Trycom Technology TRP-C28 Manuale utente

1
TRP-C28
4-Channel Isolated Digital Input and 4-Channel Relay Output
RS485 Remote Module
User’s manual
Printed Aug. 2005 Rev 1.0
Trycom Technology Co.,Ltd
1F, No.2-11,Sihu street ,Yingge Township, Taipei, Taiwan ROC
Tel: 886-2-86781191 , Fax: 886-2-86781172
Web: www.trycom.com.tw
Copyright
Copyright Notice: The information in this manual is subject to change without prior notice in order to improve reliability,
design and function and dosed not represent a commitment on the part of the manufacturer. No part of this manual may
be reproduced, copied, or transmitted in any form without the prior written permission of manufacturer.
Acknowledgment Products mentioned in this manual are mentioned for identification purpose only. Products manes
appearing in this manual may or may not be registered trademarks or copyright of their respective companies

2
Introductions
Features
TRP-C28 provides 4 optical isolated digital input channels that allow you to input the logic signal from 0
to 30V DC and 4 power relays output . All channel features screw terminals for the convenience
connection of field signals as well as LED to indicate channel status. Each output power relay equips with
high surge current suppressors varistor to entirely protect your module and devices without damage when
irregularly high power voltage input. TRP-C28 can be configured and conduct self-test by outside dip-
switch without complicated setting and connection. Build-in a full set of command, watch-dog, auto reset
function the module can be bi-directionally remote controlled by RS485 protocol.
¾Wide range power input from +18V to +30V DC.
¾All communication's command are perform in ASCII.
¾Programmable in virtually any high-level language.
¾4-CH isolated digital input (with common power) and 4- CH power relay output.
¾Baud Rate can be set from 1200 to 115.2K bps.
¾High surge current suppressors varistor for relay.
¾LED display to indicate input and relay output channels and PWR/watchdog/RS485 status.
¾Dual Watchdog for hardware reset circuit and host operating status .
¾External switch for hardware self-test and module’s configuration.
¾Digital Input Isolation with power source (2500 Vrms).
¾Support screw terminal and standard external DC power adaptor.
Specification
¾Output Channel: 4 Channel Power Relay.
¾Relay type : 2 Form A (RL1,RL2) , 2 Form C (RL3,RL4).
¾Contact rating : 5A/30V DC , 5A/120V AC , 4A/250V AC.
¾Relay surge strength : 4000V.
¾Relay Operate time : 3mS.
¾Relay Min Life : 2*10(7) ops.
¾Input channel : 4 isolated input channels and counter.
¾Input isolation voltage : 2500Vrms.
¾Digital input level 0 : +1V Max.
¾Digital input level 1 : +4V ~ +30V.
¾Input impedance : 3KΩ.
¾Distance : RS485 up to 4000ft. (1250meters) .
¾Baud-Rate: 1200, 2400, 4800, 9600, 19.2K, 38.4K, 57.6K, 115.2K (bps).
¾Communication protocol : RS485 differential 2 half-duplex wires.
¾Format : Asynchronous data with any combination of bits, parity, stop.
¾RS-485 and input/output connector : Industrial plug-in screw terminal.
¾Power input : DC +18~30V.
¾Power consumption :2.7W (max).
¾Operating Temperature:-20 ℃to 65℃.
¾Storage temperature : -20 ℃to 65℃
¾Weight: 375g
¾Humidity : 5-95% non-condensing.

3
Warning
Warning: Don
: Don’
’t connect external DC
t connect external DC-
-Jack and screw terminal DC input simultaneously.
Jack and screw terminal DC input simultaneously.
Communication Wiring
Pin Definitions
Relay 4 –CommonRL4-COMDigital Input CH 3DI3
Relay 4-Normal CloseRL4-NCDigital Input CH 2DI2
Relay 4-Normal OpenRL4-NODigital Input CH 1DI1
Relay 3 -CommonRL3-COMDigital Input CH 0DI0
Relay 3-Normal CloseRL3-NCExternal Voltage Input For Digital InputIN-COM
Relay 2 -CommonRL2-COMRS485 +DATA+
Relay 2-Normal OpenRL2-NORS485 -DATA-
Relay 1 –CommonRL1-COMInput Voltage DC +18-30VDC 18-30V
Relay 1-Normal OpenRL1-NOInput Voltage GroundGND
Relay 3-Normal OpenRL3-NONoneNC

4
TRP-C28 Panel Layout
Relay Output Connector
Digital Input LED Indicator
Relay Output LED Indicator
Power or Watchdog/ RS485 flow LED Indicator
Digital Input Connector
External Voltage Input
RS485 Communication
DC Voltage Input From +18V~30V
System Switch Configuration
and hardware test.
External DC-Jack Input
DC-jack connector (0.5*2.1 mm plug).
Use in RS485 interface along with bellowing TRP converter family
TRP-C06 :RS232 to RS422/485 optical isolated converter.
TRP-C07 :RS422/485 optical isolated repeater.
TRP-C06E :RS232 to RS422/485 converter.
TRP-C08 :USB to RS232/422/485 optical isolated converter.
TRP-C36 :TCP/IP to RS232/422/485 optical isolated converter.
TRP-C39 :Multi-mode fiber to RS232/422/485 optical isolated converter.

5
Block Diagram
Wire Connection For Digital Input
Wire Connection For Relay Output

6
1.Calculate all characters of the command string to get the ASCII sum, except the character return.
2.Mask the sum of string with 0FFH.
Example :
Send the command is “$06M”.
Sum of string is “$”+”0”+”6”+”M”=“24H”+”30H”+” 4D“=“A1H”……The checksum and [CHK]=“A1”.
Response string with checksum is :” A1 “.
How To Calculate The Checksum
Default setting:ID Address :01 Baud Rate:9600 DIO Mode Type :40 Checksum:Disable
Command Format :”Leading Code”+”ID Address”+”Command”+”CHK”+(cr) .
Response Format :”Leading Code”+”ID Address”+”Data”+”CHK”+(cr) .
Command Description
Self- test Switch.2
1.Power off the module , then adjust switch.2 to ON.
2.Power on the module , The module start self-testing, PWR
and digital input LED start lighting one by one, power relay
activating.
3.Power off the module to stop self-testing.
1.Power off the module, then adjust Switch.1 to ON.
2.Power on the module ,The module will be reset to
ID=00, baud rate:9600, checksum: Disable!.
3. Send command to configure TRP-C28.
4.Power off the module, then adjust the Switch to OFF.
System Configuration Switch.1

7
See 11.2Clear digital input latched data$IDC(CHK)(cr)
See 11.1Read digital input latched value$IDLS(CHK)(cr)
See 9.2Clear digital input N channel counter’s value#IDCN (CHK)(cr)
See 9.1Read digital input N channel counter value#IDN (CHK)(cr)
See 10.1Clear all digital input counter’s value#IDCW(CHK)(cr)
See 10.2Save all digital input counter’s value to EEPROM#IDCS(CHK(cr)
See 19.1Save existing digital input status#**
See 19.2Read synchronized data$ID4
See 17.1Read watchdog timeout value~IDWR (CHK)(cr)
See 17.2System stand by (Host ok!)~**(CHK)(cr)
See 18.1Read power on/safe value~ID4V (CHK)(cr)
See 18.2Save existing digital output status to power on
mode or safe mode
~ID5V (CHK)(cr)
See 16.2Disable watchdog~IDWD (CHK)(cr)
See 16.1Enable watchdog and set the timeout value~IDWENN (CHK)(cr)
See 15.2Set the module’s LED operating mode~IDLEDA(CHK)(cr)
See 15.1Change the module’s name~IDONN (CHK)(cr)
See 14.2Read reset status$ID5 (CHK)(cr)
See 14.1Read the module’s firmware version$IDF (CHK)(cr)
See 13.2Read the module’s name$IDM (CHK)(cr)
See 13.1Reset the module$IDRS (CHK)(cr)
See 12.2Read the module’s configuration$ID2 (CHK)(cr)
See 12.1Read digital input/output status$ID6 (CHK)(cr)
See 8.1Digital Output Data#IDPPDD (CHK)(cr)
See 7.1~7.3
Page Index
Set the module’s configuration%IDNNPPBBDD(CHK)(cr)
Function DescriptionCommand List
Command List
Safe mode: Digital output when Watchdog enable.
Power on mode: Digital output when power on.
Watchdog: The watchdog is designed to monitor the module's output status to prevent the module
from communication problem or system halt due to unexpected situation
*User can save the module output value by using the command "ID5V" if the power is fails.

8
7.1 Set the module’s configuration *Must adjust the system configuration Switch.1 to ON ( See Page 6)
?ID (CHK)(cr)
!ID(CHK) (cr)
(cr)
CHK
DD
BB
PP
NN
ID
%
%IDNNPPBBDD(CHK)(cr)
Command Invalid
Command validResponse
Carriage return
Checksum
Data format (See 7.3)
Set new baud rate (See 7.2)
The Digital I/O module type define to 40
New address of setting from 00-FF(HEX)
Address of setting module 00-FF(HEX)
First leading code
Syntax
Description
Command
1152005760038400192009600480024001200Baud rate
0A09080706050403Code number
7.2 Baud rate (BB) setting
7.3 Data (DD) format setting
EX: Send command:”%0001400600”…..If you turn on the system setting switch , the ID will be reset to “00”,
New ID is “01”,D I/O type is “40” ,Bard-Rate:9600 ,Checksum setting disable is “00”, Response:”!01”.
EX: Send command:%0003400540….New ID=“03”,Bard-Rate=“4800”,Checksum=“Enable”,Response:”!03”.
*We offer the utility to guide you to configure the module ,the utility is with on-line RS485 modules scanning and
searching function. You can find the utility in the CD which bundled in TRP-C24 standard package. (See the
page 21).
000000Checksum
0:Disable
1:Enable
Input counter
0:Rising
1:Falling
Function
01234567Bit

9
Command valid>(CHK)(cr)
?ID (CHK)(cr)
!ID(CHK) (cr)
(cr)
CHK
FD
PP
ID
#
#IDPPFD(CHK)(cr)
Command Invalid
Parameter invalid (*Command data error !)
Response
Carriage return
Checksum
F=0, D:Sent the data from 0-F output for relay channel
Output(relay) command parameter :00,0A Multi-Channel
:1L:Single-Channel (L=0-3)
Address of setting module 00-FF(HEX)
First leading code
Syntax
description
Command
8.1 Digital output data
*Multi-Channel mode (Output control for one BYTE)
EX: Send command :”#010A0F”…..Data=”0F”:DO0-DO3=“1111”, (RL1/RL2/RL3/RL4= ON).
Response:”>”……. Command valid.
EX: Send command:”#010008”…..Data=”08”:DO0-DO3=“0001”,(RL1/RL2/RL3:OFF/RL4:ON).
Response:”>”……. Command valid.
EX: Send command:”#01000G”…Data=“0G”…….Data error!.
Response:”!01”…….Parameter error!.
*Single-Channel mode( Output control for one BIT)
EX: Send command:”#011001”….. Data=”01”:DO0=“1”.
Response:”>”……. Command valid.
Send command:”#011201”….. Data=“01”:DO2=“1”.
Response:”>”……. Command valid.
Send command:#011300……Data=“00”:DO3=“0”.
Response:”>”……..Command valid.

10
9.2 Clear digital input N channel counter value
Command valid!ID(CHK)(cr)
?ID (CHK)(cr)
(cr)
CHK
N
C
ID
#
#IDCN(CHK)(cr)
Command Invalid
Response
Carriage return
Checksum
N=0-3 *Channel DI0-DI3 digital input
Clear N channel counter value to 0
Address of setting module 00-FF(HEX)
First leading code
Syntax
description
Command
EX: Send command:”#01C2”…..Clear DI2 counter value to 0.
Response:”!01”.
*If counter’s value already been reset to 0 you must use command “#IDCS” to save the new
value in EEPROM again , or the module will load old value if power fail or reset.
EX: Send command:”#012”…..Read the TRP-C28 channel 2 counter value.
Response:”!0100023”…..The digital input have been trigger 23 times.
*Unless you save value to EEPROM by using the command “#IDCS”. The counter’s value will
reset to 0 if power fail or send command “$IDRS”.
Command valid CCCCC from 0 – 65535 (DEC)!IDCCCCC(CHK)(cr)
?ID(CHK) (cr)
(cr)
CHK
N
ID
#
#IDN(CHK)(cr)
Command Invalid
Response
Carriage return
Checksum
Digital input channel from channel 0-3
Address of setting module 00-FF(HEX)
First leading code
Syntax
description
Command
9.1 Read digital input N channel counter value
Altri manuali per TRP-C28
1
Altri manuali Trycom Technology Unità di controllo
Manuali Unità di controllo popolari di altre marche

Festo
Festo Compact Performance CP-FB6-E Manuale elenco delle parti

Elo TouchSystems
Elo TouchSystems DMS-SA19P-EXTME Manuale utente

JS Automation
JS Automation MPC3034A Manuale utente

JAUDT
JAUDT SW GII 6406 Series Guida rapida

Spektrum
Spektrum Air Module System Manuale utente

BOC Edwards
BOC Edwards Q Series Manuale utente