010.1220.0719 01.21 Installation & Operating Manual
ENERVEX
BEF 225-800X BOX VENTILATOR
MAKE-UP AIR FOR LAUNDRY ROOMS
TYPE I & II RESIDENTIAL & COMMERCIAL
CLOTHES DRYERS
KITCHEN HOOD, BATHROOM EXHAUST
INTAKE AND EXHAUST APPLICATIONS
FOR MULTI-STORY BUILDINGS
File No. E479840
READ AND SAVE THESE INSTRUCTIONS!

2
010.1220.0719 01.21
Symbol Legend
The following terms are used throughout this manual to bring
attention to the presence of potential hazards, or to important
information concerning the product.
DANGER: Indicates an imminent hazardous
situation which, if not avoided, will result in death,
serious injury or substantial property damage.
WARNING: Indicates an imminent hazardous
situation which, if not avoided, may result in
personal injury or property damage.
DANGER: Indicates an imminent electrical shock
hazard which, if not avoided, will result in death,
serious injury or substantial property damage.
How to use this manual
This installation manual does not contain any system design
documentation. System design documentation is available
from any authorized ENERVEX representative. Accessories,
fans, and variable frequency drives are not covered by
this manual. Please refer to these component’s individual
manuals.
TO REDUCE THE RISK OF FIRE,
ELECTRICAL SHOCK OR INJURY TO
PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit in the manner intended by the manufacturer.
If you have questions, contact the manufacturer at the
address or telephone number listed on the front of the
manual.
2. Before servicing or cleaning the unit, switch off at service
panel and lock service panel to prevent power from being
switched on accidentally.
3. Installation work and electrical wiring must be done by a
qualied person(s) in accordance with applicable codes
and standards.
4. Follow the appliance manufacturer’s guidelines and safety
standards such as those published by the National Fire
Protection Association (NFPA), and the American Society
for Heating, Refrigeration and Air Conditioning Engineers
(ASHRAE), and the local code authorities.
5. This unit must be grounded.
This symbol shows that ENERVEX BEFx Box Ventilators are listed under Category Code ZACT.
UL File E479840

3
010.1220.0719 01.21
1. GENERAL INFORMATION
1.1 Introduction......................................................4
1.3 Components ....................................................4
1.4 Shipping...........................................................5
1.5 Accessories ......................................................5
1.6 Listings .............................................................5
1.7 Warranty ...........................................................5
2. SPECIFICATIONS AND DIMENSIONS
2.1 Specications ...................................................6
3. MECHANICAL INSTALLATION
3.1 Positioning........................................................7
3.2 Door Position....................................................8
3.3 Floor Or Roof Mounting....................................9
3.4 Ceiling Mounting...............................................9
3.5 Connection to Duct...........................................10
3.6 Connection to Flexible Duct ..............................10
3.7 Outdoor Termination.........................................10
3.8 Field Junction Box............................................11
4. ELECTRICAL INSTALLATION
4.1 General.............................................................12
4.2 Motor Controller ...............................................12
4.3 Mounting of EDrive Motor Controller .................13
4.4 Grounding Guidelines........................................13
4.5 EMC Filter Disconnect......................................13
4.6 Electrical Connection of the Motor and EDrive..14
4.7 Motor Terminal Connections.............................14
4.8 Wiring Diagram BEF 225-355x / 1x120V...........14
4.9 Wiring Diagram BEF 225-800x / 3x208-480V...15
4.10 Checking and Changing Rotation of Impeller...15
4.11 Installing a Proven Flow System......................16
5. STARTUP AND CONFIGURATION
5.1 Managing the Keypad.......................................17
5.2 Operating the Display........................................17
5.3 Changing Parameters .......................................18
5.4 Read Only Parameter Access ...........................18
5.5 Resetting Parameters.......................................18
5.6 Resetting a Fault ..............................................18
5.7 LED Display......................................................18
5.8 Start Up Sequence (Auto Tune) ........................19
6. MAINTENANCE AND TROUBLESHOOTING
6.1 Cleaning Intervals..............................................20
6.2 Cleaning ...........................................................20
6.3 Service..............................................................20
6.4 Replacement Parts Ordering.............................21
7. WARRANTY TERMS ......................................22
Content
WARNING
This product is equipped with an electronically
commutated (EC-motor) and can not be
connected directly to ac mains. Motor must
be connected to approved motor controller
to ensure proper function. Failure to use approved motor
controller may result in damage to the motor.
ATTENTION
Ce produit est équipé d’un commutateur électronique
(moteur EC) et ne peut pas être connecté directement au
secteur. Le moteur doit être connecté au contrôleur de
moteur approuvé pour assurer un fonctionnement correct.
Ne pas utiliser le contrôleur de moteur approuvé peut
endommager le moteur.
!

4
010.1220.0719 01.21
1. GENERAL INFORMATION
1.1 introduction
These instructions provide both general guidelines and
special requirements for all parts in the BEFx Ventilator Fan
product line. Before specifying a design or beginning an
installation please carefully review these instructions. Contact
local building or re ofcials about restrictions and installation
inspection in your area.
1.2 Features
The BEFx is a highly efcient box ventilator that uses a
backward curved centrifugal impeller for the movement of air
in exhaust and air supply systems by providing high capacity
at high static pressure. It is designed to exhaust lint-laden air
from multiple Type I and Type II residential and commercial
clothes dryers, exhaust commercial hoods, or to provide
make-up air for laundry or mechanical rooms. The ventilator
cannot be used for transport of large particles. Suitable uses
include, but are not limited to: comfort ventilation, make-up
air for laundry and mechanical rooms, and exhaust and air
supply in kitchens/bathrooms in multi-story, multi-family
buildings. The BEFx box ventilator can be installed indoors
as well as outdoors and used in both intake and exhaust
applications.
The BEFx ventilator housing is made in galvanized steel,
while the impeller is welded aluminum. The design is Type
B, Spark Resistant Construction, completely insulated
against re, noise, condensation and heat with 2” berglass
insulation. A service door is provided to allow easy access
to the motor and impeller. The welded aluminum impeller
is statically and dynamically balanced with permanently
attached balancing weights. The BEFx is equipped with
an extremely energy-efcient, totally enclosed, permanent-
magnet motor of class NEMA Super Premium EISA (IE4).
IP54 Protection Class. Sealed ball bearings. The motor
is protected from overloading, blocking, over and under
voltage, and over-heating by a factory programmed EDrive
motor controller by ENERVEX for optimal operation of the
ventilator.
The BEFx Box Ventilator is a component in the MCAS
Modulating Combustion Air System™, MDVS Mechanical
Dryer Venting System™ and MBES Modulating Building
Exhaust System™.
Exhaust temperature must be above 10°F (-12°C) but should
not exceed 400°F (200°C). The ambient temperature must
be within -20°F (-30°C) and 105°F (40°C).
1.3 Components
The box ventilator comes with the components shown in Fig.
1.
Fig 1
Fig 2
WARNING
The ventilator is not to be used to transport solid
particles, nor in areas where there is a risk of
explosive gases.
!
1. Housing
2. Motor
3. Junction Box
4. Support legs with vibration dampers (2)
5. Kit with Allen key for door locking screws for door hinges
and (4 sheet metal screws for mounting junction box)
6. EDrive
7. Installation Manual

5
010.1220.0719 01.21
1.4 Shipping
BEFx ventilator fan units are shipped on a pallet and
protected by packaging.
Do not place other products or items on top of the
packaging.
After unpacking, the product must be handled in a way to
prevent damage to the collars and the ventilator housing.
The door handle should never be used to lift or carry the fan.
If necessary, the access door can be removed to facilitate
transport.
The ventilator is shipped with the motor installed on the
access door with a dedicated motor controller.
If other components are shipped, they will appear on the
shipment packing list.
NOTE: All fans are shipped with a Field Junction Box
connected via exible conduit.
1.5 Accessories (Optional)
• MEC 24 Exhaust Control
• EBC 30/31 Modulating Pressure Control
• Proven Draft Switch PDS
1.6 Listings
UL705, Standard for Power Ventilators with special
consideration for venting lint-laden air from single or multiple
dryers and CSA 22.2 No. 113, Standard for Fans and
Ventilators.
CSA C22.2 NO. 113-12 Fans and Ventilators Edition 9 -
Revision Date 2012/10/01
UL 705 Standard for Power Ventilators Edition 6 - Revision
Date 2013/12/17
Complies with and meets Type B, Spark Resistant
Construction per AMCA standard 99-0401 classications of
Spark Resistant Construction.
1.7 Warranty
2-year factory warranty (see back cover). Complete warranty
conditions are available from ENERVEX Inc.
WARNING
Never use access door handle as a carrying
handle.
AVERTISSEMENT
N’utilisez jamais la poignée de la porte d’accès comme
poignée de transport.
!
WARNING
This duct fan shall be installed a minimum of
one meter from any accessible opening of the
duct.
AVERTISSEMENT
Ce ventilateur de conduit doit être installé au moins un
mètre d’une ouverture accessible du conduit.
!

6
010.1220.0719 01.21
2. SPECIFICATIONS AND DIMENSIONS
2.1 Specifications
Fan Type
Motor
Voltage Conguration
Motor Rating
Max Speed
Max Motor Torque
EDrive Model
EDrive Rating
Supply Voltage
Power
Max Input Current
Max Output Current
Operating Temperature
A - in / mm
B - in / mm
C - in / mm
D - in / mm
E - in / mm
F - in / mm
G - in / mm
H - in / mm
Weight
BEF 315x
1x120 / 3x240 V
2100 RPM
3.0 Nm
321.2208.1200
321.2208.2200
1x120 / 3x240 V
0.75 kW
15.8 / 5.6 A
4.3 / 4.3 A
22.64 / 575
30.79 / 782
12.60 / 320
7.12 / 181
9.80 / 249
24.41 / 620
11.34 / 288
1.97 / 50
84 lbs / 38 kg
BEF 355x
1x120 / 3x240V
1950 RPM
3.0 Nm
321.2208.1200
321.2208.2200
1x120 / 3x240V
0.75 kW
15.8 / 5.6 A
4.3 4.3 A
25.00 / 635
33.35 / 847
13.11 / 333
7.12 / 181
11.77 / 299
24.41 / 620
12.48 / 317
1.97 / 50
99 lbs / 45 kg
BEF 500x
3x240 / 3x480V
1750 RPM
24.0 Nm
321.2214.2200
321.2214.4200
3x240 / 3x480V
5.5 kW
26.4 / 17.2 A
24.0 / 14.0 A
33.54 / 852
42.36 / 1076
16.42 / 417
9.06 / 230
19.65 / 499
31.50 / 800
16.77 / 426
1.97 / 50
208 lbs /95 kg
BEF 800x
3x480V
1750 RPM
137.9 Nm
321.2220.4200
3x480V
22.0 kW
51.9 A
46.0 A
51.26 / 1302
61.69 / 1567
24.09 / 612
20.83 / 529
35.83 / 910
41.77 / 1061
25.63 / 651
1.97 / 50
652 lbs / 296 kg
BEF 710x
3x480V
1750 RPM
70.0 Nm
321.2220.4200
3x480V
15.0 kW
34.2 A
30.0 A
46.10 / 1171
55.98 / 1422
22.36 / 568
14.57 / 370
31.46 / 799
45.71 / 1161
23.03 / 585
1.97 / 50
385 lbs / 175 kg
BEF 630x
3x240 / 3x480V
1750 RPM
50.0 Nm / 44.0 Nm
321.2218.2200
321.2218.4200
3x240 / 3x480V
11.0 / 7.5 kW
33.3 / 21.2
30.0 / 18.0
41.22 / 1047
41.26 / 1048
20.00 / 508
9.69 / 246
27.83 / 707
37.80 / 960
20.63 / 524
1.97 / 50
357 lbs / 153 kg
BEF 560x
3x240 / 3x480V
1850 RPM
50.0 Nm
321.2216.2200
321.2216.4200
3x240 / 3x480V
5.5 kW
26.4 / 17.2 A
24.0 / 14.0 A
37.09 / 942
45.43 / 1154
17.83 / 453
9.69 / 246
23.82 / 605
37.80 / 960
18.54 / 471
1.97 / 50
264 lbs / 120 kg
BEF 450x
3x240 / 3x480V
1500 RPM
6.0 Nm
321.2212.2200
321.2212.4200
3x240 / 3x480V
1.5 kW
12.1 / 7.5 A
10.5 / 5.8 A
30.60 / 777
39.80 / 1011
15.28 / 388
8.35 / 212
15.83 / 402
31.22 / 793
15.32 / 389
1.97 / 50
142 lbs/ 64.5 kg
Centrifugal
EC - motor
NEMA 3R / IP54
NEMA 4X / IP54
14-122°F / -10-50°C
BEF 225x
1x120 / 3x240 V
3100 RPM
3.0 Nm
321.2206.1200
321.2206.2200
1x120 / 3x240 V
0.75 kW
7.8 / 7.8 A
2.3 / 2.3 A
17.33 / 440
17.36 / 441
10.13 / 257
7.12 / 181
7.84 / 199
20.3 / 509
10.36 / 263
2.00 / 51
60 lbs / 27 kg

7
010.1220.0719 01.21
3. MECHANICAL INSTALLATION
3.1 Positioning
The ventilator can be oriented in multiple positions.
Acceptable ventilator orientations are shown in Fig 3.
The BEFx can be installed indoors and outdoors without any
modications.
Wherever the ventilor is installed, make sure there is
space enough to open the access door to an angle of
approximately 90°, as shown in Fig 4, and to access the
locking screws.
Fig 3
Fig 4
CAUTION
Never operate the ventilator with open access
door
MISE EN GARDE
Ne jamais utiliser le ventilateur avec la porte d’accès
ouverte.
A
C
B
D
90°

8
010.1220.0719 01.21
3.2 Door Position
The ventilator can be oriented in multiple positions.
Acceptable ventilator orientations are shown in Fig 3.
The BEFx can be installed indoors and outdoors without any
modications.
Wherever the ventilor is installed, make sure there is space
enough to be able to open the access door to an angle of
approximately 90°, as shown in Fig 4, and to access the
locking screws.
Fig 4

9
010.1220.0719 01.21
3.3 Floor Or Roof Mounting
To minimize transfer of noise and vibration, the ventilator
unit should be mounted on a level, stable and vibration-free
surface. If mounting on a wooden surface, a cement tile
should be placed on the oor prior to mounting as shown in
Fig 5.
Once the installation location is selected the support legs
must be installed. To facilitate support leg installation, keep
ventilator unit on pallet.
For the standard position (Fig 5), bolt holes are pre-drilled
and support legs should be aligned and secured with the
enclosed hardware.
For all other positions, the legs should be placed in proper
position using variable mounting points.
DO NOT FASTEN THE VENTILATOR TO THE BASE.
The ventilator is tted with sound dampers suited to the
requirements of the operating area.
Fig 5
Fig 6
3.4 Ceiling Mounting
If hung from the ceiling, brackets with eye hooks (not
included) must be installed as shown in Fig. 6..
Ceiling bolts must be properly sized to safely carry weight of
the ventilator unit.

10
010.1220.0719 01.21
3.5 Connection To Duct
The ventilator can be connected to a duct. To acheive
maximum performance with minimal energy consumption,
the ventilator should be connected to the duct system with
the specied lengths of duct before and after the ventilator.
NOTE: The distance “3 x D” is not a requirement. It is a
recommendation that will help achieve maximum performance with
minimal energy consumption
3.6 Connection To Flexible Duct
Flexible duct sections can be used to reduce vibrations in the
duct system. If used, the FLF should be connected between
the fan inlet/outlet and the main duct as shown in Fig 8.
This will decrease system vibration and prevent fan housing
deection.
NOTE: The distance “3 x D” is not a requirement. It is a
recommendation that will help achieve maximum performance with
minimal energy consumption
3.7 Outdoor Termination
The BEFx box ventilator is suitable for outdoor installations. It
can mount directly to the roof or on a roof curb as shown in
Fig. 9 and Fig. 10. When the ventilator is used at an exhaust
termination point, local codes may require a gooseneck to
be installed at the outlet, preventing rain entering into the
ventilator. See Fig. 9.
Fig 8
Fig 7
Fig 9
Questo manuale è adatto per i seguenti modelli
8
Indice
Altri manuali ENERVEX Fan

ENERVEX
ENERVEX RS 009 Istruzioni per l'installazione

ENERVEX
ENERVEX IPVB 300 Istruzioni per l'installazione

ENERVEX
ENERVEX BESF Istruzioni per l'installazione

ENERVEX
ENERVEX PowerStack EPSC Istruzioni per l'installazione

ENERVEX
ENERVEX RSHT009-016 Manuale utente

ENERVEX
ENERVEX RSV Istruzioni per l'installazione