5PPS
FM Rev. 05/05
4.0 Operation
The PPS comes with either a N/O or N/C switch (at no flow), as specified by order code.
The switching function is factory set and is not user adjustable. The reed switch of the
PPS may be used to switch loads directly as long as switch limits are not exceeded
(Table 2.1). For DC circuits, we strongly suggest the use of a 1A, 1N4000 series diode
wired in parallel with the load (e.g. band or cathode toward positive). For AC loads, use
an RC circuit or MOV (metal oxide varistor) wired in parallel with the switch.
It is important to realize that large capacitive or inductive loads (such as relay coils, light
bulbs, etc.) typically have momentary voltage/current requirements far exceeding any of
the rated operating values of the reed switch. If in doubt, we suggest the use of a higher
capacity isolation relay (such as the Kobold MSR or RL series) to protect your model
PPS flow switch.
4.1 Adjustment of the Setpoint
The switch setpoint is adjustable only via the paddle length. If a higher switchpoint is
desired, paddle length may be changed by additional trimming of the paddle. There is no
specified procedure for this, but in general, for a given pipe diameter:
1. Longer Paddle: Lower switch point
2. Shorter Paddle: Higher switch point
5.0 Maintenance
The simplicity of the device ensures that it is nearly maintenance free. If the media is
dirty, it is possible that the dirt will deposit in the switch body and impede the motion of
the ceramic magnet. In this case, remove the device and clean as appropriate. Do not
use sharp objects to scrape away dirt as this may damage the PPS. After cleaning,
reinstall as per the installation instructions.
6.0 Arrival of Damaged Equipment
Your instrument was inspected prior to shipment and found to be defect-free. If damage
is visible on the unit, we advise that you carefully inspect the packing in which it was
delivered. If damage is visible, notify your local carrier at once, since the carrier is liable
for a replacement under these circumstances. If your claim is refused, please contact
KOBOLD Instruments for further advisement.
7.0 Need help with your PPS
Call one of our friendly engineers at 412-788-2830.