TRIATEK UVM-1000 Manuale utente

1
UVM-1000
Universal Valve Module
LIT-12013155
September 2020
Installation Guide
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC
Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a
commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in
accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a
residential area may cause harmful interference, in which case users will be required to correct the interference at their own expense.
Canada
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
IMPORTANT: The UVM-1000 Universal Valve Module must be wired to 24 VAC only. Wiring the unit to 110 VAC will cause serious
damange and void the warranty.
Risk of Property Damage.
Ensure that the power source conforms to the requirements of the equipment. Failure to use a correct power source may result in
permanent damage to the equipment.
Risque de dégâts matériels.
S’assurer que la source d’alimentation électrique est conforme aux spécications de l’équipement. L’utilisation d’une source
d’alimentation électrique inappropriée risque d’endommager irrémédiablement l’équipement.
North American Emissions Compliance
United States

UVM-1000
LIT-12013155
2
Setup Overview............................................................................................................................................................................ 3
Introduction / Overview of Operation ........................................................................................................................................ 4
Overview of Operation ................................................................................................................................................................ 6
Installation and Setup ............................................................................................................................................................... 11
UVM to FMS165X-S-0-1 Start Up .............................................................................................................................................. 17
Wiring ......................................................................................................................................................................................... 17
UVM Conguration Tool............................................................................................................................................................ 19
Before you begin .................................................................................................................................................................. 19
Overview of Lin Module Interface......................................................................................................................................... 19
Installation.................................................................................................................................................................................. 20
Misc Tab ..................................................................................................................................................................................... 22
User Settings Tab ...................................................................................................................................................................... 23
User Cong Settings ............................................................................................................................................................ 24
User Settings Tab and CFM Table Tab..................................................................................................................................... 27
CFM Table Tab ........................................................................................................................................................................... 28
CFM Table Tab and Dynamic Values Tab................................................................................................................................. 29
Dynamic Values Tab .................................................................................................................................................................. 30
Dynamic Values Tab and Factory Cong Settings Tab.......................................................................................................... 32
Factory Settings Tab ................................................................................................................................................................. 33
Factory Settings Tab and Calibration Import Tab................................................................................................................... 34
Table of contents

UVM-1000
LIT-12013155
3
Setup Overview
UVM Box and Venturi valve
1. Valve is calibrated at Triatek®.
2. The valve label indicates the calibration values at set positions.
3. Set controllers for a 0 V - 10 VDC, or 10 V - 0 VDC depending on the valve actuation type, Normal or Reverse acting.
4. Set the output airow scale based on your valve size.
5. Set your feedback signal voltage the same as the cfm scale.

UVM-1000
LIT-12013155
4
Introduction
Triatek’s Universal Valve Module (UVM) is designed to allow for
interoperability between Triatek Venturi valves and third party
controllers.
Each Triatek valve is individually calibrated and has its own
unique position to cubic feet per minute (cfm) curve. The UVM
enables you to create a linearization curve in each controller for
each associated valve. It also allows you to span, scale, and
linearize the feedback sensor to obtain useful information from it.
Overview of Operation
A diagram of the basic functionality of the UVM is shown in
Figure 1.
The UVM takes a 0 -10 V signal from the third party equipment,
and depending on the scaling setting, interprets this as a 0 –
xxxx cfm request signal. The UVM is pre-programmed with the
associated valve’s linearization curve, and will move the valve’s
actuator to the correct position for the requested cfm.
Each valve is tted with an electronic position sensor on the lever
arm at the point of entry into the valve body (see Figure 1). The
electronic position sensor is used to provide actual valve position
information to the controllers. This signal is non-linear, and has a
random 0 and 100% position voltages.
It converts the sensor signal to a position on the valve and then
translates that to a cfm value. The cfm value is in turn output
from the UVM as a 0 – 10 V signal at the same scaling as the
cfm request signal.
The 0 -10 V signal is processed by the valve’s calibration
settings as set by the factory. The user has the ability to access
and adjust this curve if so desired. The subsequent signal is
then converted to an equivalent cfm request value. This value
is dependent on settings provided by the factory as applicable
for the associated valve size. The user can modify this signal if
desired.
The factory default settings relative to valve size are:
8 in. valve 10 V = 800 cfm
10 in. valve 10 V = 1100 cfm
12 in. valve 10 V = 1600 cfm
14 in. valve 10 V = 2300 cfm
The equivalent cfm request value is applied to the calibration
curve as entered by the factory for the associated valve and a
corresponding valve position value is generated.
This position value is applied to the actuator output voltage
calibration section and output to the actuator. The consequent
result is that the actuator will move to the required position so
that the valve passes the requested cfm.
As the valve moves to position, the position feedback sensor
moves as well. The signal from this sensor is processed by a
sensor voltage to position calibration section. The output of this
section provides an accurate position value. The position value is
applied to the position to cfm mapping table and a corresponding
cfm value is output.
This cfm value is then passed through cfm to voltage scaling
factor and converted to a voltage value. This value is then
passed through the factory set output calibration section and
made available to the voltage output for use by the third party
equipment as the actual valve cfm.
In certain circumstances the feedback signal may not match the
requested cfm signal. If 0 cfm is requested (0V input), and the
valve is a partially closed valve, the valve has a minimum cfm
that it can attain. This value is not 0 and for a 12 in valve would
be around 90cfm. In this case the feedback signal would be the
equivalent of 90 cfm or 0.56V for a 10V = 1600 setting.
If a UVM for an 8 in. valve is set with an arbitrary scaling of 10V
= 1100 cfm (or 110 cfm / volt), and a request signal of 9 V (or 990
cfm) is input to the unit, then the actuator will end up driving to
100%, as the maximum the valve can do is 700 cfm. The voltage
feedback output signal will only be around 6.4 V as the actual
valve cfm would be around 700.
Introduction / Overview of Operation

UVM-1000
LIT-12013155
5
Triatek reserves the right to change product specications without notice.
Figure 1. Basic Functionality of the UVM
Electronic Position Sensor
Actuator
UVM Box
Venturi Valve

UVM-1000
LIT-12013155
6
Overview of Operation
Figure 2. UVM Use with DP Switch
Digital Input DP Switch
The UVM has the ability to accept a digital input DP switch. The
pneumatics of the DP switch are connected across the valve, and
the factory supplied switch is set to trip at 0.6 in. W.G.
Any pressure across the valve below this is to be interpreted as
the valve cfm is inaccurate or non-existent. The DP switch signal,
when enabled in the UVM, is used to provide a 0 cfm feedback
signal should the pressure across the valve drop below the 0.6
in. W.G. threshold.
The DP switch functionality can also be implemented by using
a pressure sensor with a 0-5 V output. The UVM can accept the
0-5 V signal and, via user gain and oset settings, convert it to an
internal pressure value.
Typically a 0-4 or 5 in. W.G. sensor would be used. When
enabled in the UVM, this value can be compared to a minimum
pressure value (typically 0.6 in. W.G.) as a threshold below
which, as like the DP switch, the cfm feedback signal goes to 0.

UVM-1000
LIT-12013155
7
Figure 3. UVM with Pressure Sensor

UVM-1000
LIT-12013155
8
Figure 4. UVM use as a VAV Interface
The UVM can also be made to operate with a variable air volume
(VAV) box instead of a Venturi valve. In this case, instead of
providing the UVM with a cfm request signal, the input will
be interpreted as an actuator position signal where 0-10 V
represents a 0 -100% position signal.
This signal only provides positioning information for the VAV
box. The feedback sensor signal is replaced by the VAV box
ow probe pressure signal. This voltage signal is scaled and
converted to an internal pressure value.
The pressure value is then square-rooted and multiplied by a K
factor to obtain an internal velocity value. The velocity value is
multiplied by a duct area value to obtain an internal cfm value.
This cfm value is then scaled to the appropriate voltage, passed
to the Vo feedback voltage signal for use by the third party
controller. The scaling, K factor, and area can be set by the user
with the UVM Conguration Tool.

UVM-1000
LIT-12013155
9
Figure 5. UVM Module DIP Switch Functions
Other than through the UVM Conguration Tool, the user does
not have access to any settings or operating modes of the UVM.
The exception is that the input and output signal modes and the
normal/reverse operation can be set via the DIP switches if that
functionality is enabled in the UVM.
The inputs and outputs can be set to be interpreted as a
Percentage (0 – 10 V = 0 – 100%) control or feedback signal, or
as a cfm ( 0 – 10 V = 0 – xxxx cfm ) control or feedback signal.
DIP switches 6 and 7 are used for this function. DIP switch 5 is
Normal Reverse Selection.
The UVM can communicate with the UVM Conguration Tool. To
this end, the UVM can reside at one of 16 hardware addresses.
These addresses are set via DIP switches 1, 2, 3, and 4. Via
the UVM Conguration Tool, the UVM is able to have up to an
additional 16 software addresses set for communications use.

UVM-1000
LIT-12013155
10
Due to continuous improvement, Triatek reserves the right to change product specications without notice.Triatek reserves the right to change product specications without notice.
Figure 6. UVM Controller Utilizing UVMNet to sum cfm values
The later version (S series revisions) is capable of being
congured to sum cfms over the RS485 network and output
the summed equivalent on the Vo of the unit designated to be
primary. The primary unit is the unit designated with hardware
address 15. Secondary (polled) units are units with address 16
on-wards. The primary unit species how many units to poll from
address 16 on-wards.
Indice
Manuali Unità di controllo popolari di altre marche

Festo
Festo Compact Performance CP-FB6-E Manuale elenco delle parti

Elo TouchSystems
Elo TouchSystems DMS-SA19P-EXTME Manuale utente

JS Automation
JS Automation MPC3034A Manuale utente

JAUDT
JAUDT SW GII 6406 Series Guida rapida

Spektrum
Spektrum Air Module System Manuale utente

BOC Edwards
BOC Edwards Q Series Manuale utente











