GEZE TSA 160 Manuale tecnico

1
GEZE
PlanungsunterlageTSA160Datei84338PuTSA160_GB_200999_.p65
TSA 160
GB
Swing Door Drive forAutomatic Doors
Planning document

2
PlanungsunterlageTSA160Datei84338PuTSA160_GB_200999_.p65
MATERIALPRÜFUNGSAMT NORDRHEIN-WESTFALEN
Prüfstelle,ÜberwachungsstelleundZertifizierungsstellegemäß§28BauONW
CERTIFICATE OF CONFORMITY
Reg.-No. 12 9820 - DO 14.1
This is to certify in accordance with § 22 para.2 No. 2 of the Building Code (Landesbauordnung) for the Land
Baden-Württemberg, that
thebuildingproducts: Swing door drive ‘’GEZE TSA 160 ’’ complies with
the requirements
• set forth by the technical rules in accordance with the Technical Schedule Apart 1 (edition 98/2),
consecutive number 6.14 of DIN 18 263-4
the manufacturer: GEZEGmbH
Postfach 1263
D-71229 Leonberg
the production plant: GEZEGmbH
Reinhold-Vöster-Str. 21-29
D-71229 Leonberg
in accordance with the results of the
• product tests carried through by the MPA NRW
• internal product control carried through by the producer
• foreign control carried through by the MPANRW
The manufacturer is therefore entitled to mark the building products, the packing or the delivery note with the
sign of conformity (Ü-sign) in accordance with the ordinance regulating conformity signs.
Dortmund, 12.12.2000
Marsbruchstraße 186 • Dortmund-Aplerbeck • Postanschrift: 44285 Dortmund • Telefon (0231) 4502-0 • Telefax (0231) 4502 586

3
GEZE
PlanungsunterlageTSA160Datei84338PuTSA160_GB_200999_.p65
Contents
Fields of application 4
Product features 5
List of product variants 6
Swing door drive for smoke and fire-proof doors TSA 160 F 7
Accessories for TSA 160 F on fire-proof doors 8
TSA160Invers and TSA 160 Z Invers 9
TSA 160 WC-compartments for the handicapped 10
Description of drive 11
System description 14
Technical Features 15
Connection possibilities for actuation elements 16
Safety sensors 17
Side view and installation dimensions TSA 160 18
Side view and installation dimensions TSA 160 and TSA 160 F-IS 20
Side view and installation dimensions TSA 160 pulling 22
Side view and installation dimensions, 1- and 2- leafs
TSA160ZandTSA160Z-IS 24
Cable plan single-leaf door 26
Cable plan single-leaf smoke and fire-proof door,
incl. central smoke control unit 27
Cable plan double-leaf door incl. integrated closer control 28
Cable plan double-leaf door incl. central smoke control unit 29
Cable plan single and double-leaf with door control unit TZ 220 30
Cable plan TSA 160 WC-compartment for the handicapped 31

4
PlanungsunterlageTSA160Datei84338PuTSA160_GB_200999_.p65
Fields of application
Wherehelpisneeded:
Hospitals,rehabilitationcentres
Old-peopleshomes as wellas homesandworkshops fordisabled persons
Publicbuildings,airports,stations
Canteens,waiter’sswingingdoors
Schools,kindergardens
Whereenergyhastobesaved:
Exterior doors, corridor end doors
Draught-proofsystems
Workshops,ateliers,studios
Wherehygieneisrequired:
Foodmanufacturingshops,pharmaceuticalindustry
Hospitals,surgeries
Social rooms, toilets
Wheresafetyisthefirstpriority:
Forsafetylocksand accesscontrol
Forfire preventionpurposes (fireand smokeprevention) typeTSA 160F on
single-leafanddouble-leafdoors
Wherecomfortisthechoice:
Inshops
Inbanks
Inpublicbuildings

5
GEZE
PlanungsunterlageTSA160Datei84338PuTSA160_GB_200999_.p65
Product features
TSA160isanelectronicallycontrolled,electrohydraulicswingdoordrive.
Openingiseffectedbyahydraulicpumpsystem.Theclosingprocessiseffectedbya
closingspringmechanismandadjustablehydraulicvalves.
Smallexterior dimensions,i.e. thedrive canalso beinstalled withlimited space
conditions.
The closing force is infinitely variable from EN size 3 to 6 acc. to EN 1154 for diffe-
rentleafwidths.
Max.leafwidth1400mm
Max. door weight 250 kg
Systemscanbeusedfor eitherpushing orpulling versions(hingesideandopposite
hingeside)
Forsingle-leafdoors
TSA 160
onlyonesystemfordoorDINleftorDINright(retrofittable)andusableforeither
pullingorpushingversion
TSA 160 F
forsmokeandfire-proofdoors,pushing
Fordouble-leafdoors
Intermediate cover possible
TSA 160 - IS
includinginvisibleclosingsequenzcontrol,concealedunderthecover
TSA 160 F - IS
for smoke and fire-proof doors
TSA 160 - IS / TS
automatic2ndclosingleaf,1stclosingleafwithdoorcloserfunction”permanently
open”only.
Themotorisactivatedbyanelectronicsystem:
Start-upasrequiredincl.evaluationofthesensorsandthecontrolunitsintheperiphery.
Samesystemforalldoorsinthehouse(single-leaf,double-leaf,fire-proofdoorsetc.)
reducesmaintenance andinstallation workas wellas stockkeepingof spare partsfor
mechanicalequipment.

6
PlanungsunterlageTSA160Datei84338PuTSA160_GB_200999_.p65
List of product variants
Swing door drive for interior and exterior doors
TSA 160
pulling or pushing
for single-leaf or double-leaf
single-action doors
TSA160pulling + TSA 160pushing
for double-motion, double-leaf doors
TSA 160 - IS
pushingorpullingincl.integratedcloser
controlondouble-leafdoors
TSA 160 / 162
as”master/slave”combinationwithonlyone
combinedcontrolforbothdrivesof
double-leafdoors
TSA 160 - IS / TS
pushingorpullingincl.integratedclosercontrol.
2ndclosingleafincl.automaticfunction,
1stclosingleafincl.doorcloserfunctionand
permanently-openposition
Hinge side, pulling
incl. guide rail
Opposite hinge side, pushing
incl.linkage
Hinge side pulling incl. guide rail
Opposite hinge side pushing incl. linkage
Opposite hinge side pushing
incl.linkage Hinge side, pulling
incl. guide rail

7
GEZE
PlanungsunterlageTSA160Datei84338PuTSA160_GB_200999_.p65
Swing door drive for smoke and fire-proof doors
TSA 160 F
TheTSA160Fis ahold-open mechanisminaccordancewiththe guidelinesfor hold-open
systemsissuedbyDIBt*)
Thedrivesystemisusedtoautomaticallyopenandclosefire-proofdoors.Thesystemcanbe
actuatedviatheusualpulsegenerators.Besidesautomaticopeningandclosing,thedoors
can also be held in an open position.
Inthecaseoffire,theautomaticfunctionorthehold-openfunctionmustbeswitchedoffbya
correspondingfire alarm system.The mains cableis interrupted byamains PCboardfor
powercutoff(F-accessories)andthenormaldoorclosingfunctionthedriveismaintained.
Doorcloserswithautomaticopeningfunction(swingdoordrive)inaccordancewith
DIN18263part4arethereforean integralpartofhold-open mechanismsandrequire
approvalbythebuildingsupervisionauthorities.
TSA 160 F
pushingincl.DIBt-approvalfortheuseon
single-leafsmokeandfire-proofdoors.
TSA 160 F-IS
pushingincl.integratedclosercontrol;
incl.DIBt-approvalfortheuseon
double-leafdoors.
TSA 160 F - IS / TS
pushingincl.integratedclosercontrol;
incl.DIBt-approvalfortheuseondouble-leaf
doors,2ndclosingleafincl.automaticfunction
1stclosingleafincl.doorcloserfunctionand
permanently-openposition.
*) DIBt: German Institute for Structural Engineering (Deutsches Institut für Bautechnik)

8
PlanungsunterlageTSA160Datei84338PuTSA160_GB_200999_.p65
Accessories for TSA 160 F on fire-proof doors
For
TSA 160 F
TSA 160 F - IS
TSA 160 F - IS / TS
thefollowingitemsare requiredfortheuseonfire-proofdoors:
Smokeswitchwithenergysupplye.g.RSZ6
probably additional smoke detectors in accordance with the guidelines for hold-
openmechanisms
break key (manually operated release button) in accordance with the guidelines
for hold-open
electric door opener, approved for fire-proof doors (customer)
MountingplateTSA160
Electric door
opener
Interrupter
button Actuation
button
Emergency
cut-out
RSZ6

9
GEZE
PlanungsunterlageTSA160Datei84338PuTSA160_GB_200999_.p65
TSA 160 Invers and TSA 160 Z Invers
Functional description
Singleordouble-leaf doors are kept close by theescaperoute locking
mechanism. The door is monitored via an emergency exit system
which controls all safety-relevant functions. The doors are electro-
hydraulically closed and opened through spring force. This ensures
that the doors can be reliably opened and kept permanently open in
the case of power failure.
Automaticfunction
The system is released at the emergency exit system via the key-operated switch (or e.g.
card reader), which activates the actuation elements of the automatic door drives. As soon
as the sensors respond, the drives open
the doors through spring force. Upon
lapse of the pre-set hold-open time, the
doors close automatically with all safety
elements being active. This means that
the sensors will stop the movement of the
door if a person is within the swing of the
door and the door will not close until the
obstacle has been removed.
Smoke/heat extracting system – fresh air
If an alarm has been released by the
smoke detector or the fire alarm system
the doors are immediately unlocked and
mechanically opened to allow secure
smoke extraction. The doors remain open
until the alarm has been reset.
Escape way function
If the red emergency button is operated by a
fleeing person, the doors are immediately
unlocked and mechanically opened through
spring force. Thus the escape route is free. The
operation of the emergency button at the same
time releases an alarm which is transmitted to
the control centre.
Smoke/heat extracting system
View of the door: opposite hinge side featuring
TSA 160 Z Invers
BURG
NOTTASTE
NurbeiGefahr betätigen
BURG
NOTTASTE
NurbeiGefahr betätigen

10
PlanungsunterlageTSA160Datei84338PuTSA160_GB_200999_.p65
TSA 160 WC-compartments for the handicapped
Functional description
Afterthepad switchhadbeenoperated,thetoiletdooropensandcloses automaticallyuponlapse
ofapresettablehold-opentime.
Byoperatingthechangeoverswitchinsidethetoiletcabin,theuseractivatestheilluminatedsign
“OCCUPIED“outsidethecompartmentaswellasthecontrollampatthechangeoverswitch.
Simultaneouslytheinteriorandexteriorpadswitchisswitchedoff.Thusthedoorcanneitherbe
openedbyathirdpersonnorbytheuserhimselfbyaccident.
Thelivedooropenerpreventsthatthedoorscanbeopenedmanually.
Toleavethelavatory,theuseragainoperatesthechangeoverswitch;thesign“OCCUPIED“out-
sidethecompartmentaswellasthe
controllampgoout.
Byoperatingthe interiorpadswitch
“DOOROPEN“,thedoorwillimmediately
open.
Inthecaseofpowerfailuretheuserhas
thepossibilitytoopenthedoormanually
bypushingorpullingitopen,theclosed-
circuitopenerisunlocked.
The door can also be opened from inside
byoperatingthedoorhandleevenifthe
systemislive.Inanemergencythedoor
canalsobemanuallyopenedfromout-
side using a key or by operating the
emergencycutout.
TSA160
Illuminatedsign
“OCCUPIED“
Pad switch “DOOR
OPEN“(insideand
outside)
Emergency
cutout
Door
opener
Changeover
switch
locked/unlocked
Illuminatedsign
“OCCUPIED“
Indice
Altri manuali GEZE Sistema di apertura della porta

GEZE
GEZE Slimdrive SC Manuale

GEZE
GEZE TS 5000 R Manuale utente

GEZE
GEZE Perlan AUT-NT Manuale utente

GEZE
GEZE TS 4000 R Manuale utente

GEZE
GEZE Slimdrive EMD Invers Istruzioni operative

GEZE
GEZE Slimdrive SL NT GGS Manuale utente

GEZE
GEZE ISM Boxer Manuale utente

GEZE
GEZE Slimdrive SD Manuale utente

GEZE
GEZE TS 5000 E Manuale utente

GEZE
GEZE Slimdrive SL NT Guida rapida

GEZE
GEZE ECturn Inside Guida rapida

GEZE
GEZE FA GC 150 Guida

GEZE
GEZE ECdrive H Guida

GEZE
GEZE ECturn Guida rapida

GEZE
GEZE Levolan 120 Manuale utente

GEZE
GEZE Powerdrive PL-HT Manuale utente

GEZE
GEZE TS 5000 R Manuale utente

GEZE
GEZE TS 5000 Istruzioni utente

GEZE
GEZE Slimdrive EMD Guida

GEZE
GEZE Powerturn Series Guida rapida