Testing a Detector
MULTI-STIMULUS DETECTOR TESTER
testifire®
www. .comtestifire
Smoke
Heat
CO
Menu Status
l
l
To carry out a simple, single stimuli
test, use the UP and DOWN keys
on the keypad to highlight the stimul
required ).
Raise the Testifire head unit up to the
detector to be tested, and place it
centrally over the detector.
‘’ ‘ ’
us
e.g. ‘Smoke’ (23
23
1. How to Perform a Test
N:ote
22
It is very important that the detector under
test is in the correct position ). Ideally, the
bellows should seal against the ceiling surface.
(
24
In this example, ‘Smoke’ and ‘Heat’ are selected as a
simultaneous test ( ).
Move the cursor to ‘Smoke’ and press the ‘ENTER’ key
‘ ’ will be displayed alongside ‘Smoke’.
Move the cursor to ‘Heat’ and press the ‘ENTER’ key
‘ ’ will be displayed alongside ‘Heat’. Press ‘ENTER’
once more to display ‘ ’ alongside ‘Heat’.
Repeat the above as required for additional stimuli.
To delete a test setup, use the ‘ESCAPE’ key .
1
2
1
l
l
l
l
2. Simultaneous Testing (selected tests at the same time)
In this example, ‘Smoke’, ‘Heat’ and ‘CO’ are selected as a
sequential test ( ).
Move the cursor to ‘Smoke’ and press the ‘ENTER’ key
‘ ’ will be displayed alongside ‘Smoke’.
Move the cursor to ‘Heat’ and press the ‘ENTER’ key
‘ ’ will be displayed alongside ‘Heat’.
Move the cursor to ‘CO’ and press the ‘ENTER’ key
‘ ’ will be displayed alongside ‘CO’.
To delete a test setup, use the ‘ESCAPE’ key .
25
1
2
3
l
l
l
l
In this example, ‘Smoke’ and ‘Heat’ are combined as a
simultaneous test followed by ‘CO’ ( ).
‘Heat’ and ‘Smoke’ can be combined as the first operation,
followed by a ‘CO’ test. you will need to lower the
head unit between each test.
To delete a test setup, use the ‘ESCAPE’ key .
26
Note:
l
l
3. Sequential Testing (selected tests, one after another)
4. Combined Simultaneous and Sequential Testing
Smoke 1
Heat 1
CO
Menu Status
Smoke 1
Heat 2
CO 3
Menu Status
Smoke 1
Heat 1
CO 2
Menu Status
1. Programme the tests: Smoke 1
Heat 1
2. Raise Testifire
over the detector:
‘Smoke’ and ‘Heat’
are tested at the
same time as test ‘ ’.1
3. Lower Testifire
from the detector:
The test is completed
and ready to test another
detector in the same way.
1. Programme the tests: Smoke 1
Heat 2
CO 3
The test is completed and ready to
test another detector in the same way.
Lower Testifire:5.
2. Raise Testifire over the detector:
‘Smoke’ is tested as test ‘ ’.1
3. Lower for 2-10 seconds, then
raise Testifire again:
‘Heat’ is tested as test ‘ ’.2
4. Lower for 2-10 seconds, then
raise Testifire again:
‘CO’ is tested as test ‘ ’.3
Using these methods, you can
programme Testifire to combine tests
and continue in sequence.
‘Clear’ (clearing) can also be
selected in any of the above operations.
Note:
24
25
26
lAs the detector enters Testifire, the infrared beam
is interrupted by the body of the detector
chosen test indicated by the LED
flashing faster.
and the
will begin, ‘Status’
In this example ‘Smoke’ and ‘Heat’ are
tested together as test ‘ ’ and then
‘CO’ is tested as test ‘ ’.
1
2