Lenze AC Tech POSITIONSERVO Manuale utente

Modbus Communication Module
Communications Interface Reference Guide
P94MOD01B

2P94MOD01B
Copyright ©2005 by AC Technology Corporation.
All rights reserved. No part of this manual may be reproduced or transmitted in any form without written
permission from AC Technology Corporation. The information and technical data in this manual are subject to
change without notice. AC Tech makes no warranty of any kind with respect to this material, including, but not
limited to, the implied warranties of its merchantability and fitness for a given purpose. AC Tech assumes no
responsibility for any errors that may appear in this manual and makes no commitment to update or to keep
current the information in this manual.
MotionView®, PositionServo®, and all related indicia are either registered trademarks or trademarks of Lenze
AG in the United States and other countries.
ModBus®is a registered trademark of ‘Schneider Automation’.
This document printed in the United States of America
About These Instructions
This documentation applies to Modbus RTU and Modbus TCP/IP communications for the PositionServo drive and
should be used in conjunction with the PositionServo User Manual (S94P01) that shipped with the drive. These
documents should be read carefully as they contain important technical data and describe the installation and
operation of the drive and this option module.

3 P94MOD01B
Table of Contents
1. Safety Information...................................................................................................4
1.1 Warnings, Cautions & Notes.............................................................................................4
1.2 Reference Documents...................................................................................................... 6
2. Introduction.............................................................................................................6
2.1 Modbus Overview ........................................................................................................... 6
2.2 Ethernet TCP/IP Modbus Configuration............................................................................ 6
2.3 Modbus RTU Implementation Specification ..................................................................... 7
3. Installation ..............................................................................................................9
3.1 Mechanical Installation .................................................................................................... 9
3.2 Electrical Installation....................................................................................................... 10
4 Modbus Protocol Details.........................................................................................11
4.1 Data Transmission.......................................................................................................... 11
4.2 Register Numbering........................................................................................................ 12
4.3 Supported Modbus Function Codes................................................................................. 12
5 Drive Memory Access ............................................................................................12
5.1 Mapping from Drive Variable to the Register Address...................................................... 12
5.2 Register Reading ............................................................................................................ 13
5.3 Register Writing .............................................................................................................. 13
5.4 No Response Conditions ................................................................................................. 14
5.5 Exception Responses ...................................................................................................... 15
6 Commissioning ......................................................................................................16
6.1 Drive Monitoring ............................................................................................................. 16
6.2 Controlling the Drive .......................................................................................................16
6.3 Changing Drive Parameters ............................................................................................ 16
7 Programming Parameters ......................................................................................16
7.1 Negative Number Transmission ...................................................................................... 16

4P94MOD01B
1. Safety Information
1.1 Warnings, Cautions & Notes
General
Some parts of Lenze controllers (frequency inverters, servo inverters, DC controllers) can be live, with the
potential to cause attached motors to move or rotate. Some surfaces can be hot.
Non-authorized removal of the required cover, inappropriate use, and incorrect installation or operation creates
the risk of severe injury to personnel or damage to equipment.
All operations concerning transport, installation, and commissioning as well as maintenance must be carried
out by qualified, skilled personnel (IEC 364 and CENELEC HD 384 or DIN VDE 0100 and IEC report 664 or DIN
VDE0110 and national regulations for the prevention of accidents must be observed).
According to this basic safety information, qualified skilled personnel are persons who are familiar with the
installation, assembly, commissioning, and operation of the product and who have the qualifications necessary
for their occupation.
Application as directed
Drive controllers are components which are designed for installation in electrical systems or machinery. They
are not to be used as appliances. They are intended exclusively for professional and commercial purposes
according to EN 61000-3-2. The documentation includes information on compliance with the EN 61000-3-2.
When installing the drive controllers in machines, commissioning (i.e. the starting of operation as directed)
is prohibited until it is proven that the machine complies with the regulations of the EC Directive 98/37/EC
(Machinery Directive); EN 60204 must be observed.
Commissioning (i.e. starting of operation as directed) is only allowed when there is compliance with the EMC
Directive (89/336/EEC).
The drive controllers meet the requirements of the Low Voltage Directive 73/23/EEC. The harmonised standards
of the series EN 50178/DIN VDE 0160 apply to the controllers.
The availability of controllers is restricted according to EN 61800-3. These products can cause radio
interference in residential areas.
Installation
Ensure proper handling and avoid excessive mechanical stress. Do not bend any components and do not
change any insulation distances during transport or handling. Do not touch any electronic components and
contacts.
Controllers contain electrostatically sensitive components, which can easily be damaged by inappropriate
handling. Do not damage or destroy any electrical components since this might endanger your health!
Electrical connection
When working on live drive controllers, applicable national regulations for the prevention of accidents (e.g. VBG
4) must be observed.
The electrical installation must be carried out according to the appropriate regulations (e.g. cable cross-sections,
fuses, PE connection). Additional information can be obtained from the national regulation documentation. In
the United States, electrical installation is regulated by the National Electric Code (nec) and NFPA 70 along with
state and local regulations.

5 P94MOD01B
The documentation contains information about installation in compliance with EMC (shielding, grounding, filters
and cables). These notes must also be observed for CE-marked controllers.
The manufacturer of the system or machine is responsible for compliance with the required limit values
demanded by EMC legislation.
Operation
Systems including controllers must be equipped with additional monitoring and protection devices according to
the corresponding standards (e.g. technical equipment, regulations for prevention of accidents, etc.). You are
allowed to adapt the controller to your application as described in the documentation.
DANGER!
• After the controller has been disconnected from the supply
voltage, live components and power connection must not be touched
immediately, since capacitors could be charged. Wait at least 60
seconds before servic-ing the drive Please observe the corresponding
notes on the controller.
• Do not continuously cycle input power to the controller more than once
every three minutes.
• Please close all protective covers and doors during operation.
WARNING!
Network control permits automatic operation of the inverter drive.
The system design must incorporate adequate protection to prevent
personnel from accessing moving equipment while power is applied to
the drive system.
Pictographs used in these instructions:
Pictograph Signal Word Meaning Consequence if Ignored
DANGER! Warning of Hazardous Electrical
Voltage.
Reference to an imminent
danger that may result in death
or serious personal injury if the
corresponding measures are
not taken.
WARNING! Impending or possible danger to
personnel
Death or injury
STOP! Possible damage to equipment Damage to drive system or its
surroundings
NOTE Useful tip: If note is observed, it
will make using the drive easier

6P94MOD01B
1.2 Reference Documents
• Modbus Application Protocol Specification V1.1
To view this specification, visit: http://www.modbus.org/tech.php
or: http://www.modbus-ida.org/specs.php
• Modbus Over Serial Line Specification & Implementation Guide V1.0.
Refer to: http://www.modbus.org/
• PositionServo Programming Manual: PM94P01
Refer to: http://www.actech.com
NOTE:
The complete list of variables can be found in Appendix A of the PositionServo
Programming Manual (PM94P01).
2. Introduction
This reference guide assumes that the reader has a working knowledge of Modbus RTU or Modbus TCP/IP
Protocol and familiarity with the programming and operation of motion control equipment. This guide is intended
as a reference only. The PositionServo drive supports both Modbus TCP/IP and Modbus RTU communication
protocols. Modbus TCP/IP communications can be established via the PositionServo drive’s Ethernet port.
When using the RS485 option module (P/N E94ZARS41), Modbus RTU is the standard communication protocol.
Refer to Section 3 for installation of the RS485 option module.
2.1 Modbus Overview
Modbus is an internationally accepted asynchronous serial protocol designed for commercial and industrial
automation applications. The Modbus RTU architecture is based upon a Master-Slave orientation. In Modbus
RTU, the PositionServo drive always acts as the slave, responding to reads and writes from the Master. In
Modbus TCP/IP, the PositionServo drive can act as the Master or a slave. While the Modbus RTU protocol does
not specify the physical layer, the E94ZARS41 module uses a 2-wire RS-485 physical interface which is quite
common and well suited for the industrial environment. The E94ZARS41 module provides both galvanic and
optical isolation of the physical interface.
2.2 Ethernet TCP/IP Modbus Configuration
The PositionServo Drive is a standard ModbusTCP slave device and its IP address, subnet mask and default
gateway can be configured using MotionView software. It supports up to two (2) simultaneous connections
on the standard Modbus TCP port 502. On open connections with no activity for more then 75 seconds, the
PositionServo Drive sends a TCP keep-alive message every 75 seconds to check the connection status.

7 P94MOD01B
2.3 Modbus RTU Implementation Specification
Typical communications between master and slave would be:
• Write commands from Master
- Run command
- Reference values
- Modification of Drive operating parameters
• Read requests from Master
- Reporting of drive status
- Fault status (and fault history)
The PositionServo drive most nearly conforms to the Modicon® Micro 84 in capabilities. This may be of
importance when configuring networks for DDE Servers.The following table identifies the Modbus serial
communication specifications. If the specification is fixed (non-adjustable) the value is shown under “Range”,
if the specification is selectable, the table identifies the Parameter and available range of selections.
Table 1: ModBus Communications Module Parameters
Description Type Range
Baud Rate Selectable 19200, 38400, 57600, 115200
Data Bits Fixed 8
Parity/Stop Bits Selectable Even/1, Odd/1, None1, None2
Network Address Selectable 1 - 247
The following communication parameters are available:
RS485 configuration – If the value of this parameter is ‘Modbus slave’, the modbus slave protocol is enabled
on the RS485 port. If the value is ‘Normal’, the RS485 uses PPP (Point-to-Point Protocol). In Modbus ‘Slave’
mode the drive is configured to receive commands from the Modbus Master.
Modbus Baud Rate – the RS485 baud rate in Modbus mode. The default configuration uses 2 stop bits and
no parity. Stop and parity bits are configurable from the same RS485 configuration menu.
Modbus Reply Delay – The delay introduced after receiving a Modbus request and before sending a reply.
Note that this delay will always be >= 3.5 characters as required by the Modbus specification. Some Modbus
master devices are slow and an increase of the ‘Modbus reply delay’ value may be required to successfully
work with these devices.
Each slave device in the Modbus network must have its own unique network address. The ‘Addr’ submenu
on the drive display and the front panel buttons can be used to set the Modbus network address. The Modbus
Master has no address.
The PositionServo is a Modbus slave device in a single master, multiple slave network. Sometimes slave
devices are named servers because they wait for requests. Therefore the PositionServo drive can be one of
many slaves communicating to the Modbus master. Most terminals are configured as masters with a Modbus
generic driver.
The PositionServo drive uses the required delay of 3.5 characters time between packets to determine the end
of a packet.
The following Modbus functions are supported:
1. 03 (0x03) Read Multiple Holding Registers
2. 16 (0x10) Write Multiple Holding Registers

8P94MOD01B
Note that all parameters in the PositionServo drive are 32 bit values and they cannot be accessed by Write
Single Register functions or Read Holding Register functions with a length of 1 (one 16 bit register). The
user has to use two 16 bit registers to read/write one 32 bit register and for this purpose should reserve 2
consecutive addresses per 32 bit register.
31
Discrete Number
17 16 0
30
ModBus Discrete Number and 32-bit Format
14 1
15
Bit
29 28 27 26 25 24 23 22 21 20 19 18 13 12 11 10 9 8 7 6 5 4 3 2
16
215
1 3 4 567 8 9 10 11 12 13 14
Hex value
x0001
x4000 x0002
x8000 x2000 x1000 x0800 x0400 x0200 x0100 x0080 x0040 x0020 x0010 x0008 x0004
Figure 1: 32 bit Pack Format Discrete Data
The user doesn’t have any discrete functions but can use holding registers with DWORD (integer 32 bit) access
to write discrete values.
When the PositionServo drive receives a Modbus message, the requested function is executed and the drive
can reply with a ‘Normal’ message, an ‘Exception’ Message or a ‘No’ message. These messages are described
in the Modbus Application Protocol Specification V1.1.
The PositionServo drive also supports a Modbus broadcast address. In this case the PositionServo drive receives
a correct Modbus request and executes it without sending any reply back.
The DWORD (double word) and FLOAT numbers are sent with the LOW WORD FIRST convention by the
PositionServo drive.
15
Register_L (Bits 15 ... 0)
1 0 16
14
DWORD_ Unsigned Single Precision 32-bit Format
Register_H (Bits 31... 16)
30 17
31
HByte HByte
LByte LByte
13 12 11 10 9
15 8 7 6 54 3 229 28 27 26 25 24 23 22 21 20 19 18
Figure 2: DWORD Format
31
1bit
sign
8 bits
exponent
23 bits
mantissa
23 22 0
30
IEEE 754 Floating Point: Single Precision 32-bit Format
Figure 3: FLOAT Format
Note: Some terminals may have to be configured appropriately in order to accept such a WORD order.

9 P94MOD01B
3. Installation
This section is only applicable to Modbus RTU communication with the RS485 option module, E94ZARS41.
3.1 Mechanical Installation
Install the RS485 Communications Module as illustrated in Figure 4.
Disconnect power from drive and wait 3 minutes.
Remove the two COMM module screws that secure Option Bay 1.
With a flat head screwdriver, pry up the Option Bay 1 cover plate.
Install the RS485 COMM Module (E94ZARS41) in Option Bay 1.
Secure with two COMM module screws (max torque: 0.3Nm/3lb-in).
S921
Figure 4: Installation of RS485 Communications Module

10P94MOD01B
3.2 Electrical Installation
Table 2 and Figure 5 illustrate the pinout of the PositionServo RS485 Option Module E94ZARS41. The 3-pin
connector provides 2-wire plus isolated ground connection to the network.
Table 2: RS485 Interface Pin Designation
Terminal Name Description
1 ICOM Isolated Common
2 TxB (+) Transmit B (+)
3 TxA (-) Transmit A (-)
Figure 5: RS485 Interface Pin Designation
Connections and Shielding
Figure 6 illustrates the connection of the cables for a PositionServo drive in a Modbus master/slave network.
A 120ohm (1%) termination is necessary between the high and low terminals of the first and last slaves in the
network. Note that while ModBus serial protocol supports up to 247 slave addresses, the maximum number
of slave nodes for a network is dictated by the Modbus Master
PLC/PC
Modbus Master
PositionServo
Modbus Slave
PositionServo
Modbus Slave
GND ABGND GND
TxA TxATxB TxB
120Ω
120Ω
Modbus Network
Modbus Network
Figure 6: 120W(1%) Termination in RS485 Network
Indice
Altri manuali Lenze AC Tech Unità di controllo
Manuali Unità di controllo popolari di altre marche

Festo
Festo Compact Performance CP-FB6-E Manuale elenco delle parti

Elo TouchSystems
Elo TouchSystems DMS-SA19P-EXTME Manuale utente

JS Automation
JS Automation MPC3034A Manuale utente

JAUDT
JAUDT SW GII 6406 Series Guida rapida

Spektrum
Spektrum Air Module System Manuale utente

BOC Edwards
BOC Edwards Q Series Manuale utente