frequency Drive
(VFD). It is a component in the MDVS, Mechanical Dryer Venting
SystemTM and the MBES, Modulating Building Exhaust SystemTM.
The MEC 18 is typically used to control the pressure in duct
systems serving clothes dryers, bathrooms, kitchen hoods and
other building venting applications.
The control monitors the pressure in a duct system via connection
to a pressure sensor (XTP2) , and maintains the pressure by
modulating the fan speed.
The control has an integrated safety system that assures the
appliance shuts down in the event of fan and/or control failure.
The use of the MEC 18 is not restricted to any type of duct or
venting application. When the appliance is activated, the control
sends maximum voltage to the fan or VFD. Once the specified
pressure is achieved, the control regulates the voltage to the fan or
VFD to manintain the specified pressure (the value can be viewed on
the display).
If desired, the control can be interlocked with an appliance. When
the appliance is activated, the control sends maximum voltage to
the fan or VFD. Once the specified pressure is achieved, the control
releases the appliance for operation and continues to regulate the
voltage to the fan or VFD to maintain the specified pressure (the
value can be viewed in the display). In the event of insufficient
pressure, the control assures the appliance(s) shuts down after 15
seconds. When the appliance shuts down, the control turns off the
fan.
The control can be used in one of two ways:
• Interlocked with the appliance to pre-purge the duct prior to
appliance start-up and post-purge the duct for 3 minutes after
appliance shut down, or,
• Set to run the fan continuously.
In most cases, local codes will require continuous fan operation.
The control has an integrated safety function. It can be operated
with a manual reset function (reset button) or an automatic reset
function. All terminal connections are monitored by LED’s for easy
service and troubleshooting.
ENERVEX’s MEC 18 is tested and listed to the Standard for Indus-
trial Control Equipment, UL Standard 508, 16th Ed. and CSA C22.2
No. 14-95 as well as UL378, Standard for Pressure Equipment. It is
also tested and listed as a part of an ETL listed MDVS System (ETL
Report J99*18091-004) for exhausting of lint-laden air from single or
multiple type I and type II residential and commercial clothes dryers
whether electric or gas-fired.
1.2 SHIPPING
Standard packing list
The MEC 18 contains the following:
• MEC 18 control unit
• Pressure transducer (XTP)
• Silicone tubing
• Duct probe
• Jumpers
If other components are shipped, these will appear as separate
items on the shipment packing list.
1.3 WARRANTY
2-Year Factory Warranty. Complete warranty conditions are
available from ENERVEX, Inc.

5
3916010 06.16
2. SPECIFICATIONS
2.1 DIMENSIONS AND CAPACITIES
MEC 18 Control
Power supply V 1x120VAC
Amperage A 6.3
Operating temperature °F/°C -4 to 122 / -20 to 50
Range of operation inWC / Pa 0-0.6 / 0-150
Tolerance inWC / Pa 0.01 / 3 +/-10%
Output Current mA max. 10
Max. Load 120 VAC / 8A
Real-time PID Control Method Infinitely variable
Real-time PID Signal Stability +/- 0.5%
Ramp Up/Down Time Seconds max 20
Output VAC 10-120
VDC 0-10
Dimensions A in / mm 7.17 / 182
B in / mm 7.09 / 180
C in / mm 4.37 / 111
Weight lbs/kg 3.0 / 1.5
EMC standard Emission EN50 081-1
Immunity EN50 082-2
XTP Sensor
Power supply VDC 12-36
Amperage mA <20
Output VDC 0-10
Operating temperature °F / °C 0 to 160 / -18 to 71
Accuracy +/- 0.08%
Dimensions D in / mm 3.70 / 94
E in / mm 5.12 / 130
F in / mm 6.18 / 157
G in / mm 3.13 / 80
Weight lbs / kg .6 / .3
Stack Probe
Dimensions H in / mm 4.25 / 108
I in / mm 3.50 / 89
MEC 18
Specifications
I
A
D
C
E
FBGH
MEC 18
EXHAUST CONTROL
+24V
+24V
COM-0
COM
+24V-+
0-10V-
+0-10V
__
>
Symbols:
Fig. 1-A Fuse holder
Fig. 1-B Alarm-red LED
Fig. 1-C Reset button
Fig. 1-D Set point button
Fig. 1-E Potentiometer for pressure
setting
Fig. 1-F Display
Fig. 1-G LEDs (yellow) showing
increasing/decreasing speed
Fig. 1-H Dipswitch block
Fig. 1-I LEDs (green) showing ON/OFF
status

6
3916010 06.16
3. MECHANICAL INSTALLATION
3.1 LOCATION
The control and transducer must be installed indoors. The
control does not need to be installed in an enclosure. See
Fig. 2 for component connections.
Fig. 2
Fig. 2a
Fig. 3
The transducer cannot be mounted inside an
airtight enclosure. It uses the atmoshpheric
pressure as reference pressure.
XTP Sensor
Max. 300 feet
3.2 MOUNTING OF CONTROL
The control can be mounted directly to a wall or similar.
Remove the cover. The mounting holes are located under the
plastic screws that hold the cover in place. See Fig. 3.
The distance between the control and the transducer should
not exceed three hundred (300) feet.
MEC 18
EXHAUST CONTROL

7
3916010 06.16
3.3 MOUNTING OF TRANSDUCER
Attention must be paid to the location of the transducer. The
transducer can be mounted in any orientation but preferably
with the pressur eports facing down.
The transducer should be mounted within six (6) feet of the
duct probe.
Fig. 4
Fig. 5
3.4 MOUNTING OF DUCT PROBE
The probe (Fig. 2a on page 6) is inserted into the duct or vent
at a point where the pressure is kept constant.
This could be at the appliance outlet, in the common duct or
similar.
Make sure the tip of the tube is flush with the inner wall of
the duct. Protrusion into the duct may affect the reading and
thereby the operation.
3.5 CONNECTING TRANSDUCER TO DUCT PROBE
The transducer (XTP) is connected to the duct probe via a
silicone tube. Connect one end of the silicone tubing to the
duct probe and the other end to the NEGATIVE port of the
transducer as shown in Fig. 5.
+
-
Fron
t

8
3916010 06.16
4. ELECTRICAL INSTALLATION
4.1 GENERAL
The control can be used in one of two ways:
• Interlocked with an appliance so the appliance operation
indirectly controls the fan operation (see Chapter 4.2).
NOTE: This option is not available when used with a VFD.
• Connected so the fan runs continuously independent of
appliance operation (see Chapter 4.3).
In both cases, the control monitors and maintains a
constant pressure.
There are two types of safety systems available:
• Integrated Proven Pressure Switch (standard).
• Integrated Proven Pressure Switch with External Proven
Pressure Switch (accessory) backup (see Chapter 4.4).
MEC 18 is designed for a 1x120VAC power
supply only. Fan output is regulated on the
neutral side and cannot be connected to other
circuits.
!
DANGER
Turn off electrical power before servicing.
Contact with live electric components can cause
shock or death.
Fig. 6
The terminals are connected as shown on Fig. 6:
+24V
+24V
COM-0
COM
+24V-+
0-10V-
+0-10V
__
>
Terminal Use
1 Power Supply-L1
2 Power Supply-N
3 Power Supply-Ground
4-5 Voltage Input from Appliance thermostat
Optocoupler (-) (10-120VAC/CDC
6-7 Voltage Input from Appliance thermostat
Optocoupler (+) (10-120VAC/DC)
8 24VDC power supply to dry set of contacts
(appliance thermostat)
9 0VDC power supply to dry set of contacts
(appliance thermostat)
14 Appliance relay contact-Common (max. 120 VAC, 8
Amps.)
15 Appliance relay contact-Normally Open (max.
120VAC, 8 Amps.)
16 PDS-C (Common) Proven Pressure Switch
17 PDS-NC (Normally Closed) Proven Pressure Switch
18 PDS-NO (Normally Open) Proven Pressure Switch
19 Fan-L1
20 Fan-N (regulating)
21 Fan-Ground
22 XTP-0VDC Power Supply(transducer)
23 XTP-24VDC Power Supply (transducer)
24 XTP-0-10VDC Return Signal (transducer)
25 Control signal 0VDC
26 Control signal 0-10VDC

9
3916010 06.16
4.2 CONTINUOUS FAN OPERATION
For continuous fan operation, connect the fan to the control
as described below.
• Connect a 1x120 VAC power supply to terminals 1, 2 and 3
• Jump terminals 5 and 9.
• Jump terminals 6 and 8.
• Connect the appliance:
- Connect the start signal from the appliance to terminals
14 and 15.
• Connect the fan:
- If using a 1x120V fan, connect it to terminals 19, 20 and
21. Refer Fig. 7 and the fan’s Installation Manual.
- If using a 3-phase fan and VFD, connect the VFD to
terminals 25 and 26 as shown in Fig. 10 and 11.
DO NOT connect the fan directly to the MEC 18 control.
• Connect the transducer (XTP) to terminals 22, 23 and 24.
Fig. 7
MEC 18 Control Board
COMVout Vin

10
3916010 06.16
4.3 INERMITTENT FAN OPERATION
The control can be set up for intermittent operation in one of
two ways:
It can be interlocked directly with the appliance control or
with a dry set of contacts.
Interlock with Appliance
Fig. 8 shows how an appliance control signal (10-120V AC/
DC) is connected to the MEC 18:
• Connect the power supply to terminals 1, 2 and 3.
• Connect the appliance:
- Connect the appliance start signal to terminal 4.
- Jump terminals 5 and 14.
- The start signal to the appliance is now activated by
terminal 15.
- Connect Neutral to terminal 6.
• Connect the fan:
- If using a 1x120V fan, connect the fan to terminals 19,
20 and 21. Make sure the neutral line is dedicated to
the fan and control (term. 20) only. Refer to the fan’s
Installation Manual.
- If using a 3-phase fan and VFD, connect the VFD to
terminals 25 and 26 as shown in Fig. 10 and 11. DO
NOT connect the fan directly to the MEC 18 control.
• Connect the transducer (XTP) to terminals 22, 23 and 24.
Fig. 8
Sample Wiring Diagram - Appliance Interlock
Connection to 120V Fan - Intermittent Operation
MEC 18 Control Board
COMVout Vin
Indice
Manuali Unità di controllo popolari di altre marche

Festo
Festo Compact Performance CP-FB6-E Manuale elenco delle parti

Elo TouchSystems
Elo TouchSystems DMS-SA19P-EXTME Manuale utente

JS Automation
JS Automation MPC3034A Manuale utente

JAUDT
JAUDT SW GII 6406 Series Guida rapida

Spektrum
Spektrum Air Module System Manuale utente

BOC Edwards
BOC Edwards Q Series Manuale utente