ET98 SHUTOFF/LOCKOFF WITH FILTER
REPAIR KIT INSTRUCTIONS RK-ET98
Important: Any maintenance, service or repair should
be performed by trained and experienced service
technicians. Proper tools and equipment should be
used to prevent injury to the servicing technician,
property or system components. Service repairs
should always be performed in a safe environment
and the technician should always wear protective
clothing to prevent injury.
The IMPCO PPI-118 repair kit instructions will provide
the technician information to successfully repair the
ET98 Lockoff with Filter.
NOTE: This repair kit cannot be used to repair an
ET98 not originally equipped with an integrated
fuel filter.
Always inspect the major casting pieces for damage,
corrosion, cracks, or pits before attempting a service
repair.
PRIOR TO ANY REPAIR OR MAINTENANCE:
1. Close the valve on the LPG or Natural Gas source.
2. Run engine until it stalls from lack of fuel.
Do not allow LPG to contact the skin. LPG is
stored in the fuel tank as a liquid. When LPG
contacts the atmosphere, it immediately ex-
pands into a gas, resulting in a refrigeration ef-
fect that can cause severe burns to the skin
and/or eyes.
REBUILD INSTRUCTIONS
1. Remove the Bolt (10) at the bottom of the Filter
Bowl (8) and remove the Filter Bowl assembly.
Some residual pressure may be present
2. Remove the Bracket (3) and O-ring (2).
3. Remove the Filter (5) from the Filter Bowl (8) and
O-rings (6, 9) from the Bolt (10) and rim of Filter
Bowl. Discard Filter and O-rings.
Old (with wire leads) and new (integrated elec-
trical connector) ET98-51315-001
Shutoff/Lockoff Valves
4. Thoroughly clean the Filter Bowl (8), Bolt (10),
Bracket (3) and the Valve Body (1) with a safety
solvent. DO NOT submerge the induction coil
in cleaning solvent, water or any type of liquid.
5. Lubricate O-rings with Vaseline or petroleum jelly.
6. Place the O-ring (7) in the rim of the Filter Bowl
(8).
7. Place O-ring (9) on the Bolt (10). Insert Bolt all
of the way into the Filter Bowl (8).
8. Place O-ring (6) on the Bolt (10) and slide
down to the bottom of the Filter Bowl (8). NOTE
O-ring (6) may already be installed in the filter
(5). Place Filter (5) over Bolt.
9. Place O-ring (4) on the top of the Filter (5).
10. Insert O-ring (2) into the ET98 Valve Body (1).
If necessary, apply extra Vaseline or petroleum
jelly to the O-ring to hold in place during as-
sembly.
11. Place the Bracket (3) on top of the Filter Bowl (8)
and mount the entire assembly on the Lockoff
Body (1). Thread Bolt (10) into the Lockoff Body
(1), ensuring that the O-ring (3) is properly seat-
ed. Torque bolt to 11.1 +/- 1.1 ft/lbs. (15 +/- 1.5
Nm).
12. Open fuel valve and inspect for leaks using an
approved leak detector solution. If no leaks are
found, re-connect the negative battery cable. If
a leak is detected, correct the problem before
proceeding with these instructions.
13. Turn Key to ON and inspect for leaks again
using an approved leak detector solution. Per-
form a final leak test with the engine running.

PPI-118 REV. C IMPCO Technologies Inc April, 2013
Page 2 of 2 3030 South Susan St.
Santa Ana, CA 92704
www.impcotechnologies.com
O-Rings included in the RK-ET98. (Not to scale--use relative size to de-
termine application)
Item Part # Description
1 NSS Valve Body
2* NSS O-ring
3 NSS Bracket
4* NSS O-ring
5* NSS Filter
6* NSS O-ring
7* NSS O-ring
8 NSS Filter Bowl
9* NSS O-ring
10 NSS Bolt
*Included in Repair Kit
Note: The parts are called out by number and designated by parentheses () in
the Rebuild Instructions.
WARNING:
IMPROPER INSTALLATION OR USE OF THIS PRODUCT MAY CAUSE SERIOUS INJURY
AND/OR PROPERTY DAMAGE.
THE FOLLOWING IS SPECIFIC TO USA AND CANADA. IF INSTALLED, REPAIRED OR MAINTAINED OUTSIDE OF THE USA OR CANADA,
REFER TO LOCAL STANDARDS AND LAWS GOVERNING THIS AND RELATED PRODUCTS. CANADA: REFER TO CAN/CGA PROPANE
INSTALLATION CODES.
SERVICE TECHNICIANS AND USERS
SHOULD CAREFULLY READ AND ABIDE BY THE PROVISIONS SET FORTH IN NATIONAL FIRE PROTECTION ASSOCIATION PAMPHLET
#37 FOR STATIONARY ENGINES, #52 FOR CNG VEHICULAR FUEL SYSTEMS OR #58 FOR LPG SYSTEMS.
INSTALLERS
LPG INSTALLATIONS IN THE UNITED STATES MUST BE DONE IN ACCORDANCE WITH FEDERAL STATE OR LOCAL LAW, WHICHEVER IS
APPLICABLE AND NATIONAL FIRE PROTECTION ASSOCIATION PAMPHLET #58, STANDARD FOR STORAGE AND HANDLING OF LIQUE-
FIED PETROLEUM GASES TO THE EXTENT THESE STANDARDS ARE NOT IN VIOLATION WITH FEDERAL, STATE OR LOCAL LAW.
CANADA: REFER TO CAN/CGA PROPANE INSTALLATION CODES.
CNG INSTALLATIONS IN THE UNITED STATES/CANADA
MUST RE DONE IN ACCORDANCE WITH FEDERAL STATE OR LOCAL LAW AND NATIONAL FIRE PROTECTION ASSOCIATION PAMPHLET
#52, COMPRESSED NATURAL GAS (CNG) VEHICULAR FUEL SYSTEMS TO THE EXTENT THESE STANDARDS ARE NOT IN VIOLATION
WITH FEDERAL, STATE OR LOCAL LAW. CANADA: REFER TO CAN/CGA CNG INSTALLATION CODES.
LPG AND/OR NATURAL GAS INSTALLATIONS ON STATIONARY ENGINES
MUST RE DONE IN ACCORDANCE WITH FEDERAL, STATE OR LOCAL LAW AND NATIONAL FIRE PROTECTION ASSOCIATION PAMPHLET
#37, STATIONARY COMBUSTION ENGINES AND GAS TURBINE ENGINES, TO THE EXTENT THESE STANDARDS ARE NOT IN VIOLATION
WITH FEDERAL, STATE OR LOCAL LAW. FAILURE TO ABIDE BY THE ABOVE WILL VOID ANY IMPCO WARRANTY ON THE PRODUCTS
AND MAY CAUSE SERIES INJURY OR PROPERTY DAMAGE. DUE TO THE INHERENT DANGER OF GASEOUS FUELS THE IMPCO PROD-
UCTS SHOULD NOT BE INSTALLED OR USED BY PERSONS NOT KNOWLEDGEABLE OF THE HAZARDS ASSOCIATED WITH THE USE OF
GASEOUS FUELS.
Manuali Unità di controllo popolari di altre marche

Festo
Festo Compact Performance CP-FB6-E Manuale elenco delle parti

Elo TouchSystems
Elo TouchSystems DMS-SA19P-EXTME Manuale utente

JS Automation
JS Automation MPC3034A Manuale utente

JAUDT
JAUDT SW GII 6406 Series Guida rapida

Spektrum
Spektrum Air Module System Manuale utente

BOC Edwards
BOC Edwards Q Series Manuale utente