2 I511
:
b
2: [671 b
Lh ONLY ON MODELS WITH VENT DAMPER PLUG.
M1123 ._ ____ --.._--.__-__-_-~.- ___. _ _
FIG. l-APPROXIMATE IGNITION MODULE DIMENSIONS IN In. [mm].
ELECTRICAL RATINGS:
Voltage and frequency: 20.5 to 28.5 V (24 V nom.), 60
HZ.
CANADIAN GAS ASSOCIATION CERTIFIED: 1029-ABI-
6269.
Current rating: 0.2 A. AMERICAN GAS ASSOCIATION DESIGN CERTIFIED:
20-l 4D3.
Valve contact ratings (at 24 Vat):
S8600, S8660 S8610, S8670
Run 1 Inrush Run 1 Inrush
Pilot l.OA 1 lO.OA 1.0 A 1 lO.OA
Main 1 l.OA 1 lOoA I 2.0A t 20.0A
SPARKGENERATOROUTPUT: 13 kVpeakat25 pf load.
THERMOSTAT ANTICIPATOR SETTING: 0.2 A plus pilot
valve rating plus main valve rating.
AMBIENT TEMPERATURE RATING:
S8600,58660: -40” F to +175” F [-40° C to +79O C].
S8610, S8670: -40” F to +175” F [-40° C to +79” C] with
main valve rated 1.OA or less; -40” F to +165’ F [-40°
C to +74” C] with main valve rated over 1.OA to 2.0 A.
RELATIVE HUMIDITY RATING: 5 to 90 percent RH at
95” F.
FLAME FAILURE RESPONSE TIME: 0.8 sec. at 1.OuA
flame current.
CONTINUOUS RETRY TIMING (SSSOOMonly): 5 minute
min., 6 minute nom. off time between trials for ignition.
TERMINALS:
SENSE (S8600A,B; S8610A,B only): 3/16 in. male
quick connect.
All otherterminals, including ignition: l/4 in. male quick
connects. Models available with Molex plug forconnec-
tion to Honeywell D80D Vent Damper.
FLAME CURRENT: 1 ).LA,min.
MOUNTING: Mounts in any position except with terminals
up. However, recommended mounting position is with
terminals down to provide maximum protection from
dripping water or dust accumulation. Fasten with No. 6-
32 machine or No. 8 sheetmetal screws of appropriate
length.
UNDERWRITERS LABORATORIES INC. COMPONENT
RECOGNIZED: File No. MH15564, Guide No. MCCZ2.
OTHER SYSTEM COMPONENTS
These modules provide operating control of an intermit-
tent pilot system. Additional components required to
complete the system must be ordered separately. They
include:
Dual valve combination gas control designed for
intermittent pilot
Combination pilot burner/igniter-sensor
(S8600F,H,M; S8610F,H; and S8670D)
Separate igniter and sensor on pilot burner bracket
(S8600A,B)
Ignition cable
Transformer
24V thermostat
High limit and other auxiliary controls as required
DUAL VALVE COMBINATION GAS CONTROL: Any that
meets current ratings listed below. VR8204, VR8440 or
VR8520 recommended.
S8600, S8660: 1.OA pilot, 1.O A main valve.
S8610, S8670: 1.OA pilot, 2.0 A main valve.
PILOT BURNER/IGNITER-SENSOR: See Table 2.
TABLE 2-PILOT BURNER/IGNITER-SENSORS.
PILOT BURNEW FLOW RATE*
MODULE IGNITER-SENSOR cfh 1 m3/hr
S8600F.H.M: Q345 0.8 1 0.02
S8610F;H; Q346 1.0 0.03
S8660D; Q348 1.5 0.04
S8670D Q362 0.5 0.014
Q381 0.5 0.014
S8600A,B Q179C ) 1.8 1 0.05
Q354 with Q345. Q346. Q348. Q362 or
‘With natural gas at 7.0 in. WC[1.7 kPa].
3 68-0085-2