Rotation monitor White cable connected to terminal 9, brown to terminal 10.
(9-10) The magnet is installed with south side (S) towards the sensor.
Max. gap 15 mm.
Manual speed Provides set max rpm when closed, regardless of input signal value.
(A1-A2)
15 CHECKS BEFORE POWERING UP THE CONTROL UNIT
Check that the control unit is connected as per instructions on page 10.
Connection voltage 230-240 V +/-15%, 50/60 Hz.
Check that the motor is wired for 3 x 230 V. If there is an operating switch between
the motor and the control unit, the motor thermal contact should be
connected via the auxiliary terminal in the operating switch.
Check that the input signal is 0-10 V.
Check that the cleaning function and rotation monitor DIP switch are set to ON..
16 PUTTING THE EQUIPMENT INFO OPERATION
Should be done in sequence.
Check that the motor rotates in the right direction in relation to the wheel's direction
of rotation. In the event of a fault, switch two phases to the motor.
Adjustment of Set the “High Speed” DIP switch to the ON position.
maximum rpm Adjust "Max. rpm" so that the wheel rotates at 10-12 rpm
(or as per directions from wheel manufacturer).
After a test run, set the DIP switch to OFF.
Checking Set the “Low Speed” DIP switch to ON.
minimum rpm Check that the wheel starts.
The minimum rpm is preset.
After a test run, set the DIP switch to OFF.
Checking the Switch off the voltage.
cleaning function Make sure the “Cleaning function” DIP switch is set to ON and the input
signal is disconnected. When power is switched on, the wheel will rotate
at minimum rpm for 10 seconds.
Checking the The yellow “Rotation” LED will flash when the magnet passes the
rotation monitor magnetic sensor, regardless of DIP switch position.
Finish by having the control unit drive the wheel at maximum and minimum
rpm and checking that the wheel speed is correct.