P/N 780101720 3/18 Rev Awww.fieldcontrols.com
This device MUST be installed by a qualified agency in accordance with the manufacturer’s installation instructions.The definition of
a qualified agency is: any individual, firm, corporation or company which either in person or through a representative is engaged in,
and is responsible for, the installation and operation of HVAC appliances, who is experienced in such work, familiar with all the
precautions required, and has complied with all the requirements of the authority having jurisdiction.
READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION.
Installed By:_______________________________________ Phone: _____________________ Installation Date: _____________
Please retain these instructions after installation.
The EvenAir H32 wiring hub is installed at the equipment. It is connected to the T32 or T32WF
thermostat using the existing or new 4-wire thermostat cable that normally connects the thermostat
to the equipment. The equipment is wired directly to the Wiring Hub, The upstairs sensor can be
either a wired or wireless sensor. Wireless sensors require the ER1 radio module that plugs into the
wiring hub. An outdoor temperature sensor can also be used to control fossil fuel heating in a dual
fuel heat pump or to control a whole house fan or economizer.
The EvenAir wiring hub can be used to control humidification and de-humidification, fresh air
intake per ASHRAE 62.2, ERVs or HRVs, whole house fans and economizers.
COMPONENTS: H32 Wiring Hub For Wireless Temperature Sensors
1 or 2 TSER Wireless Sensors
1 ER1 Plugin Radio Module
T32 or T32WF Thermostat
AMJ type Modulating Dampers
1 TS51 or 2 TS52 Wired Temp Sensors
H32
R
INSTALLATION MANUAL
WIRING HUB
Model H32
PN 580011201
Wiring Hub
24VAC, 10VA
Made in USA
C NO O LT SR
F I E L D
R

Screw attaches cover to base.
Cover.
Optional eLink Radio Module plugs into connectors.
24VAC Power Indicator.
Terminals for wiring
to HVAC equipment.
Terminals for upstairs
wired temperature sensor
Terminals for humidifier
Terminals for outdoor temperature sensor
Terminals for ERV/HRV
Terminals for Fresh Air Damper
Terminals for Whole House Fan or Economizer Dampers
Terminals for communicating EvenAir Thermostat
Connector for downstairs living area
plug&play modulating damper
Connector for upstairs sleeping area
plug&play modulating damper.
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
R
C
W/B
O
Y
G
W2/E
Y2
DS
HFR
HFR
SENSORS
TSTAT
LIVING SLEEP
DAMPER DAMPER
WH FAN
FR AIR
DAMPR DAMPR
HVAC
ODT
ODT
SLP
SLP
GND
+5V
SA
SB
OPN
OPN
COM
COM
24V
24V
ERV/HRV
ERV/HRV
Gas/electric equipment with 2-stage heating and 2-stage
cooling or conventional or dual fuel heat pumps with 2
compressor stages and 1 auxiliary heating stage.
One TS51 or two TS52 temperature sensors can be used in the
sleeping area.
One or two TSER wireless temperature sensors can be used in
the sleeping area. The ER1 radio module must be installed in
the wiring hub when wireless sensors are used.
Round or rectangular dampers using the AMJ plug and play
actuator and up to 1 inch static pressure. Up to 6 dampers can
be daisy chained to define the upstairs sleeping area or
downstairs living area.
Wiring hub is powered by 24VAC from the HVAC equipment R
and C terminals.
FEATURES
COMPATIBLE EQUIPMENT
WIRED TEMPERATURE SENSORS
WIRELESS TEMPERATURE SENSORS
MODULATING DAMPERS
POWER
WIRING HUB OVERVIEW
LED indicator.
POWER INDICATOR
Thank you for purchasing the EvenAir System from Field Controls. The EvenAir products are compatible
with any HVAC system having accessible 24VAC terminals.
page 2 of 16 P/N 780101720 3/18 Rev A

CAUTIONS
Use cautions when mounting components to surfaces
that may have concealed wiring beneath the surface.
!
INSTALLATION
Before installing the EvenAir comfort system, turn off
all power to your HVAC system.
Read and follow all instructions carefully.
Follow all local electrical codes during installation. All
wiring must conform to local and national electrical
codes.
i
ATTENTION INSTALLER
Nighttime Airflow Control is defaulted to ON. If
bedrooms are located downstairs, consider turning this
option Off using the User Options if bedrooms are not
on the same trunk.
Fresh Air Control is defaulted to Off and controlled by
Options 20 thru 25.
Whole House Fan or Economizer Control is defaulted
to Off and controlled by Options 30 thru 34.
Humidifier and De-Humidification Control is defaulted
to Off and controlled by Options 40 thru 42.
Airflow Control is defaulted to On and controlled by
Options 50 thru 57.
Install and wire components to the wiring hub.
(See Wiring Diagrams section).
Airflow Control Off Option 50 turns off Airflow Control.
The thermostat controls the system, dampers fully open,
nighttime airflow control is disabled and airflow is no
longer displayed on the thermostat.
User Airflow Control can be enabled using Option 52
User turns off automatic airflow control in the User
Options.
Read entire manual before installing EvenAir products.
When servicing EvenAir system or accessing products,
turn off all power to these items.
Place the thermostat on the subbase. Do not install
batteries. (See T32 or T32WF manual).
Turn power to the HVAC equipment On.
Check for Start Up Messages/Errors.
Set equipment options 1-6 if different than factory
default settings. (see T32 or T32WF manual).
1)
3)
If wireless sensors are used, install the ER1 electronic
receiver module in the wiring hub and set the sensor
number and home number as necessary.
2)
4)
5)
6)
Test the installation by initiating a heating call, cooling
call and fan call.
7)
Install batteries and set the time and day (see T32 or
T32WF manual).
8)
i
Homes with plaster walls with steel lathe may
experience wireless communication interference
when using wireless sensors. Wired sensors are
recommended under those conditions.
ATTACH THE H32 TO THE WALL
Attach the H32 at the equipment to a solid surface as shown
using the screws and wall anchors supplied.
4-5/16 inches
INSTALLER
page 3 of 16 P/N 780101720 3/18 Rev A
Refer to T32 or T32WF manuals for accessing:

Install a modulating damper in the duct supplying air to the
upstairs sleeping area and plug one end of the cable into the
connector marked IN on the AMJ actuator and the other end into
the connector marked SLEEP DAMPER on the Wiring Hub. Install a
second modulating damper in the duct supplying air to the
downstairs living area and plug one end of the cable into the
connector on the AMJ actuator marked IN and the other end into
the connector on the Wiring Hub marked LIVING DAMPER. Each
damper uses 2.4VA of power.
When two or more dampers are required to define the upstairs or
downstairs areas, the second damper may be plugged into the
connector marked OUT on the first damper. Up to 6 dampers
can be connected to define an area. LEDS on the damper
actuator indicate when the damper is fully open (green) or fully
closed (red).
INSTALL UPSTAIRS & DOWNSTAIRS DAMPERS
Ensure that damper installation does not cause
obstruction to the damper blade.
WIRING
Wiring Thermostat to H32 Wiring Hub
Use the existing thermostat cable to wire the EvenAir
commununicating thermostat to the Wiring Hub.
EvenAir
Terminal
5V
GND
SA
SB
Wire Color
Red
White
Blue
Yellow
Wiring Hub
Terminal
5V
GND
SA
SB
Function
24VAC Power
Common
Signal A
Signal B
!
Green LED
Red LED +5V
GND
SB
WIRING HUB
SA
Thermostat Model T32 or T32WF
Existing thermostat cable
in replacement installations.
Wiring Diagram
T32
Wiring Hub Model H32
Warning - Only use plug and play cable provided
with the Dampers. Additional RJ cables in 25 ft.
lengths with connector PNP25C p/n 580011525) is
available for runs of 50, 75 or 100 feet.
!
R
C
W/B
O
Y
G
W2/E
Y2
DS
HFR
HFR
SENSORS
TSTAT
LIVING SLEEP
DAMPER DAMPER
WH FAN
FR AIR
DAMPR DAMPR
HVAC
ODT
ODT
SLP
SLP
GND
+5V
SA
SB
OPN
OPN
COM
COM
24V
24V
ERV/HRV
ERV/HRV
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Warning!
!
Turn the power to the HVAC equipment off before wiring.
INSTALLER
page 4 of 16 P/N 780101720 3/18 Rev A

Wiring H32 to Gas/Electric, 1H/1C
Use 5-conductor, 18 or 20 gage, thermostat cable to wire the
H32 Wiring Hub to the equipment.
H32
Terminal
R
C
W/B
Y
G
Wire Color
Red
Blue
White
Yellow
Green
Equipment
Terminal
R, Rc, Rh
C
W, W1
Y, Y1
G
Function
24VAC Power
Common
Stg1 Heating
Fan
Stg1 Cooling
Use 2-conductor, 18 or 20 gage, thermostat cable to wire from
the H32 Wiring Hub to the sleeping area temperature sensor.
Thermistor
Thermistor
FunctionSensor
Terminal
SNR
SNR
Wire Color
White
Red
H32
Terminal
SLP
SLP
Single
Temperature Sensor
Dual
Temperature Sensors
Place wire between brass washer
and the printed circuit board and
hand tighten screw.
The TS51 or TS52 can be installed
in a single gang box or directly to
the wall using the hardware
provided.
HAND
TIGHTEN
Printed circuit board
Brass washer
Model TS51
Temperature
Sensor
Model TS52
Temperature
Sensor
Model TS52
Temperature
Sensor
Wiring Hub
H32
Wiring Hub
H32
SLP
SLP
SLP
SLP
Wiring H32 to Gas/Electric, 2H/2C
Wiring H32 to Heat Pump, 3H/2C
Use 7-conductor, 18 or 20 gage, thermostat cable.
Use 7-conductor, 18 or 20 gage, thermostat cable.
H32
Terminal
H32
Terminal
R
R
C
C
W/B
W/B
O
Y
Y
G
G
W2/E
W2/E
Y2
Y2
Wire Color
Wire Color
Red
Red
Blue
Blue
White
Not Used
White
Yellow
Yellow
Green
Green
Brown
Brown
Orange
Orange
Equipment
Terminal
Equipment
Terminal
R, Rc, Rh
R, Rc, Rh
C
C
W, W1
Not Used
O
Y, Y1
Y, Y1
G
G
W2
E/W2
Y2
Y2
Function
Function
24VAC Power
24VAC Power
Common
Common
Stg1 Heating
Not Used
Reversing Valve
Fan
Fan
Stg2 Heating
Aux Heating
Stg2 Cooling
Stg2 Compressor
Stg1 Cooling
Stg1 Compressor
Wired Sleeping Area Temperature Sensors
INSTALLER
page 5 of 16 P/N 780101720 3/18 Rev A

The outdoor temperature sensor should be placed in a shaded
location and protected from rain or snow such as under the
eves of a home. Select a location and drill a 5/16-inch
diameter hole to pass the sensor wires through.
Use 2-conductor, 18 or 20 gage, thermostat cable to wire
from the H32 Wiring Hub to the outdoor temperature sensor.
Thermistor
Thermistor
FunctionSensor
Terminal
SNR
SNR
Wire Color
White
Red
H32
Terminal
ODT
ODT
Model TS3
Outdoor
Temperature
Sensor
Wiring Hub
H32
ODT
ODT
ER1 Electronic Receiver
Wiring Hub.
Install the ER1 Electronic Receiver
The ER1 Electronic Receiver plugs into the two 6-pin terminal strips
on the H32 Wiring Hub.
Do not turn power on until AFTER the wireless sensors have
been installed and the sensor numbers set, as shown in the
following steps. The Wiring Hub will automatically detect the
electronic receiver and the sensors being used when powered
up.
USING WIRELESS SENSORS
Before installing the wireless remote temperature sensor, the ER1
Electronic Receiver Module needs to be installed in the Wiring
Hub.
Install Remote Wireless Sensors
The TSER is wireless and powered by two AA
batteries. Two remote temperature sensors can
be used and the temperatures are averaged. For
a single sensor installation, install the sensor on
an interior wall about 4-feet above the floor and
in a location that best senses the upstairs
sleeping area temperature.
For a dual sensor installation, install the sensors
in locations that will best sense the average
upstairs sleeping area temperature, such as the
master bedroom and the bedroom hallway.
Mount the TSER subbase using the screws
provided.
Install two AA batteries as shown.
The TS3 outdoor temperature sensor is required for dual fuel
heat pumps. The wiring hub automatically switches to fossil fuel
heating when the outdoor temperature drops below the OBP,
Outdoor Balance Point temperature. The temperature limit can
be changed using Installer Option 03 (see T32 or T32WF
manual).
Sensor and
Cover
Wire Nuts
Wall
Gasket
Mounting Plate
Mounting Screws
Screw attaches Cover to Mounting Plate.
Outdoor Temperature Sensor
Warning!
!
INSTALLER
page 6 of 16 P/N 780101720 3/18 Rev A

Selecting a Different Home Number
EvenAir Thermostat
Remote Wireless Temperature Sensors
Remote Wireless Bedside Control
When two or more wireless EvenAir installations are within 300-
feet of each other, the EvenAir thermostat and remote wireless
temperature sensors must be set to different Home numbers so
they do not interfere with one another.
Use Installer Option 58 in the thermostat installer manual to set
a new Home number.
Remove one of the batteries to remove power to the sensor.
While pressing the push button switch on the sensor, re-install
the battery. The LED will blink red once, then two rapid blinks,
then three rapid blinks and so on. Release the switch after the
number of blinks corresponding to the Home number to be set.
Changing the Home number does not affect the assignment as
the #1 or #2 sensor (1 to 8).
If a TSRC bedside control is used to control the ECool mode
for a whole house fan or economizer, the Home number in the
TSRC must be set to same home number selected in the
thermostat options. (see the TSRC manual).
Setting Wireless Sensors as #1 or #2 Using the TSRC Wireless Bedside Control
The TSER is factory set as #0 wireless temperature sensor and
must be set to #1. If two temperature sensors are used, set the
address number on the second sensor to #2. The sensor
location needs to be documented for future reference. Use the
removable labels included with the wireless sensor to identify
the sensors as #1 or #2. Place the labels on the front of the
thermostat over the battery cover.
The TSRC can be used to turn Econo
Cooling (ECool) On of Off. The TSRC
can be wall mounted or can sit on a
bedside table.
When the Econo Cool mode (ECool) is
turned On, the installed whole house fan
or Economizer will be activated using the
timer or temperature control.
The TSRC is battery powered and
requires no wiring.
Push Button
Switch
LED Indicator
Press the push button and the LED will blink once, then twice
and repeat this pattern. To set the sensor as the #1 sensor,
release the push button switch after one blink or after two blinks
to set it as #2 sensor. After releasing the push button, the LED
will blink yellow once to indicate successful communication or
blink red indicating that communication was not successful.
1 Blink = #1 Sensor
2 Blinks = #2 Sensor
After setting the sensor number, power can now be applied
to the Wiring Hub. The Wiring Hub will automatically detect
the Radio and the sensors being used when powered up.
!
Outdoors
Link
Menu
ed
Set To
PM
Cool
Indoors
Econo
Cooling
ON
oF
R
The following pages include wiring diagrams and
options for different types of installations:
Wiring Diagram - Installation using wireless temperature
sensors.
Wiring Diagram - Installation using wired temperature
sensors.
Wiring Diagram - Humidifier.
Wiring Diagram - De-Humidification.
Wiring Diagram - Fresh Air Damper.
Option - Indoor Fan Vent Mode.
Wiring Diagram - Whole House Fan
Wiring Diagram - Whole House Ventilation Using Damper
and Equipment Fan
Wiring Diagram - Economizer Using Three Dampers and
Equipment Fan
INSTALLER
WIRING DIAGRAMS
page 7 of 16 P/N 780101720 3/18 Rev A

Modulating
Plug&Play Damper
Sleeping Area Airflow
Modulating
Plug&Play Damper
Living Area Airflow
Optional Second
Battery Powered
Wireless Temperature
Sensor
Battery Powered
Wireless Temperature
Sensor
Optional TS3 Outdoor
Temperature Sensor
HVAC Equipment
EvenAir Thermostat
EvenAir H32 Wiring Hub
T32 or T32WF
Installed at equipment.
Installed in
Wiring Hub
Existing thermostat Wires
25-foot Plug&Play Cables
Supplied with Dampers.
TSER Sensor installed
in Bedroom Hallway.
Required when using
dual fuel heat pumps.
TSER Sensor installed
in Master Bedroom
ER1 Electronic
Receiver Module
Inside
Tu
Day
Upstairs
Auto
Downstairs
Airflow %
HEAT
Schedule
AUTO
FANMENU MODE
Heat
Set To
SYSTEM
AM
4
2
IN
OUT
IN
OUT
P&P
P&P
GND
R
ODT
R
GND
+5V
C
ODT
C
+5V
SA
W/B W/B
SA
SB
0 0
Y Y
G G
W2/E W2/E
Y2 Y2
SB
R
R R
Model TS3
PN 580011306
Temperature Sensor
10K @ 77F
Made in USA
C NO O LT SR
F I E L D
Wiring Diagram, Installation Using Battery Powered, Wireless Temperature Sensors
Model H32
PN 580011202
Wiring Hub
24VAC, 10VA
Made in USA
C NO O LT SR
F I E L D
R
Number of wires used in cable.
4
INSTALLER
page 8 of 16 P/N 780101720 3/18 Rev A
DWG: 780301206

Modulating
Plug&Play Damper
Sleeping Area Airflow
Modulating
Plug&Play Damper
Living Area Airflow
Optional Second
Wired Temperature
Sensor
Wired Temperature
Sensor
Optional TS3 Outdoor
Temperature Sensor
HVAC Equipment
EvenAir Thermostat
EvenAir H32 Wiring Hub
T32 or T32WF
Installed at equipment.
Existing thermostat Wires
25-foot Plug&Play Cables
Supplied with Dampers.
Sensor installed
in Bedroom Hallway.
See Note 1.
Required when using
dual fuel heat pumps.
Sensor installed
in Master Bedroom.
See Note 2.
Note 1
Note 2
Use one TS51 sensor for single sensor installations.
Use two TS52 sensors for dual sensor installations.
Number of wires used in cable.
Inside
Tu
Day
Upstairs
Auto
Downstairs
Airflow %
HEAT
Schedule
AUTO
FANMENU MODE
Heat
Set To
SYSTEM
AM
4
4
2
22
IN
OUT
IN
OUT
P&P
P&P
GND
R
ODT
SLP
R
GND
+5V
C
ODT
SLP
C
+5V
SA
W/B W/B
SA
SB
0 0
Y Y
G G
W2/E W2/E
Y2 Y2
SB
R
Model H32
PN 580011202
Wiring Hub
24VAC, 10VA
Made in USA
C NO O LT SR
F I E L D
R
Model TS3
PN 580011306
Temperature Sensor
10K @ 77F
Made in USA
C NO O LT SR
F I E L D
Wiring Diagram, Installation Using Wired Temperature Sensors
INSTALLER
page 9 of 16 P/N 780101720 3/18 Rev A
R R
DWG: 780301207

Wiring Diagram, Humidifier Wiring Diagram, De-Humidification
Enable Humidifier Operation
Enable Automatic Adjustment
Enable De-Humidification
HFR DS
Humidifier HVAC Equipment
HDS*
* Equipment terminal can be designated DS, BK, ODD or DHUM
HFR H
Model H32
Model H32
PN 580011202
PN 580011202
Wiring Hub
Wiring Hub
24VAC, 10VA
24VAC, 10VA
Made in USA
Made in USA
C
C
N
N
O
O
O
O
L
L
T
T
S
S
R
R
F
F
I
I
E
E
L
L
D
D
R
R
Dry relay contacts (HFR and HFR) are provided for controlling a
humidifier. A call for humidification is only made during a
heating call if Option 40 is set to On. If Auto RH mode is set to
On using Option 41, the Outdoor Temperature Sensor must be
installed. In Auto mode, the RH setpoint is automatically
decreased at outdoor temperatures below 35F.
Some HVAC equipment is supplied with an input terminal that
forces the equipment fan into low speed to extract more
moisture from the air during cooling calls. The equipment
terminal can be designated as DS, BK, ODD or DHUM. The
Wiring Hub DS terminal is normally 24 VAC and goes to 0VAC
when de-humidification is active. Option 42 turns de-
humidification On or Off.
Select ON if a Humidifier is installed.
Factory Default: OFF. Range: On or Off.
Option
NEXT ENTER
If automatic adjustment is set to On, the RH
setpoint will decrease at outdoor temperatures
below 35F. The RH Setpoint is reduced 1% for
each 2F below 35F. Requires Outdoor
temperature sensor be installed.
Factory Default: OFF. Range: On or Off.
Option
NEXT ENTER
Select if de-humification is used during
cooling calls.
If de-humidification is On and the humidity is
above the setpoint, the DSBK terminal on the
Wiring Hub will be set to 0VAC to force the
indoor fan to operature at low speed to
remove moisture.
Factory Default: OFF. Range: On or Off.
Option
NEXT ENTER
See T32 or T32WF Manual, Installer Options Section
See T32 or T32WF Manual, Installer Options Section
INSTALLER
page 10 of 16 P/N 780101720 3/18 Rev A
DWG: 780301210
S2000 *
S2020 *
* Models S2000 and S2020 are Field Controls humidifier products.
Indice
Altri manuali Field Controls Interruttore

Field Controls
Field Controls 46178400 Manuale utente

Field Controls
Field Controls WMO-1 Manuale utente

Field Controls
Field Controls 46114900 Manuale utente

Field Controls
Field Controls 46170300 Istruzioni per il montaggio

Field Controls
Field Controls 46457600 Manuale operativo e di manutenzione

Field Controls
Field Controls 46112100 Manuale utente

Field Controls
Field Controls 46091800 Manuale utente

Field Controls
Field Controls LS-140A Manuale utente

Field Controls
Field Controls 46094300 Manuale utente

Field Controls
Field Controls 46149200 Manuale utente