JALpower JP9960 Manuale utente

USER’S MANUAL
JP9960 20-80KVA

Thanks for choosing our products!
All warnings and operation instructions in the manual and on the machine
should be strictly followed and this user manual should be kept properly
for future reference. Do not attempt to operate the UPS until reading
through all safety information and operating instructions of this manual
carefully.
This manual applies to the JP9960 series products, including:
JP9960 20K
JP9960 30K
JP9960 40K
JP9960 60K
JP9960 80K

Safety Instructions
Operation Safety
1. Prior to the application, please read Safety Instructions carefully to ensure correct and
safe application. Please keep the user manual properly.
2. During operation, attention should be paid to all warning symbols and operations should
be followed strictly as required.
3. Equipment is not supposed to be used in environment that directly exposed to the sunlight
or raindrops or in humid environment.
4. The equipment should not be installed close to area of thermal sources or any area where
there is presence of devices such as electric heaters and furnaces.
5. Make sure the safety space should be left for proper ventilation and product
maintenance when placing UPS. Refer to the instructions during installation.
6. Dry and non-conductive items should be used for cleaning.
7. In case of a re hazard, dry powder extinguisher should be used properly. Using liquid
fire extinguisher may result in electric shock hazard.
8. Storey bearing capacity of machine and batteries should be taken into consideration prior
to installation.
9. Using this device, please ensure that the load power is match with the rated power of UPS
and the battery specifications.
Prohibitions
1. There is high voltage presented inside the UPS, non-licensed company or technical
personnel is not allowed to open the case cover arbitrarily, otherwise there might be a
danger of electric shock and loss of warranty eligibility.
2. When applied to the following equipment, please contact the dealer or in
advance since there might be special requirements and design for the application, setting,
management and maintenance:
A Precision industrial, scientific and medical instruments and equipment;
B Equipment that might endanger physical safety such as elevator etc;
C Load equipment with large startup current and negative power;
3. Do not place battery to re in order to avoid possible explosion.

Electric Safety
1. Before electricity is switched on, make sure earthing is properly done and wire and
battery polarity are correctly connected.
2. Battery protection device must be configured with over-current breaker of rated
specifications.
3. When UPS relocation or wire reconnection is necessary, AC and battery should be
switched off and UPS should be completely turned off, otherwise there might be a danger
of electric shock because output terminal might be still electrified.
4. Please use specified appendix devices and accessories.
5. Prior to connecting the power distribution system to the UPS, make sure the rated
quadrupole over-current breaker is installed to break off all the input lines and thus
prevent a risk of electric shock.
Battery Safety
1. Battery service lifetime will be shortened as ambient temperature rises. Replace
batteries periodically to guarantee normal UPS performance and sufficient back-up time.
2. Only personnel with proper expertise can carry out the maintenance of accumulator
batteries.Replacement of accumulator batteries requires a match of same type and
model
with equal quantity.
3. As accumulator batteries may contain potential electric shock and short-circuit current
danger, to avoid accidents that might be thus resulted, the following warnings should be
observed during battery replacement:
4. Do not expose accumulator battery to fire in order to avoid possible explosion that
might endanger physical safety.
5. Non-professionals are not allowed to open or destroy accumulator batteries for
electrolytes in batteries contain strong acid and other dangerous substances which will
cause damages to both human skins and eyes. Should electrolytes come into any contact
with human body unintentionally, rinse with clean water and seek medical advice.
A. Do not wear watches, rings or similar metallic items;
B. Use insulated tools;
C. Put on rubber shoes and gloves;
D. Do not place metallic tools or similar metallic parts on the batteries;
E. Switch off load connected to the batteries before dismantling battery connection
6. Do not cause battery positive and negative polarity short circuit otherwise electric shock
or information may occur.

Maintenance
1. Working environment and storage means can affect the service term and reliability of this
product to some extent. Therefore, the product is not suitable for performance in the
following environment:
A. Locations where temperature exceeds the maximum or goes below the minimum
temperature as required by technical specifications or humidity is improper (temperature
range: 0-40℃ ; relative humidity range: 0-95%).
B. Locations where vibration and collision are constant;
C. Locations where metallic dusts,corrosive substances as well as salts and
inflammable gases are present.
2. For long-term inaction, UPS (without batteries) should be kept in dry environment with
temperature ranging from -25-55℃. Before start-up, ambient temperature should be brought
back to 0 or above for a certain period of time (above 2 hours).
3. Keep good ventilation; otherwise, it will lead to internal temperature rise, shorten the
lifetime of the components and thus shorten the lifetime of the UPS.
4. For long-term inaction, the battery should be charged once every three moths in normal
temperature environment and once every two moths in high temperature environment with
no less than 10 hours; no-load discharge is not allowed, and the battery continuous
discharge time should not exceed 14 hours.

Contents
Chapter 1 Briefintroduction....................................................................................................1
1.1 Product introduction.........................................................................................................1
1.2 Frequently used symbols.................................................................................................2
Chapter 2 Exterior appearance.............................................................................................3
2.1 Unpacking inspection......................................................................................................3
2.2 Exterior figure..................................................................................................................5
2.3 LCD Panel instructions....................................................................................................6
Chapter 3 Installation instructions.........................................................................................8
3.1 Installation Notice............................................................................................................8
3.2 Installation space............................................................................................................ 8
3.3 Installation and wiring connection diagram....................................................................10
3.4 Requirements of wiring cables and protect device for JP9960 series UPS .................14
3.5 Parallel UPS installation................................................................................................15
3.6 Procedures of connecting battery bank to UPS.............................................................18
Chapter 4 Operation ............................................................................................. .............19
4.1Single UPS operation.....................................................................................................19
4.2Parallel UPS operation...................................................................................................27
Chapter 5 Communication Interface...................................................................................29
Chapter 6 Transportation, Maintenance and Troubleshooting............................................32
Appendix 1Techinial parameters and specifications............................................................34
Appendix 2 Light reference table.........................................................................................35

1
1.1 Product introduction
1.1 Product introduction
JP9960 series products are high-efficiency ,double conversion, pure-online and three phase
input and three phase output UPS.This series provides perfect solution for power source
protection and successfully solves problems such as blackout, be widely used in
computer equipment, communications equipment and other controlling equipments, and
under the impact of the load for a particular election can be installed accessories to deal
with complex industrial environment. Therefore, JP9960 Series
Products can be applied in a diversified multi-industries field such as telecommunications,
financing, transportation, government, manufacturing and energy sectors.
Manifold function of JP9960 series products to provide high-quality power supply
guarantee for your device:
Advanced DSP digital control technology to effectively improve product
performance
and system reliability
N + X parallel redundancy ( support sharing batteries in parallel)
Excellent performance of industrial environment protection
Economy and security of ECO mode of operation allows UPS efficiency of more
than 98%
High-definition LCD interface for human-machine interaction, intuitive and
convenient operation
Powerful communication interface and remote monitoring
Abundant optional accessories, can be flexibly configured according to actual
demands.

2
1.2 Frequently used symbols
The following symbols will be frequently used in this User Manual as well as in the
process of actual application; therefore, correct identification and understanding of their
connotations prove necessary.

3
Chapter 2 Exterior appearance
2.1 Unpacking inspection
1. Unpack and there should be:
1) UPS
2) Winpower Disc
3) Accessories including user manual ,RoHS card and two keys of the door
2. Check whether the UPS is damaged during the process of transportation or not. Should
any damage be observed or parts be found missing, do not start the machine. Contact the
forwarder and distributor immediately.
Note: Make sure that the heights of the door and some other obstacles are
Appropriate

4
Note: 1) JP9960 20K/30K/40K and Long back up models
are provided with brake pads, rotate the wrench
(NO.19) clockwise until the brake pad revolves to
the ground, which can prevent the unit from moving.
2) For JP9960 60K/80K models, remove the iron brackets fixing the UPS with
a wrench firstly, then move the frame smoothly from the pallet to the ground, and
fix the UPS with the iron brackets again.
Questo manuale è adatto per i seguenti modelli
5
Indice
Altri manuali JALpower UPS
Manuali UPS popolari di altre marche

Pylontech
Pylontech Victron & Pylontech US5000 Manuale utente

Tecnoware
Tecnoware EVO DSP PLUS MM 6.8 Manuale utente

Mecer
Mecer ME-1000-WTU Manuale utente

Mustek
Mustek PowerMust 530(B) Plus Manuale di installazione e funzionamento

Emerson
Emerson Liebert NXL series Manuale utente

MAKELSAN
MAKELSAN BOXER SERIES Manuale utente