INT500 EN
1
Introduction
WARNING
Safety Information
This Insulation Tester is an accurate, professional industry tool
for measuring ACV, DCV, Frequency, Low Pass Filter, Earth-
Bond Resistance, Capacitor, Insulation Resistance.
Understand and follow operating instructions carefully.
• If the equipment is used in a manner not specied by the
manufacturer, the protection provided by the equipment may
be impaired.
• Always use proper terminals, switch position, and range for
measurements.
• To reduce the risk of re or electric shock, do not use this
product around explosive gas or in damp locations.
• Verify the Meter operation by measuring a known voltage. If
in doubt, have the Meter serviced.
• Do not apply more than the rated voltage, as marked on
Meter, between terminals or between any terminal and earth
ground.
• To avoid false readings that can lead to electric shock and
injury, replace battery as soon as low battery indicator blinks /
appears.
• Avoid working alone so that assistance can be rendered.
• Do not use the Tester if the Tester is not operating properly or
if it is wet.
• Individual protective device must be used if hazardous live
parts in the installation where the measurement is to be
carried out could be accessible.
• Disconnect the test leads from the test points before changing
the position of the function rotary switch.
• Never connect a source of voltage when the function rotary
switch is not in voltage position.
• When using test leads or probes, keep your ngers behind
the nger guards.
• Use caution with voltages above 30Vac rms, 42 Vac peak, or
60Vdc. These voltages pose a shock hazard.
• Remove test lead from Meter before opening the battery door
or Meter case.

INT500 EN
2
• DO NOT USE the test leads when the internal white insulation
layer is exposed.
• DO NOT USE the test leads above maximum ratings of CAT.
Environment, voltage and current, that are indicated on the
probe and the probe tip guard cap.
• DO NOT USE the test leads without the probe tip guard cap
in CAT III and CAT IV environments.
• Probe assemblies to be used for MAINS measurements shall
be RATED as appropriate for MEASUREMENT CATEGORY
III OR IV according to IEC 61010-031 and shall have a
voltage RATING of at least the voltage of the circuit to be
measured.
• Only replace the blown fuse with the proper rating as
specied in this manual.
• Do not attempt a resistance measurement when the open
voltage is above the fuse protection rating. Suspected open
voltage can be checked with voltage function.
• Never attempt a voltage measurement with the test lead
inserted into the Ω input terminal.
• Disconnect circuit power and discharge all high-voltage
capacitors before testing resistance, continuity, or
capacitance.

INT500 EN
3
Symbols as marked on the Meter and
Instruction manual
Risk of electric shock
See instruction manual
DC measurement
Equipment protected by double or reinforced insulation
Battery
Fuse
Earth
AC measurement
Bluetooth
Conforms to EU directives
Do not discard this product or throw away.
Both direct and alternating current
This product CONFORMS TO UL STD 61010-1,
61010-2-034
Unsafe Voltage
Maintenance
Cleaning
To alert you to the presence of a potentially hazardous voltage,
when the Tester detects a voltage ≧30 V in insulation test, or
a voltage overload (OL), the ” “ symbol is displayed and High
voltage indicator is turned on.
Do not attempt to repair this Meter. It contains no user service
able parts. Repair or servicing should only be performed by
qualied personnel.
Periodically wipe the case with a dry cloth and detergent. Do
not use abrasives or solvents.

INT500 EN
4
The Meter Description
Front Panel Illustration
Display
Function button
Pass indicator
High Voltage
indicator
Funtions & Power
On/O
Ω Input
V insulation
Input
Common Input
INSULATION
>660V
TEST
COM
600V
CAT IV
315mA
FUSED
5 Sec
Del Last
SETUP
RECALL
PI/DAR/t
PASS
V
LPF
OFF
TRUE RMS
L nk
100M
6100GK
10GK
1GK
100M
10M
1M
0
MEM
TEST
LOCK
AutoSense
RENPIDAR
COMPARE
m
A
MK
G
Hz
V
APO
LPF
R
V
A
MK
G
m
F
AC S
DC 0
V

INT500 EN
5
Measuring ACV/DCV : Auto sense function
Auto sense mode: The meter displays ACV or DCV whichever
is higher (>1V).
If the measured voltage is above 660Vac/dc, "> 660Vac/dc" will
appear on the display.
30V
LPF
INSULATION
COM
600
0
0
600
V
AC
Hz
V
DC
AutoSense
AutoSense
V
LPF
V
V

INT500 EN
6
Measuring Capacitance
WARNING
When connecting the test leads to the DUT (Device Under
Test) connect the common test leads before connecting the live
leads; When removing the test leads, remove the test live leads
before removing the common test leads.
Don’t apply more than AC/DC 600V between the V-COM
terminals.
INSULATION
COM
COMP LOCK
F
STORE
V

INT500 EN
7
Wireless Link
L nk
L nk
L nk
The meter uses Bluetooth low energy (BLE) V5.0 wireless
technology to download the stored data. The open-air
communication range is up to 6m. The LINK icon of the
meter will freeze on LCD after the connection establishes
successfully.

INT500 EN
8
Switch Auto Voltage sense/ACV/DCV/LPF
function when the rotary switch is in voltage
position
Do not use the High Frequency Rejection (Low Pass Filter) to
verify the presence of hazardous voltages. Voltages greater
than what is indicated may be present. First, make a voltage
measurement without the lter to detect the possible presence
of hazardous voltage. Then select the lter function.
600
0
V
AC
Hz
AutoSense
600
0
LPF
AC
V
Press
600
0
V
AC
Hz
Press>2Sec
600
0
V
DC
Press
Press
Press
SETUP
SETUP
SETUP
SETUP
SETUP
WARNING

INT500 EN
9
Measuring Earth-Bond Resistance (Continuity)
0
0
&
hold
Press
TEST
0
&
hold
Press
TEST
COMCOM
100 K
10K
1 K
100
10
1
0
100 K
10K
1 K
100
10
1
0
TEST
m
A
m
A
R
R
1. Before starting the test :
(a) The circuit under test must be completely de-energized.
(b) Check the fuse is good. See the chapter “Testing the
fuse”.
(c) Short the test leads before measurement, and press the
Function button to zero the wire resistance of probe. If
the wire resistance is <10Ω, the resistance oset value
will be saved, and the “->0<-” symbol will be displayed
on LCD.
2. Lock mode :
Press the Lock button to enter the Lock Mode.
Then press the TEST button to start the test. The test voltage
will continue to be applied until the TEST/LOCK button is
Indice
Altri manuali Power Probe Apparecchiature di prova
Manuali Apparecchiature di prova popolari di altre marche

SMART
SMART KANAAD SBT XTREME 3G Series Manuale utente

Agilent Technologies
Agilent Technologies BERT Serial Manuale utente

Agilent Technologies
Agilent Technologies N3280A Manuale utente

Vernier
Vernier Go Direct Voltage Manuale utente

Lifeloc
Lifeloc R.A.D.A.R. Manuale utente

Fluke
Fluke T5-600 Istruzioni per l'uso e l'installazione