Autometers Systems IC 970 Istruzioni per l'installazione

The IC 970 is the latest meter in the IC 900 series
of Information Centres from Autometers Systems
Ltd. With new advances in micro processors and
new added features, the meters are user friendly,
easy to install and simple to programme.
The IC 900 range of Information Centres are electronic meters and great care has been taken to
ensure that they meet the stringent requirements of all the potential users and specifiers of the
product, from the buyer who wants a competitively priced product, the installer who wants
simple fitting with good connection terminals to the end user who wants a quick and easy means
of obtaining information. The IC 900 range of meters meets these varied demands.
The IC 970 meter has been designed to communicate with other systems by means of either pulse
outputs standard on all IC 900 meters or via a separate plug in communication module which is
sold with the meters or can be retro fitted at a later date.
All the IC 900 range of meters have been designed to communicate with Autometers Systems Ltd
Horizon range of data collection units, this enabling complete measurement and data collection
systems to be built up.
A new feature to the IC 970 is the protocol set up information which can be viewed on the display
when a communication module has been installed.
There are two optically isolated volt free relays outputs on the IC 970 and IC 990, one relay for
kWh and the other for kVah. Both these relays are fully programmable to adjust the value of the
pulse (4 settings) and the time of the contact closure. Both meters are factory set to 1 imp/kWh
and 1 imp/kVah.
An optional communication module can be fitted to the IC 970 and IC 990 meters offering a wider
range of information which can be transferred to a BMS system.
IC 970
INSTALLATION
& OPERATING
MANUAL
Autometers Systems Limited,
4B Albany Road,
Chorlton-cum-Hardy,
Manchester.
M21 0AW
Tel: +44 (0) 161 861 9056
Fax: +44 (0) 161 881 3745
www.autometers.co.uk
Email: [email protected].uk
Product development is continuous and Autometers
Systems Ltd reserves the right to make alterations and
manufacture without notice. Products as delivered may
therefore differ from the descriptions and illustrations
in this publication.
Publication No. 23.09.2014
24 1
Overview of the meter
Pulse outputs
Communication module


5
Please follow these instructions precisely.
1. Press Function Key
The display will change to:
You will notice the cursor is flashing at the first digit on the left of the two digits. Press the key
with 1 on it, the cursor will now move to the next digit, now press 2.
2.Press Enter.
The display will change to.
Press Enter. This will RESET The Maximum Demand and take you back to the default register.
To check you have reset the max demand press the “Max demand” key all numbers should have
reset to zero.
4
When you receive the meter there will be at least one value that you must programme into the
meter. This is the current transformer ratio. If you want to monitor the neutral current then the
neutral current transformer ratio will also need to be programmed.
If the meter has been purchased with the communication module you may need to alter the
standard protocol set up. See page 17 & 18 For communication module set up.
First you must locate the two red binary switches on the back of the meter.
See connection details page 3.
You will see two sets of RED binary switches with numbers 1-8 on each of them.
SELECT the binary switch with the word “func” above and switch number 8 to the “on” position.
This puts the meter into programming mode.
Important.
When you have completed programming the meter you must switch number 8 to the “off”
position.
To reset maximum demand - code 12 (view)Programming the meter
Programming the CT Ratio

7
Please follow these instructions precisely.
1. Press Function Key
The display will change to.
You will notice the cursor is flashing at the first digit on the left of the two digits. Press the key
with 2on it, the cursor will now move to the next digit, now press 1.
2. Press Enter
The display will change to.
You will notice the cursor is flashing at the first digit on the left TO ALTER THE OUTPUT VALUE (kWh)
Select the value you require by pressing the keys numbered 1, 2, 3 or 4. When you press one of
these keys the meter will automatically update & return you back to the default display.
The kVah pulse output will automatically be set to the same value.
6
Your Current Transformer Ratio requires to be programmed into this meter. Please follow these
instructions precisely.
1. Press Function Key
The display will change to.
You will notice the cursor is flashing at the first digit on the left of the two digits
Press the key with 1on it, the cursor will now move to the next digit, now press 3.
3. Press Enter.
The display will change to.
Enter the current transformer value by pressing the numbers which are on the front of the key pad.
The cursor will automatically move to the right as you enter the numbers. The cursor will drop
down to the NT primary, repeat the previous steps.
When you have completed inputting the value of the current transformers.
Press Enter.
This will programme the meter and take you back to the default register.
To check you have programmed the correct value press the Information key continuously until
you reach the correct screen.
Please Note.
When setting the C.T or N.T ratios and you have only three digits you must enter “0” as the first digit.
E.g. 100/5 would be entered as 0100/5.
To change the pulse output value
Code 21 (switch 8 on)To enter the C.T. Ratio code 13 (switch 8 on)

9
Please follow these instructions precisely.
1. Press Function Key
The display will change to.
You will notice the cursor is flashing at the first digit on the left of the two digits
Press the key with 3 on it, the cursor will now move to the next digit, now press 0.
Press Enter.
The display will change to.
You will notice the cursor is flashing at the first digit on the left (+)
To Increase Contrast Press The Key “Energy Imp” The contrast will start to go darker.
Keep pressing until you have reached your desired setting
( - ) Press the “Energy Exp” key to lighten the display.
When finished
Press Enter.
The meter will automatically take you back to the default display.
8
Please follow these instructions precisely.
1. Press Function Key
The display will change to.
You will notice the cursor is flashing at the first digit on the left of the two digits
Press the key with 2on it, the cursor will now move to the next digit, now press 2.
Press Enter.
The display will change to.
You will notice the cursor is flashing at the first digit on the left TO ALTER THE time
Select the number and press the key, the cursor will now move to the next digit to the right.
When finished
Important.
The pulse time can be set from 20ms to 300ms. If it is above 300ms, the default
time is 100ms.
Press Enter.
The meter will automatically take you back to the default display.
The kVah pulse output will automatically be set to the same value.
To change the display contrast
Code 30 (switch 8 on)
To change the pulse closure time
Code 22 (switch 8 on)

11
Please follow these instructions precisely.
1. Press Function Key
The display will change to.
You will notice the cursor is flashing at the first digit on the left of the two digits
Press the key with 5on it, the cursor will now move to the next digit, now press 0.
Press Enter.
The display will change to.
The display will indicate what the meter is sensing.
If you have connected the meter correctly you should see above display.
If you see L1, L2 or L3 SHOWING “EXP” this indicates that one or more current transformers are
not connected correctly. This must be corrected to ensure accurate meter readings.
If you see V1,V2 or V3 showing “LOW” check your voltage connections and the actual voltage
on the terminals. This must be corrected to ensure accurate meter readings.
Press Enter.
The meter will automatically take you back to the default display.
10
Please follow these instructions precisely.
1. Press Function Key
The display will change to.
You will notice the cursor is flashing at the first digit on the left of the two digits
Press the key with 3on it, the cursor will now move to the next digit, now press 1.
Press Enter.
The display will change to.
You will notice the cursor is flashing at the first digit on the left, TO ALTER the time the back
light remains on; enter a new digit by pressing the desired number on the key pad.
When you have selected your first digit press enter and the cursor will move to the second
number, repeat above. The maximum time the backlight will remain on is 99 minutes.
When finished
Press Enter.
The meter will automatically take you back to the default display.
To check the connections on the meter
Code 50 (view)
To change the time the back light is on
Code 31 (switch 8 on)

13
Please follow these instructions precisely.
1. Press Function Key
The display will change to.
You will notice the cursor is flashing at the first digit on the left of the two digits
Press the key with 5on it, the cursor will now move to the next digit, now press 2.
Press Enter.
The display will change to.
The above display indicates the individual switches which have been switched to the “on”
position on the binary switch.
“0” indicates the switch is in the “OFF” position
“1” indicates the switch is in the “ON” position.
Press Enter.
The meter will automatically take you back to the default display.
12
Please follow these instructions precisely.
1. Press Function Key
The display will change to.
You will notice the cursor is flashing at the first digit on the left of the two digits
Press the key with 5on it, the cursor will now move to the next digit now, press 1.
Press Enter.
The display will change to.
When you see above display the relay output will open and close once every second. This will
test if the relay is functioning correctly.
When finished
Press Enter.
The meter will automatically take you back to the default display.
Indication of binary switch settings
Code 52 (view)Relay test mode code 51 (switch 8 on)

15
14
Voltage Display Frequency
Amps Display Actual Demand
Power Factor Maximum Demand
Energy IMP (Default Screen)
Energy EXP
Instantaneous KVAR
Maximum and Minimum Volts
Maximum and Minimum Neutral Amps
Maximum and Minimum Amps
Instantaneous KVA
Instantaneous KW
The Information Key
indicates how the
meter has been
programmed.
The Function Key to
select special
functions.
Display of 4 lines with
20 characters per line.
Membrane Keypad
with 15 sealed keys.
To View Minimum and Maximum Values Press: Volts (FUNC 60), Amps (FUNC 61) and
Neutral Amps (FUNC 62).
To reset minimum and maximum values
above press: Function Key 09 (Volts), 10
(Amps) or 11 (Neutral Amps). E.g. Amps: Press
‘Function Key’, Enter Function Number 10,
Press ‘Enter Key’ to reset phase amps, this
returns you back to default screen.
Key functions

17
16
8
94
5
6
7
10
2
1
3
When you press the information key and the communication module is fitted the following displays
will appear.
To move on to the displays shown below press the “INFORM” key repeatedly until
the required display is shown.
Please Note.
If there is no communication module fitted, you will only see displays 1, 4, 5, 6, 7, 8, 9 & 10.
You will notice in the picture below two red vertical rows of switches 1 - 8. Above each row the
letters “ADDR” and “FUNC” are printed. These individual switches will have to be selected to
programme the correct protocol in the meter. See below.
You will notice two red binary switches next to each other, one is marked “ADDR” and the other
switch is marked “FUNC”.
The binary switch has 8 switches numbered 1-8.
The number sequence is as follow.
1 = 1 3= 4 5= 16 7 = 64
2= 2 4= 8 6= 32 8 = 128
“ADDR” Binary Switch
The binary switch on the left is marked “ADDR” and is for setting the meters address number.
Each meter in the Modbus system must have its own unique number.
E.G. by moving the number 1 switch to the “on" position you have numbered this meter as 1.
By switching numbers 1 and 4 to the “on” position this becomes number 9.
The highest number which you can allocate to a meter is 128.
Binary Switches
ADDR.
Information key Programming the communication module

Indice
Altri manuali Autometers Systems Strumento di misura

Autometers Systems
Autometers Systems A-45 Series Manuale utente

Autometers Systems
Autometers Systems HORIZON HT-1095 Manuale utente

Autometers Systems
Autometers Systems IC 995 Manuale utente

Autometers Systems
Autometers Systems ADP3-80C Manuale utente

Autometers Systems
Autometers Systems Q-180 Manuale utente

Autometers Systems
Autometers Systems HORIZON HT-400 Manuale utente

Autometers Systems
Autometers Systems HORIZON HT-35 Manuale utente

Autometers Systems
Autometers Systems ic9 Manuale utente

Autometers Systems
Autometers Systems HORIZON HT-35 Manuale utente

Autometers Systems
Autometers Systems HORIZON HT-1095 Manuale utente