Page 9 of 32
www.sgm-lektra.eu
VLW602 - configuration and calibration
6-CONFIGURATION AND CALIBRATION
Via the VLW602 the operator can: access any transmitter function, change configuration parameter settings and other
functions.
6.1 VLW602FEATURES
The VLW602 program module has 4 buttons which allow to perform all operational, control and programming
instrument functions.
In the configuration menus, is possible:
1. Submenus and parameters access; press to select and press to access.
2. Parameter options choice: Press to select the option and press to store the option.
Press to exit without storing.
3. Configure the parameter values; in some parameters the configuration is done by setting a value
(eg., in the SET DISTANCE 4mA parameter is possible to change the the corresponding distance value, in mm):
press to select the digit to be modified (the digit is highlighted in inverse ),
press to change the high lighted digits number, press to save the set value and exit automatically.
Press to exit without storing.
!
LEFT ARROW button:
• Exit configuration
• Back to previous menu
• Echo map (from RUN mode)
UP ARROW button:
• Parameter values modification
• Parameter scroll
SCROLL button:
• Cursor movement (to the right)
• Parameter scroll
ENTER button:
• Configuration access
• Options confirmation
• Parameters values confirmation
Displayed at the top alerts that there is a generic error; press SCROLL to show the message that
indicates the present error type.
The PTU5_ returns automatically to RUN mode.
!
Displayed at the top alert thet the PTU sensor is not communicating with VLW602.