Trikdis Ethernet E16 Manuale utente

www.trikdis.lt UAB Trikdis Draugystės str. 17, LT-51229 Kaunas, Lithuania +370 37 408 040 info@trikdis.lt
“Ethernet” communicator E16
Installation manual
February, 2020

www.trikdis.com 2 February, 2020
“Ethernet”
communicator
E
16
Contents
SAFETY REQUIREMENTS........................................................................................................................................................ 3
1 DESCRIPTION ............................................................................................................................................................. 4
1.1 List of compatible control panels ............................................................................................................................................ 5
1.2 Specifications .......................................................................................................................................................................... 5
1.3 Communicator elements ......................................................................................................................................................... 6
1.4 Purpose of terminals ............................................................................................................................................................... 6
1.5 LED indication of operation ..................................................................................................................................................... 6
1.6 Structural schematic with E16 usage ...................................................................................................................................... 7
2 QUICK CONFIGURATION WITH TRIKDISCONFIG SOFTWARE .................................................................................................... 7
2.1 Settings for connection with Protegus app ............................................................................................................................. 8
2.2 Settings for connection with Central Monitoring Station ........................................................................................................ 9
3 INSTALLATION AND WIRING ......................................................................................................................................... 10
3.1 Schematics for wiring the communicator to a security control panel ................................................................................... 10
3.2 Schematic for connecting to panel keyswitch zone ............................................................................................................... 11
3.3 Schematics for input connection ........................................................................................................................................... 12
3.4 Connect LAN cable ................................................................................................................................................................ 13
3.5 Schematics for wiring a relay ................................................................................................................................................ 13
3.6 Schematics for connecting iO series expansion modules ...................................................................................................... 13
3.7 Turn on the communicator ................................................................................................................................................... 13
4 PROGRAMMING THE CONTROL PANEL ............................................................................................................................ 14
5 REMOTE CONTROL .................................................................................................................................................... 16
5.1 Adding the security system to Protegus app ......................................................................................................................... 16
5.2 Additional settings to arm/disarm the system using the control panel’s keyswitch zone ..................................................... 16
5.3 Arming/disarming the alarm system with Protegus ............................................................................................................. 18
6 TRIKDISCONFIG WINDOW DESCRIPTION .......................................................................................................................... 19
6.1 TrikdisConfig status bar description ...................................................................................................................................... 19
6.2 “System settings” window .................................................................................................................................................... 20
6.3 “CMS reporting” window ...................................................................................................................................................... 21
6.4 “User reporting” window ...................................................................................................................................................... 23
6.5 “Ethernet settings” window .................................................................................................................................................. 23
6.6 “IN/OUT” windows................................................................................................................................................................ 24
6.7 “RS485 modules” window ..................................................................................................................................................... 24
6.8 “Event summary” window .................................................................................................................................................... 26
6.9 Restoring factory settings ..................................................................................................................................................... 27
7 REMOTE CONFIGURATION ........................................................................................................................................... 27
8 TEST COMMUNICATOR PERFORMANCE ........................................................................................................................... 27
9 FIRMWARE UPDATE ................................................................................................................................................... 28
10 ANNEX ................................................................................................................................................................... 29

www.trikdis.com 3 February, 2020
“Ethernet”
communicator
E
16
Safety requirements
The communicator should be installed and maintained by qualified personnel.
Prior to installation, please read this manual carefully in order to avoid mistakes that can lead to malfunction or even damage
to the equipment.
Disconnect the power supply before making any electrical connections.
Changes, modifications or repairs not authorized by the manufacturer shall void your rights under the warranty.
Please act according to your local rules and do not dispose of your unusable alarm system or its components with
other household waste.

www.trikdis.com 4 February, 2020
“Ethernet”
communicator
E
16
1 Description
“Ethernet” communicator E16 directly connects to supported DSC, Paradox, UTC Interlogix (CADDX), Innerrange, Texecom,
Honeywell, Crow and Pyronix alarm panels.
Communicator transmits full event information to the Central Monitoring Station.
Communicator also works with Protegus application. With Protegus users can control their alarm system remotely and get
notifications about security system events. Protegus app is compatible with all security alarm panels from various manufacturers
that are supported by the E16 communicator. Communicator can transmit event notifications to the Central Monitoring Station
and work with Protegus simultaneously.
For panels from other manufacturers use the E16T communicator.
Features
Sends events to monitoring station receiver:
Sends events to TRIKDIS software or hardware receivers that work with
any monitoring software.
Can send event messages to SIA DC-09 receivers.
Can send event messages to SUR-GARD receivers. The annex has a
table for converting Contact ID codes to SIA codes.
Connection supervision by polling to IP receiver every 30 seconds (or
by user defined period).
Backup channel, that will be used if connection with the primary
channel is lost.
With parallel communication channels events can be sent to two
receivers at same time.
When Protegus service is enabled, events are first delivered to CMS,
and only then are sent to app users.
Works with Protegus app:
“Push” and special sound notifications informing about events.
Remote system Arm/Disarm.
Remote control of connected devices (lights, gates, ventilation
systems, heating, sprinklers, etc.).
Remote temperature monitoring (with iO or iO-WL expanders).
Different user rights for administrator and installer.
Notifies users:
Users can be notified about events with Protegus app.
Controllable outputs and inputs:
3 double I/O terminals that can be set either as input (IN) or controllable output (OUT) terminals.
Outputs controlled by the Protegus app.
Add additional inputs and controllable outputs with wired and wireless iO expanders.
Quick setup:
Settings can be saved to file and quickly written to other communicators.
Two access levels for configuring the device for CMS administrator and for installer.
Remote configuration and firmware updates.

www.trikdis.com 5 February, 2020
“Ethernet”
communicator
E
16
1.1 List of compatible control panels
Underlined - Control panels directly controlled by E16.
*Connect control panels from other manufacturers to the E16T communicator.
1.2 Specifications
Parameter Description
Dual purpose terminals
[IN/OUT]
3, can be set as either NC; NO; NC/EOL; NO/EOL; NC/DEOL; NO/DEOL (2,2 kΩ) type inputs
or open collector (OC) type outputs with current up to 0,15 A, 30 VDC max.
Expandable with iO series expanders.
Power supply voltage 10-18 V DC
Current consumption 100 mA (on standby)
Up to 250 mA (while sending data)
Ethernet connection IEEE802.3, 10 Base-T, RJ45 socket
Transmission protocols TRK, DC-09_2007, DC-09_2012, TL150
Memory Up to 60 messages
Changing settings With TrikdisConfig computer program remotely or locally via USB Mini-B port
Operating environment Temperature from -10 °C to 50 °C, relative humidity - up to 80% at +20 °C
Communicator dimensions 88 x 65 x 26 mm
Weight 80 g
Manufacturer Model
DSC® PC585, PC1404, PC1565, PC1616, PC1832, PC1864, PC5020
PARADOX® SPECTRA SP4000, SP5500, SP6000, SP7000, SP65
MAGELLAN MG5000, MG5050, MG5050E
DIGIPLEX EVO48, EVO192, EVOHD, NE96, EVO96
SPECTRA 1727, 1728, 1738
ESPRIT E55, 728ULT, 738ULT
UTC Interlogix® NetworX (Caddx) NX-4v2, NX-6v2, NX-8v2, NX-8E
Texecom® Premier 24, 48, 88, 168
Premier Elite 12, 24, 48, 64, 88, 168
Pyronix® MATRIX 424, MATRIX 832, MATRIX 832+, MATRIX 6, MATRIX 816
Innerrange® Inception
Honeywell® Ademco Vista-5, Ademco Vista-20, Ademco Vista-48
Crow® Runner 4/8, Runner 8/16

www.trikdis.com 6 February, 2020
“Ethernet”
communicator
E
16
1.3 Communicator elements
1. Light indicators.
2. Frontal case opening slot.
3. Terminal for external
connections.
4. USB Mini-B port for
communicator programming.
5. Ethernet connection RJ45
socket.
1.4 Purpose of terminals
Terminal Description
+DC +10 V/+18 V power supply
-DC +10 V/+18 V power supply
CLK Serial bus terminals for direct connection to control panel
DATA
I/O 1 1st input/output terminal
I/O 2 2nd input/output terminal
I/O 3 3rd input/output terminal
COM Common (negative) terminal
A RS485 RS485 bus A contact
B RS485 RS485 bus B contact
1.5 LED indication of operation
Indicator Light status Description
NETWORK Off No connection to a computer network
Green solid Communicator is connected to a computer network
DATA Off No unsent events
Green solid Unsent events are stored in buffer
Green blinking (Configuration mode) Data is being transferred to/from communicator
POWER Off Power supply is off or disconnected
Green solid Power supply is on with sufficient voltage
Yellow solid Power supply voltage is insufficient (≤11.5V)
Green solid and
yellow blinking
(Configuration mode) Communicator is ready for configuration

www.trikdis.com 7 February, 2020
“Ethernet”
communicator
E
16
Indicator Light status Description
Yellow solid (Configuration mode) No connection with computer
TROUBLE OFF No operation problems
1 red blink Connection error at the "physical" level (PHY Link status error)
2 red blinks DHCP error
3 red blinks DNS error
6 red blinks No connection with the receiver
7 red blinks Lost connection with control panel
Red blinking (Configuration mode) Memory fault
Red solid (Configuration mode) Firmware is corrupted
1.6 Structural schematic with E16 usage
Note: Before you begin, make sure that you have the necessary:
1. USB cable (Mini-B type) for configuration.
2. At least 4-wire cable for connecting communicator to control panel.
3. CRP2 cable for connecting to Paradox panel`s serial port.
4. Flat-head 2,5 mm screwdriver.
5. Particular security control panel`s installation manual.
Order the necessary components separately from your local distributor.
2 Quick configuration with TrikdisConfig software
1. Download TrikdisConfig configuration software from www.trikdis.com (type “TrikdisConfig” in the search field) and
install it.
2. Open the casing of the E16 with a flat-head screwdriver as shown below:

www.trikdis.com 8 February, 2020
“Ethernet”
communicator
E
16
3. Using a USB Mini-B cable connect the E16 to the computer.
4. Run TrikdisConfig. The software will automatically recognize the connected communicator and will open a window for
configuration.
5. Click Read [F4] to read the communicator’s settings. If requested, enter the Administrator or Installer 6-digit code in the
pop-up window.
Below we describe what settings need to be set for the communicator to begin sending events to the CMS (central monitoring
station) and to allow the security system to be controlled with the Protegus app.
2.1 Settings for connection with Protegus app
In “System settings” window:
1) Select Security panel model that will be connected to the communicator.
2) Select Remote Arm/Disarm if you want users to be able to control the panel in Protegus app with their keypad code.
This setting is only shown for directly controlled panels.
3) For the direct control of Paradox and Texecom panels enter PC download password. It must match the password that is
entered in the control panel.
Note: For the direct panel control to work, you will need to change the panel settings. How to do this is described in
chapter 4 “Programming the control panel”. In this section you will find information on how to change the PC
download/UDL password.
In “User reporting” window, “PROTEGUS Cloud” tab:
4) Tick the checkbox Enable connection to the Protegus Cloud.

www.trikdis.com 9 February, 2020
“Ethernet”
communicator
E
16
5) Change the Protegus Cloud access Code for logging in to Protegus if you want users to be asked to enter it when adding
the system to Protegus app (default password – 123456).
After finishing configuration, click the button Write [F5] and disconnect the USB cable.
Note: For more information about other E16 settings in TrikdisConfig, see chapter 6 “TrikdisConfig window
description”.
2.2 Settings for connection with Central Monitoring Station
In “System settings” window:
1) Enter Object ID (account) number provided by the Central Monitoring Station (4 characters, 0-9, A-F. Do not use FFFE,
FFFF Object ID.).
2) Select Security panel model that will be connected to the communicator.
In “CMS reporting” window settings for “Primary channel”:
3) Communication type - select the IP connection method.
4) Protocol - select the protocol type for event messages: TRK (to TRIKDIS receivers); DC-09_2007 or DC-09_2012 (to
universal receivers); TL150 (to SUR-GARD receivers).
5) TRK encryption key - enter the encryption key that is set in the receiver.
6) Domain or IP - enter the receiver’s Domain or IP address.
7) Port - enter receiver’s network port number.

www.trikdis.com 10 February, 2020
“Ethernet”
communicator
E
16
8) TCP or UDP - choose event transmission protocol (TCP or UDP) in which events should be sent.
Note: If you selected the DC-09 protocol, additionally enter object, line and receiver numbers in the Settings tab of
the CMS reporting window.
9) (Recommended) Configure Primary channel Backup settings.
10) (Recommended) Configure Parallel Channel and its Parallel Channel Backup settings.
After finishing configuration, click Write [F5] and disconnect the USB cable.
Note: For more information about other E16 settings in TrikdisConfig, see chapter 6 “TrikdisConfig window
description”.
3 Installation and wiring
3.1 Schematics for wiring the communicator to a security control panel
Following one of the schematics provided below, connect communicator to the control panel.
Indice
Altri manuali Trikdis Telefono cellulare

Trikdis
Trikdis G16T Manuale utente

Trikdis
Trikdis G16T Manuale utente

Trikdis
Trikdis E16T Manuale utente

Trikdis
Trikdis G10 Manuale utente

Trikdis
Trikdis G10D Manuale utente

Trikdis
Trikdis G16T 3 Series Manuale utente

Trikdis
Trikdis G10 Manuale utente

Trikdis
Trikdis G17F Manuale utente

Trikdis
Trikdis G16T Manuale utente

Trikdis
Trikdis E10T Manuale utente

Trikdis
Trikdis G16 Manuale utente

Trikdis
Trikdis GET Manuale utente

Trikdis
Trikdis G10T Manuale utente

Trikdis
Trikdis FireCom Manuale utente

Trikdis
Trikdis E14 Manuale utente

Trikdis
Trikdis G09 Manuale utente

Trikdis
Trikdis G16 Manuale utente

Trikdis
Trikdis G17F Manuale utente

Trikdis
Trikdis E10Tv2 Manuale utente