OPERATION & MAINTENANCE MANUAL
H-8000C Series Flush Valve
(includes H8RFKC)
5055 Forsyth Commerce Rd, Ste 124, Orlando, FL 32807
Phone (800) 922-9883 | Fax (866) 670-5580
www.hydrotekintl.com

ISO 9001 Cered
8000 Series
U.S. Patent 6192530B1, 5699994
AC, Baery, or Solar Powered Sensor Operated Flush
The Hydrotek 8000 Series Automac Flush Valves are the most advanced,
electronic ushing system in the industry today. By incorporang our eld-
tested electronic circuitry and slow-closing solenoid valves, Hydrotek has
developed an innovave non-diaphragm, piston ushing mechanism that
will provide years of dependable and trouble-free service. The Hydrotek
AUTOFLUSH system is completely automac: there is no need to contact
any surface, no handle to push, and it ushes only when it is used. It
provides the ulmate sanitary protecon, the convenience of cleaner
restroom facilies, and the most ecient system in water conservaon.
• ADA Compliant. Meets all
barrier free codes
• Conserves water and energy
• Easily installed in new or retrot
applicaons
• Compevely priced for today’s
commercial market
• Promotes cleanliness & hygiene
• Proven Hydrotek crasmanship
and reliability
• ACCU-SENSE adjustable sensor eyes
• Standard manual mechanical override buon for
both urinals & water closets
• Standard brass/chrome-plated, all metal
construcon with other nishes available
• AC/DC powered - eld switchable
• Preset/adjustable ow rate and sensor distance
• Self-diagnosc electronics
• Standard vandal resistant stop valve (complete
units only)
• Superior piston ushing mechanism
• Field adjustable for le and right rough-in
• Baery replacement without water shut-o
• Operang pressures: 10-125 PSI
• Standard self-cleaning ltering system
• Switchable from/to urinal or closet
• 36 hour sennel ush
• Superior VSI silicone elastomer seals, unaected
by chlorine, chloromines or ammonia
• AC with DC backup models automacally switch to
baeries during a power outage
• Uses inexpensive AA baeries
• Baery service life: 400,000 on/o cycles (650,000
for the HB-8000SLE Series)
• Low baery indicator light (baery powered only)
• No outside power source required (baery
powered only)
• Can be installed by one tradesperson (baery
powered only)
Features:
H-8000C Series (AC)
Complete Units
HB-8000C Series (Baery)
Complete Units
HB8RFKC Series (Baery)
Complete Units
HB-8000SLE Series (Solar)
Complete Units

Hydrotek Autoush Valves
8000 Series
Meets A.S.S.E. Standard 1037-89
H-8000C (AC Powered) HB-8000C (Baery Powered)
HYDROTEK INTERNATIONAL, INC.
5055 Forsyth Commerce Rd., Ste 124
Orlando, FL 32807
800.922.9883 (Phone)
866.670.5580 (Fax)
www.hydrotekintl.com
The 8000 Series Flush Valves are available in:
H-8000C Series (AC Powered):
9H-8000C-A (Closet)
9H-8000C-B1 (Urinal)
9H-8000C-B2 (Urinal)
*Water conservaon, concealed and AC with DC
backup models available*
HB-8000C Series (Baery Powered):
9HB-8000C-A (Closet)
9HB-8000C-B1 (Urinal)
9HB-8000C-B2 (Urinal)
*Water conservaon and concealed models available*
HB-8000SLE Series (Solar Powered):
9HB-8000SLE-A (Closet)
9HB-8000SLE-B1 (Urinal)
9HB-8000SLE-B2 (Urinal)
*Water conservaon and retrot models available*
HB8RFKC Series Retrot Models (Baery Powered):
Sloan & Zurn Retrot
9HB8RFKC-C (Closet)
9HB8RFKC-U (Urinal)
Delany Retrot
9HB8RFKC-CD (Closet)
9HB8RFKC-UD (Urinal)
*Water conservaon models available*
PLUMBING SPECIFICATIONS:
Model Fixture Supply Line Top Spud Flow Rate
H/HB-8000C-A Closet 1” 1-1/2” 1.6 GPF
H/HB-8-128 Closet 1” 1-1/2” 1.28 GPF
H/HB-8000C-B1 Urinal 3/4” 3/4” 1.0 GPF
H/HB-8000C-B2 Urinal 1” 1-1/4” 1.0 GPF
HB8RFKC-C/U Cl. & Ur. N/A N/A 0.5-3.5 GPF
ELECTRICAL REQUIREMENTS:
• AC Powered Units:
– Solenoid valve and sensor: 6V DC
– Transformer: Input 120V AC, 60 Hz
Output 12V DC
• Baery Powered Units
– Solenoid valve and sensor: 6V DC
– Baery: (4) AA Alkaline Baeries
– Baery Service Life:
◦ 400,000 ushes, up to 6 years (Baery)
◦ 650,000 ushes, up to 10 years (Solar)
BASIC PACKAGE INCLUDES:
H-8000C
(-A, -B1, -B2)
HB-8000C
(-A, -B1, -B 2)
HB8RFKC
(-C, -U)
HB-8000SLE
(-A, -B1, -B2)
(1) Flush Valve 9 9 9 9
(1) Stop Valve 9 9 9
(1) Sweat Kit 9 9 9
(1) Flush Tube 9 9 9
(1) Spud Coupling 9 9 9
(1) Vacuum Breaker 9 9 9
(1) AC Adapter 9
(1) AC Input Tube 9
(4) AA Baers 9 9 9
OPTIONAL ACCESSORIES:
• HC-010 Mul-Unit Power Adapter (AC only) - 8 units
• HC-0104 Mul-Unit Power Adapter (AC only) - 4 units

H-8000C
AC Powered Flush Valve
Installaon Instrucons
ISO 9001 Cer ed
H-8000C
AC Powered Flush Valve
Installa on Instruc ons
Installa on Instruc ons:
1. Prior to installa on, “DRY TEST” the unit for proper
opera ons. Loosen the Set Screws (1) using the allen
wrench provided and remove the Top Cap (2) from the
valve body by pulling it straight up.
2. Connect the AC Power Adapter (3) to the Control
Module (4) and plug it in to a working power outlet.
Push the RESET bu on and watch the indicator lights
on the Control Module (4) for the following pa ern:
Red, (click), Green, Red, Red. This indicates that the
electronics are func oning properly. If the indicator
lights do not blink, contact the factory or your local
Hydrotek representa ve.
3. Reinstall the Top Cap (2) onto the valve body and
ghten the Set Screws (1). Install the Stop Valve (5) to
the supply line using a Hydrotek Sweat Kit (op onal).
4. Connect the valve body to the Stop Valve (5) using the
Slip Joint Nut (6).
5. A ach the Vacuum Breaker (7) and Tailpiece (9) to the
valve body using the Lock Nut (8). Secure the Tailpiece
(9) to the plumbing fi xture using the provided Spud
Coupling (10).
6. Turn the water on through the Stop Valve (5) and check
for leaks. Push and hold the Override Bu on (11) for
30 seconds and check the fi xture for over ow. Adjust
the water ow from the Stop Valve (5) for a smoother
ush.
7. TEST: Stand in front of the ush valve for 4 seconds,
then step away. The valve should ush automa cally. If
not, refer to the Troubleshoo ng Guide.
8. Flow rates are preadjusted from the factory. If minor
adjustments are needed, contact Hydrotek for further
details.
Parts:
1. Set Screws 7. Vacuum Breaker
2. Top Cap 8. Lock Nut
3. AC Power Adapter 9. Tailpiece
4. Control Module 10. Spud Coupling
5. Angle Stop 11. Override Bu on
6. Slip Joint Nut
HYDROTEK INTERNATIONAL, INC.
5055 Forsyth Commerce Rd., Ste 124
Orlando, FL 32807
800.922.9883 (Phone)
866.670.5580 (Fax)
www.hydrotekintl.com
6
1
2
3
4
5
11
7
8
9
10

H-8000C Series
Sensor Operated Flush Valve
Troubleshoong Guide
Normal Operaon: When power is connected, the ush valve will immediately perform diagnosc funcon.
You will hear a clicking sound and see lights ash. When the sensor is acvated, the light will ash once and
the valve will ush. The red indicator light will ash when the baeries are low.
Problem Possible Cause To Diagnose Remedy
Valve will not turn on:
Water not turned on Check water supply Turn water on
Power supply failure
No light, no clicking:
• Check baeries
• Check power adapter
Reinstall or replace baeries/
Replace power adapter
Electronic PCB / Sensor is
defecve
No light, no clicking:
• Reinsert baeries
• Reaach power adapter
Replace electronic PCB
Solenoid valve is clogged Solenoid is clicking but no water
is coming out Clean solenoid
Solenoid coil is defecve
Insert new baeries or reaach
power adapter. Light blinks but
no solenoid is clicking
Replace solenoid coil
Valve will not shut o:
The solenoid valve is normally closed. Turn o water and acvate the valve. If there is a clicking
sound, the solenoid valve is dirty. If there is no clicking sound, then check the solenoid valve. If
water is leaking through, the solenoid valve is dirty and needs to be serviced.
Other factors include:
• Sensor distance is too long
• Control module is defecve
• Manual override buon is scking
IMPORTANT: Periodic maintenance is required for smooth and trouble-free operaon of this ush valve.
For service and inquiry about available repair kits, please call Hydrotek Technical Support at (800) 922-9883.

H-8000C Series
Sensor Operated Flush Valve
Assembly Parts
No Descripon Part Number
1AC Power Adapter HCC-008Cv
2Control Module HCC-080B
3 Solenoid Coil HCC-098
4Sensor Eye and Cable HCC-080E
5Sweat Kit Assembly HC-084 (3/4”)
HC-084B (1”)
6Angle Stop - Complete Assembly HC-082A (3/4”)
HC-082B (1”)
7Angle Stop Repair Kit HC-082C
8Control Disc Assembly HCC-102
9Manual Override Buon Assembly HC-089
10 Vacuum Breaker Repair Kit HC-086
11 Flush Tube
HC-086A (1-1/2”)
HC-086B (3/4”)
HC-086C (1-1/4”)
12 Top Spud Assembly
HC-093A (3/4”)
HC-093B (1-1/4”)
HC-093C (1-1/2”)
RSolenoid Valve Repair Kit HCC-106
Please visit our website, www.hydrotekintl.com, for
our most current Products Pricing Sheet.
2
4
3
5
6
7
8
9
10
11
12
R
1

H-8000C Series
Sensor Operated Flush Valve
Control Module
1 2 3
4
56789
LEGEND
1. DC Input Pin Receptor
2. Dip Switches
3. Reset Buon
4. Indicator Lights
5. Solenoid Pin Receptor
6. Control Cable (Sensor Eye) Pin Receptor
7. Sensor Distance Adjustment Dial
8. AC Input Pin Receptor
9. DC Input Pin Receptor

H-8000C Series
Sensor Operated Flush Valve
Control Module Sengs
Flow rate and sensor arming me can be adjusted via the dip switches located on the Control Module.
Gallons
Per
Flush Sw 1 Sw 2 Sw 3 Sw 4
Urinal
0.125* ON ON OFF ON
0.5 ON ON ON ON
1.0 ON ON ON OFF
Closet 1.28 ON ON OFF OFF
1.6 ON OFF ON ON
Flushing Volume
Flush Valves are preset to 1.0 GPF for urinal and 1.6 GPF for closet
Sw 5 Sw 6 Sw 7 Sw 8 Arming Time
Urinal Standard OFF OFF OFF ON 3 seconds
Oponal ON OFF OFF OFF 1.5 seconds
Sensor Arming Time
Sensing Time Required to Flush
Sw 5 Sw 6 Sw 7 Sw 8 Arming Time
Closet Standard ON OFF OFF OFF 4 seconds
Oponal OFF OFF OFF OFF 8 seconds
NOTE: PUSH THE RESET BUTTON ON THE CONTROL MODULE AFTER
ANY ADJUSTMENTS TO THE DIP SWITCHES.
Sensor Distance Adjustment
Clockwise Increase sensing distance
Counter-Clockwise Decrease sensing distance
*0.125 ow rate seng only available if ordered that way from the factory
For alternate ow rates not listed, please contact Hydrotek direct

Page 1
D.2162
Acorn Engineering Company • 15125 Proctor Avenue • P.O. Box 3527 • City of Industry, CA 91744-0527 U.S.A.
Tel: (800) 488-8999 • (626) 336-4561 • Fax: (626) 961-2200 • www.acorneng.com • E-mail: [email protected]
Fixture May Show Some Available Options
Please visit www.acorneng.com for most current specifications.
®
Dura-Ware 2162 Series
Washout Urinal
Exposed Mounting Screws are furnished. No concealed wall fasteners or anchor shields are
furnished.
Provide and install Acorn Dura-Ware Washout Urinal (specify model number and options). Urinal
shall be back wall washdown type. Fixture shall be fabricated from 14 gage, type 304 stainless
steel and shall have coved corners to facilitate cleaning. Urinal shall meet ASME A112.19.3 and
CSA B45.4 requirements. All welds shall be continuous and exterior surfaces shall have a satin
finish. P-trap shall be fully enclosed. Fixture shall be furnished with exposed mounting screws.
Urinal is washout type with back wall washdown manufactured to ASME A112.19.3 and CSA
B45.4 requirements. Flushing inlet connection is 3/4" NPT male. Bottom of urinal is sloped to a
high capacity stainless steel beehive dome strainer. Strainer is secured with tamper-resistant
screws. P-trap has a minimum of 2" seal.
Washout Urinal
Fixture is arranged to be installed on finished wall and serviced from the front side. Fixture is
fabricated from 14 gage, type 304 stainless steel and is seamless welded construction. Exterior
has a satin finish. Interior has a matte finish. Fixture has a back wall washdown, and is
optionally available with a continuous flushing rim that washes all four walls. Corners are coved
to facilitate cleaning. P-trap is fully enclosed. Back of fixture is sound-deadened with fire-
resistant material.
GUIDE SPECIFICATION
2162-W-1-FV-28982162-T-1-FV
Revised: 08/21/18

Page 2
Selection Summary
Model No. & Option___________________________
Quantity____________________________________
Approved for Manufacturing
Company__________________Title______________
Signature_________________ Date______________
Important: Installation instructions and current rough-in are furnished with each fixture. Do not rough in without certified dimensions.
Dimensions are subject to manufacturer’s tolerance of plus or minus 1/4" and change without notice. Acorn assumes no responsibility for use of void or superseded data. © Copyright 2007 Acorn Engineering Company
PRODUCT OPTIONS
o -CFR Continuous Flushing Rim
o -EG Enviro-Glaze Color, Specify: ______________
o -FVT Flush Valve Thru Wall Connection
q -TF Transformer, 120VAC to 24VAC (-MVCFV Option)
o -WA1 Waste Adapter to 2" NCT Female
o -WA2 Waste Adapter to 2" NPT Male
o -WA3 Waste Adapter to 2" NPT Female
o -WA4 Waste Adapter to 2" No-Hub
FLUSH VALVE OPTIONS (Must Specify)
Refer to Acorn Dura-Ware Supplementary for Box Cover(s)
and Access Panel(s)
o -FV Flush Valve, Mechanical
o -FVBO Flush Valve by Others
o -FVH Flush Valve, Hydraulic (N/A for Top Supply)
o -FVL Flush Valve, ADA Lever Handle (Concealed F.V.)
o -MVCFV Time-Trol Flush Valve (N/A for Top Supply)
D.2162
®
Dura-Ware 2162: Washout Urinal
WALL THICKNESS AND TYPE (Must Specify)
Thickness: ________ Type: o Concrete o Block o Steel
BASE MODEL NUMBER
o 2162 Washout Urinal
MODEL NUMBER AND OPTIONS SELECTION
SUPPLY (Must Specify)
o -T Top (Exposed)
o -W Wall (Concealed)
FIXTURE MOUNTING AND WASTE
o -1 Off-Floor, Wall Outlet
FLUSH VALVE GPF’s (Must Specify)
o -1.0 GPF
o -1.5 GPF
Please visit www.acorneng.com
for most current specifications.
Acorn Engineering Company • 15125 Proctor Avenue • P.O. Box 3527 • City of Industry, CA 91744-0527 U.S.A.
Tel: (800) 488-8999 • (626) 336-4561 • Fax: (626) 961-2200 • www.acorneng.com • E-mail: [email protected]
3. Urinal Waste Outlet.
5. Wall Mounting Anchors (By Others).
4. Beehive Strainer.
2. Optional -FV Flush Valve - Top Supply.
1. Optional -FV Flush Valve - Wall Supply.
NOTES: 2162-W-1
2162-T-1
5
3
241
24"
(610)
RECOMMENDED
6"
(152)
14"
(356)
12"
(305)
14"
(356)
12"
(305)
3
3
Revised: 08/21/18
WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Altri manuali per H-8000C Series
1
Questo manuale è adatto per i seguenti modelli
3
Indice
Altri manuali Hydro Tek Unità di controllo
Manuali Unità di controllo popolari di altre marche

Festo
Festo Compact Performance CP-FB6-E Manuale elenco delle parti

Elo TouchSystems
Elo TouchSystems DMS-SA19P-EXTME Manuale utente

JS Automation
JS Automation MPC3034A Manuale utente

JAUDT
JAUDT SW GII 6406 Series Guida rapida

Spektrum
Spektrum Air Module System Manuale utente

BOC Edwards
BOC Edwards Q Series Manuale utente