SUTO S011 Manuale

English
Instruction and Operation Manual
S011
Pressure Transmitter

Dear Customer,
Thank you for choosing our product.
The operating instructions must be read in full and carefully observed
before you start up the device. The manufacturer cannot be held liable
for any damage which occurs as a result of non-observance or non-
compliance with this manual.
Should the device be tampered with in any manner other than a
procedure which is described and specified in the manual, the warranty
is cancelled and the manufacturer is exempt from liability.
The device is destined exclusively for the described application.
S TO offers no guarantee for the suitability for any other purpose.
S TO is also not liable for consequential damage resulting from the
delivery, capability or use of this device.
2 S011

Table of contents
1 Safety Instructions.......................................................................4
2 Registered Trademarks..................................................................6
3 Application..................................................................................7
4 Features......................................................................................7
5 Technical Data.............................................................................8
5.1 General.................................................................................8
5.2 Electrical Data........................................................................8
5.3 Output Signals.......................................................................9
5.4 Accuracy ..............................................................................9
6 Dimensional Drawing....................................................................9
7 Installation ...............................................................................10
7.1 Installation Requirements......................................................10
7.2 Installation Procedure............................................................10
7.3 Electrical Connection.............................................................11
8 Signal Output.............................................................................12
8.1 Data Format.........................................................................12
8.2 Protocol Frame Analysis.........................................................12
8.3 Register...............................................................................13
9 Configuration.............................................................................14
10 Calibration...............................................................................15
11 Maintenance.............................................................................16
12 Disposal or Waste.....................................................................16
S011 3

1 Safety Instructions
1 Safety Instructions
Please check if this instruction manual matches with the
product type.
Please observe all notes and instructions indicated in this
manual. It contains essential information which have to be
observed before and during installation, operation and
maintenance. Therefore this instruction manual has to be read carefully
by the technician as well as by the responsible user / qualified
personnel.
This instruction manual has to be available at the operation site of the
Pressure Transmitter at any time. In case of any obscurities or
questions, regarding this manual or the product, please contact the
manufacturer.
W RNING!
Compressed air!
ny contact with quickly escaping air or bursting
parts of the compressed air system can lead to
serious injuries or even death!
•Do not exceed the maximum permitted pressure range.
•Only use pressure tight installation material.
•Avoid that persons get hit by escaping air or bursting parts of the
instrument.
•The system must be pressureless during maintenance work.
W RNING!
Voltage used for supply!
ny contact with energized parts of the product, may
lead to a electrical shock which can lead to serious
injuries or even death!
•Consider all regulations for electrical installations.
•The system must be disconnected from any power supply during
maintenance work.
•Any electrical work on the system is only allowed by authorized
qualified personal.
4 S011

1 Safety Instructions
TTENTION!
Permitted operating parameters!
Observe the permitted operating parameters, any
operation exceeding this parameters can lead to
malfunctions and may lead to damage on the
instrument or the system.
•Do not exceed the permitted operating parameters.
•Make sure the product is operated in its permitted limitations.
•Do not exceed or undercut the permitted storage and operation
temperature and pressure.
•The product should be maintained and calibrated frequently, at
least annually.
General safety instructions
•It is not allowed to use the product in explosive areas.
•Please observe the national regulations before/during installation
and operation.
Remarks
•It is not allowed to disassemble the product.
•Always use spanner to mount the product properly.
TTENTION!
Measurement values can be affected by malfunction!
The product must be installed properly and
frequently maintained, otherwise it may lead to
wrong measurement values, which can lead to
wrong results.
•Do not exceed the maximum operation temperature at the sensors
tip.
S011 5

1 Safety Instructions
Storage and transportation
•Make sure that the transportation temperature of the sensor is
between -40 ... +85°C.
•For transportation it is recommended to use the packaging which
comes with the sensor.
•Please make sure that the storage temperature of the sensor is
between -40 ... +85°C.
•Avoid direct V and solar radiation during storage.
•For the storage the humidity has to be <90%, no condensation.
2 Registered Trademarks
S TO®
Registered trademark of S TO iTEC
MODB S®
Registered trademark of the Modbus Organization, Hopkinton, SA
6 S011

3 Application
3 pplication
The S011 Pressure Transmitter is designed to measure the pressure of
compressed air and gases within the permissible operating parameter.
Detailed parameters can be found in the technical data section.
The S011 Pressure Transmitter can measure pressure values in MPa,
kPa, or bar.
The S011 Pressure Transmitter is mainly used in compressed air
systems in industrial environment. It is not developed to be used in
explosive areas. For the use in explosive areas please contact the
manufacturer.
4 Features
•Highly accurate and affordable industrial Pressure Transmitter
•Excellent anti-interference capability (EMC, EMI)
•Salt-spray, temperature and humidity test
•IP65 protection
•Modbus/RT interface
S011 7

5 Technical Data
5 Technical Data
5.1 General
Parameters Standard unit pressure: MPa
Sensor Thin-film measuring cell
Measuring medium Air, gas (non corrosive gas)
Measuring range 0 ... 1.6 MPa (g) (S694 2559)
0 ... 4.0 MPa (g) (S694 2562)
0 ... 0.16 MPa (a)) (S694 2563)
Temperature of the
meas. medium
-40 ... +85°C
Operating pressure 2 x F.S.
Burst pressure 2.5 x F.S.
Storage temperature -40 ... +85°C
Operating temperature -40 ... +85°C
Casing material Stainless steel
Protection class IP65
Dimensions See dimensional drawing on the next page
Screwing thread G 1/4” A (ISO 228/1)
Electrical connection M12, 5 pins
Stability ± 0.1% F.S.
Vibration resistance 20 … 2000 Hz, 25g
Weight 70g
5.2 Electrical Data
Power supply 24 VDC (12 ... 36 VDC)
8 S011

5 Technical Data
5.3 Output Signals
Modbus output Modbus RT
Baud rate: 19200
Device address: last two digits of the serial
number
Framing/ Parity/ Stop bit: 8,N,1
Response timeout: 1 second
Response delay : 0 ms
Inter-frame spacing : 7 char
5.4 ccuracy
Accuracy S694 2559 / S694 2562:±0.25% F.S.
S694 2563:0.5% F.S.
Repeatability S694 2559 / S694 2562:±0.1% F.S.
S694 2563:0.25% F.S.
6 Dimensional Drawing
S011 9

7 Installation
7 Installation
Please make sure that all components listed below are included in your
package.
Qty Description Item No.
1 S011 Pressure Transmitter S694 2559 (1.6 MPa (g))
S694 2562 (4.0 MPa (g))
S694 2563 (0.16 MPa (a))
1 M12 connector C219 0060
1 Instruction manual No P/N
1 Calibration certificate No P/N
TTENTION!
Wrong measurement is possible, if the Pressure
Transmitter is not installed correctly.
The Pressure Transmitter is for indoor use only! At an outdoor
installation, the Pressure Transmitter must be protected from solar
radiation and rain.
7.1 Installation Requirements
To install the Pressure Transmitter a ball valve or a nozzle is needed.
The inner thread must be G 1/4”.
7.2 Installation Procedure
The following steps explain the procedure of an appropriate installation.
Installation of the Pressure Transmitter
Screw the Pressure Transmitter tightly to the nozzle.
Removal of the Pressure Transmitter
Loose unscrew the Pressure Transmitter.
10 S011