IFM Electronic TR7432 Manuale utente

Operating instructions
Control monitor for
temperature sensors
TR7432
704469 / 00 10 / 2008
UK

2
Contents
1 Preliminary note....................................................................................................3
1.1 Symbols used.................................................................................................3
2 Safety instructions ................................................................................................3
3 Functions and features.........................................................................................4
4 Function................................................................................................................4
4.1 Communication, parameter setting and evaluation ........................................4
4.2 Switching function ..........................................................................................5
5 Installation ............................................................................................................5
6 Electrical connection.............................................................................................6
7 Operating and display elements...........................................................................7
8 Menu.....................................................................................................................8
8.1 Menu structure ...............................................................................................8
8.2 Explanation of the menu.................................................................................9
9 Parameter setting ...............................................................................................10
9.1 General parameter setting............................................................................10
9.2 Configuration of the display (optional)..........................................................12
9.3. Setting of the output signals ........................................................................12
9.3.1 Setting of the output function...............................................................12
9.3.2 Setting of the switching limits ..............................................................12
9.4 User settings (optional) ................................................................................12
9.4.1 Setting the measurement method .......................................................12
9.4.2 Zero point calibration...........................................................................13
9.4.3 Setting the switching delays ................................................................13
9.4.4 Setting of the error behaviour of the outputs .......................................13
9.4.5 Setting of the switching logic for OUT1 ...............................................13
9.5 Service functions ..........................................................................................13
9.5.1 Reading of the min/max values for the system temperature ...............13
9.5.2 Reset of all parameters to factory setting............................................13
10 Operation..........................................................................................................14
10.1 Reading of the set parameters ...................................................................14
10.2 Fault indication ...........................................................................................14

3
UK
1 Preliminary note
1.1 Symbols used
►Instruction
> Reaction, result
[…] Designation of pushbuttons, buttons or indications
→Cross-reference
Important note
Non-compliance can result in malfunctions or interference.
2 Safety instructions
Please read this document prior to set-up of the unit. Ensure that the product is•
suitable for your application without any restrictions.
Improper or non-intended use may lead to malfunctions of the unit or to un-•
wanted effects in your application. That is why installation, electrical connec-
tion, set-up, operation and maintenance of the unit must only be carried out by
qualified personnel authorised by the machine operator.
Check the compatibility of the product materials (→12 Technical data) with the•
media to be measured in all applications.
11 Scale drawing ...................................................................................................15
12 Technical data...................................................................................................16
12.1 Setting ranges ............................................................................................17
13 Factory setting..................................................................................................17

4
3 Functions and features
With temperature sensors connected the unit monitors the system temperature in
machinery and plant.
Connectable temperature sensors:
Temperature sensors TS or TT.•
Resistance thermometer RTD (Pt 100 or Pt 1000).•
The unit automatically detects the connected sensor type and configures itself ac-
cordingly The electrical measuring method (3-wire or 4-wire sensor) is determined
viathemenusetting(→9.5.1).
4 Function
4.1 Communication, parameter setting and evaluation
The unit displays the current system temperature.•
It generates 2 output signals according to the parameter setting.•
OUT1 Switching signal for system temperature limit value.
OUT2 Switching signal for system temperature limit value.
It moreover provides the process data via IO-Link.•
The unit is laid out for fully bidirectional communication. So, the following op-•
tions are possible:
Remote display: Reading and displaying the current system temperature.-
Remote parameter setting: Reading and changing current parameter settings-
with the FDT service program ifm Container or via IO-Link.
Using the FDT service program ifm Container, the current parameter settings-
can be stored and transferred to other units of the same type.
The program library of the available DTM objects can be found at www.ifm.com
→Service→Download.
Device-specific parameter lists for IO-Link parameter setting are available at:
www.ifm.com→Selectyourcountry→Datasheetdirect:

5
UK
4.2 Switching function
OUTx changes its switching state if it is above or below the set switching limits
(SPx, rPx). The following switching functions can be selected:
Hysteresisfunction/normallyopen:[OUx]=[Hno](→fig.1).•
Hysteresisfunction/normallyclosed:[OUx]=[Hnc](→fig.1).•
First the set point (SPx) is set, then the reset point (rPx) with the requested differ-
ence.
Windowfunction/normallyopen:[OUx]=[Fno](→fig.2).•
Windowfunction/normallyclosed:[OUx]=[Fnc](→fig.2).•
The width of the window can be set by means of the difference between SPx and
rPx. SPx = upper value, rPx = lower value.
1 2
T = system temperature; HY = hysteresis; FE = window
5 Installation
Connect the unit to a temperature sensor and fix it with the help of mounting accessories.►
The following components are available as accessories order no.
Mounting set for direct connection of temperature sensors TT E30017
Mounting clamp Ø 34 mm, PBT E10017
Mounting clamp Ø 34 mm, PA E10193
Mounting device 2 way, POM E30078
Mounting device 3 way, POM E30079

6
6 Electrical connection
The unit must be connected by a qualified electrician.
The national and international regulations for the installation of electrical
equipment must be adhered to.
Voltage supply to EN 50178, SELV, PELV.
Disconnect power.►
Connect the unit as follows:►
�
�
�
1: two-wire sensor
2: three-wire sensor
3: four-wire sensor
connection for
voltage supply
and output
signals
Pin 1 Ub+
Pin 3 Ub-
Pin 4 (OUT1) Binary switching output temperature monitoring.•
Data channel for bidirectional communication.•
Pin 2 (OUT2) Binary switching output temperature monitoring.•

7
UK
connection for
temperature
sensor
2-wire sensor
Menu setting: Mmod = 4w, links between 1 / 2 and 3
/ 4.
A wiring fault can be corrected in the menu COF.
3-wire sensor
Menu setting: Mmod = 3w, link between 1 / 2.
Themaximumcableresistanceof10Ωpercoremust
not be exceeded (this corresponds to a cable length of
approx. 80 m for a wire cross-section of 0.14mm²).
4-wire sensor Menu setting: Mmod = 4w.
Core colours of ifm sockets:
1 = BN (brown), 2 = WH (white), 3 = BU (blue), 4 = BK (black)
7 Operating and display elements
1 to 8: Indicator LEDs
LED 1: Current temperature in °C.-
LED 2: Current temperature in °F.-
LED 7, LED 8 = switching state of the corresponding output.-
9: Alphanumeric display, 4 digits
Display of the current system temperature.-
Indication of the parameters and parameter values.-
10: Set button
Setting of the parameter values (scrolling by holding pressed; incrementally by pressing-
once).
11: Mode/Enter button
Selection of the parameters and acknowledgement of the parameter values.-

8
8 Menu
8.1 Menu structure

9
UK
8.2 Explanation of the menu
SP1/rP1 Upper / lower limit value for system temperature at which OUT1 switches.
SP2/rP2 Upper / lower limit value for system temperature at which OUT2 switches.
OU1 Output function for OUT1:
Switching signal for the temperature limit values: Hysteresis function [H ..] or
window function [F ..], either normally open [. no] or normally closed [. nc].
OU2 Output function for OUT2:
Switching signal for the temperature limit values: Hysteresis function [H ..] or
window function [F ..], either normally open [. no] or normally closed [. nc].
Mmod Measurement method (2-wire, 3-wire or 4-wire temperature sensors).
EF Extended functions / opening of menu level 2.
HI Maximum value memory for system temperature.
LO Minimum value memory for system temperature.
COF Zero-point calibration.
dS1/dS2 Switch-on delay for OUT1 / OUT2
dr1/dr2 Switch-off delay for OUT1 / OUT2.
FOU1 Behaviour of output 1 in case of an internal fault.
FOU2 Behaviour of output 2 in case of an internal fault.
P-n Output logic: pnp / npn.
diS Update rate and orientation of the display.
Uni Unit of measurement for system temperature.
rES Restore factory settings.

10
9 Parameter setting
During parameter setting the unit remains in the operating mode. It continues its
monitoring function with the existing parameters until the parameter setting has
been completed.
9.1 General parameter setting
3 steps must be taken for each parameter setting:
1Selection of the parameter
Press [Mode/Enter] until the re-►
quested parameter is displayed.
2Setting of the parameter value
Press [Set] and keep it pressed.►
Current setting value of the param->
eter flashes for 5 s.
After 5 s: Setting value is changed:>
incrementally by pressing the button
once or continuously by keeping the
button pressed.
Numerical values are incremented continuously. For reducing the value: Let the dis-
play move to the maximum setting value. Then the cycle starts again at the minimum
setting value.
3Acknowledgement of the parameter
value
Press [Mode/Enter] briefly.►
The parameter is displayed again.>
The new setting value is stored.
Setting of other parameters
Start again with step 1.►
Finishing the parameter setting
Press [Mode/Enter] several times until the current measured value is displayed or wait►
for 15
s.
The unit returns to the operating mode.>
If [SLoc] is displayed when attempting a modification of a parameter value, the sensor is•
locked via software. This locking can only be removed via a parameter setting software.
In case of parameter setting with the user interface of the ifm Container program, the•
values can be directly entered in the specified fields.
ForIO-Linkparametersetting→device-specificparameterlistsat:www.ifm.com→Select•
yourcountry→Datasheetdirect: