JALpower JP5520 Manuale utente

USER’S MANUAL
JP5520 10-20KVA

2
Introduction……………………………………………………………………………3
Foreword………………… ………………………………………………………………3
Dimension Structure…………………………………………………………………3
10-20KVA UPS appearance ………………………………………………………3
Put by UPS ……………………………………………………………………………3
Handle or move……………………………………………………………………………3
Put by………………………………………………………………………………………3
Installation and connection…………………………………………………………5
Caution ……………………………………………………………………………………5
Single UPS installation……………………………………………………………………7
Connection wire option……………………………………………………………………7
UPS operation…………………………………………………………………………8
Prepare before for turn-on…………………………………………………………………8
Two kinds of LCD panel for choosing ……………………………………………………8
First start-up operating ……………………………………………………………………9
Condition handling …………………………………………………………………11
New LCD panel display and alarming ……………………………………………14
Work theory……………………………………………………………………………19
Maintenance of the UPS and battery ……………………………………………21
Communication interface…………………………………………………………22
Specifications …………………………………………………………………………23

3
1. Introduction
(1)Foreword
JP5520 series UPS are development produce compact and intelligently uninterrupted
power system by JALPOWER. Which ensure you to operating computer in a stable and pure
power circumstance, and to manage network system intelligently. UPS have becoming
necessary equipment to computer and information system.
(2)Caution
a. It’s must to reading this manual before operating the UPS.
b. Follow all operating and user instructions.
c. Don’t uncover the machine during operation.
d. Please handle with care of the machine.
e. Don’t use UPS over rating lead.
f. Please time limit charge at battery.
g. Keep dry and clean of the UPS.
h. Please well arranged save this manual.
2. Dimension Structure
10-20KVA UPS appearance
Fig1 Front Panel Fig2 Rear Panel
3. Put by UPS
(1)Handle or move
a. Are all the connection wire essential dismantle to after shut down.
b. Put lightly with care, Bump with strictly forbid.
c. Not to be upright and move.
(2)Put by
a. Not to be tipped Fig3.

4
Fig3 Option on place of the UPS
b. Maintain a minimum clearance of 100 mm all around the UPS for proper air flow and
cooling Fig4.
Fig4
c. Free form sun shine, raindrop or moisture Fig5, Fig6.
Fig5 Fig6

5
d. Far form fire source and high temperature, prevent over temperature Fig7.
e. Don’t put by objects on top of UPS Fig 8.
Fig7 Fig8
f. Free form moisture, flammable liquids, gasses or corrosive substances Fig9.
Fig9
g. Operation environment temperature 0~40℃。
4. Installation and connection
(1)Caution
a. Follow construction of electrician rule.
b. Do well to ground connection, be grounded on refer to point. Will grow ups
interference and data fault because of not good ground wire, influential at UPS and
computers. Joint ground, refer to Fig10.

6
Fig10
c. Free form electric operating, caution
construction safety, will be input
mains switch “off”.
d. If properly input voltage for use all
powerful meter measurement.
e. Power wire, terminal use of high
quality products, restrain use of faulty
products.
f. Use of high quality terminal pressure
connection to power wire, restrain
direct twine on terminal bus.
g. After fixation input power wire, check
if bump bezel, so as not to short
circuit or bump other substances.
h. When connection to distribution box
free from common switch and other
equipments,besuretoconnectionto Fig11
source, refer to Fig11.
i. Don’t reverse connection, the polarity of power supply.
j. Voltage drop must less than 5V, between of neutral and ground.
k. Generally socket be restrain use, otherwise will bring about load damage.

7
(2)Single UPS installation
Installation method: refer to Fig1.
Use screw driver to tear down four screws.
Opening front panel, namely seeing downside distribution box of power switch.
Refer to Fig12、13.
Fig12
SWITCH:BYPASS mode andAUTO mode transfer.
SW1:city input switch SW2:bypass switch SW3:battery input switch Fig13
First into the distribution inlet and outlet hole of the output/input and batteries
group power wire, after that assembly connection.
Caution: Don’t connection to 380V, test take place fault, for the single phase input
UPS belong to 2X0V system, when movering or again connection, be sure to
again carry on according to more than step.
(3)Connection wire option
Compare with rated value of input current and cross section of input power wire.
Cable 1
TYPE Three-phase input
current(max)
Three-phase input cable
Sez.(mm2) Wire Sep.
10KVA 63A 16 mm2OT16-6
15KVA 95A 20 mm2OT16-8
20KVA 128A 25mm2OT25-10
Compare with rated value of output current and cross section of output power wire.
Cable 2
TYPE Output current(max) Output cable Sez.(mm2) Wire Sep.
10KVA 45A 10 mm2OT10-6
15KVA 75A 16 mm2OT16-8
20KVA 90A 20mm2OT20-10

8
5. UPS Operation
(1)Prepare before for turn-on
For normal running be able to the UPS. Please validation below thing before for turn-on,
refer to Fig2.
a. Validation be located “OFF” for all power switch.
b. Again validation primary for installation places.
c. Use hand shaking input power wire, whether loose, if loose to screw up.
d. No load.
e. Whether measure up to 2X0V±15% make use of voltmeter, check input voltage.
(2)Two kinds of LCD panel for choosing:
Panel Newpanel
A: LCD display
B: Bypass input indicator
C: Mains input indicator
D: Battery indicator
E: Failure indicator
F: Inverter indicator
G: Overloads indicator
H: Page-up button
I: ON/OFF button
J: Page-down button
A: LCD display
B: ON/OFF button
C: Function button
D: Bypass input indicator
E: Mains input indicator
F: Battery indicator
G: Inverter indicator
H: Failure indicator

9
(3)First start-up operating
After validation properly of more than thing, please according under method turn-on.
a. Put switch on auto mode. Turn on the “NO fuse breaker” with front
panel(SW1,SW2,SW3), front panel indicator and bypass indicator at times are
lightness. Refer to Fig14.(panel 1)
Fig14
b. Will ON/OFF button push down with front panel, follow on lightness of input
indicator and bypass indicator, LCD display mains OK, battery OK, mains output
through bypass, refer to Fig15.
Fig15
c. After 20 seconds with the front panel, input indicator are lightness LCD display (AC )
OK, (BAT) OK, inverter output, refer to Fig16.
Fig16

10
d. Disconnected input power of the UPS, mains indicator are go out, LCD display (AC)
OFF, (BAT) OK, inverter output, beeps every 4 seconds will the UPS, show UPS is
operating from battery power.
After beeps 90 seconds, beep stop, when battery runs low, beep every 1 second,
battery capacity indicator at times flashing. Refer to Fig17.
Fig17
e. Restoration input power of the UPS, mains indicator lightness, push down LCD
cycle push button to exchange displays item, check displays value whether normal,
first turn-on are that is accomplish. Measurement output voltage whether normal,
will the load connection to output end of the UPS, UPS provides clean power to the
loads.
f. Mare connection load, will exchange displays item to output power displays the
percentage(%) on LCD indicator push button, if displays value be greater than 100%,
show overload, turn-off unimportant of loads, cause displays value be smaller than
100%.
(4)If turn-on or turn-off in everyday use, according to below method operating.
a. When everyday turn-off of the UPS, push down “on/off” button on front panel, that is
shut-down.
b. When everyday turn-on of the UPS, push down “on/off” button on front panel, that is
starting.
(5)When on/off operation for long be no use of the UPS.
a. If be no use for out march (10) days of the UPS, the first push down on/off button that
is shut down on the front panel, then will turn power switch (NFB) into OFF on the
front panel.
b. If be no use for out march three months of the UPS, according to first turn-on method,
will UPS running more than 24 hours, keep batteries at full capacity, and so external
battery life.
Indice
Altri manuali JALpower UPS
Manuali UPS popolari di altre marche

Pylontech
Pylontech Victron & Pylontech US5000 Manuale utente

Tecnoware
Tecnoware EVO DSP PLUS MM 6.8 Manuale utente

Mecer
Mecer ME-1000-WTU Manuale utente

Mustek
Mustek PowerMust 530(B) Plus Manuale di installazione e funzionamento

Emerson
Emerson Liebert NXL series Manuale utente

MAKELSAN
MAKELSAN BOXER SERIES Manuale utente