Wrong wiring will lead to breakdown or electrical shock of the instrument, please read this
operation manual clearly before installation.
zMake sure to remove AC power from the transmitter before wiring input, output connections,
and remove it before opening the transmitter housing.
zThe installation site of the transmitter should be good in ventilation and avoid direct
sunshine.
zThe material of signal cable should be special coaxial cable. Strongly recommend using our
coaxial cable. Do not use normal wires instead.
zAvoid electrical surge when using power. Especially when using three-phase power, use
ground wire correctly.
zThe internal relay contact of the instruments is for alarm or control function. Due to
safety, please must connect to external relay which can stand enough ampere to make
sure the safety operation of the instruments. (Please refer to chapter 4.5“Illustration of
electrical connection”)
3.Assemblyandinstallation
3.1 Transmitter installation: This transmitter can be installed through panel mounting,
wall mounting and pipe mounting.
Installation of panel mounting: First,prepare a square hole of 138 x 138mm on the panel box,
and then insert the transmitter directly into the panel box. Insert the accessorial mounting
bracket from the rear, and make it be fixed in to pickup groove.
3.2 Illustration of panel mounting:
2. Precautions for installation
138mm
138m