"PHASE" button
Overview; depending on the mode the display may not show all
values.
Column
left
Column
right First line Second line Third line
A
A
A
I1I2I3
Ln
Ln
Ln
V
V
V
UL1 UL2 UL3
LL
LL
LL
V
V
V
UL1L2 UL2L3 UL3L1
kW
kW
kW
PL1 PL2 PL3
var
var
var
QL1 QL2 QL3
kVA
kVA
kVA
SL1 SL2 SL3
PF
PF
PF
λL1 λL2 λL3
D
P
F
PF
PF
PF
Displace-
ment factor
cos (φ)L1
Displace-
ment factor
cos (φ)L2
Displace-
ment factor
cos (φ)L3
U
t
%
%
%
THD UL1 THD UL2 THD UL3
I
t
%
%
%
THD I1THD I2THD I3
K
Fk-factor I1k-factor I2k-factor I3
UPhase angle
UL1
Phase angle
UL2
Phase angle
UL3
IPhase angle
I1
Phase angle
I2
Phase angle
I3
"SETUP" button
Press the "SETUP" button for more than 3 s to access the setup
mode.
Press the "SETUP" button again to return to the default display
screen.
Menu overview
The following diagram will help you to familiarise yourself with
the menu:
To be able to change parameters, you must first enter
the password. (factory setting: 0)
enable energypulse EN PULSE
set backlight time out BLTO SET
OK
OK
OK
OK
OK
OK
OK
OK
Setup menu
PROGRAMMING
enter password PASSWORD
change password SET PASS enter new password NEW PASS
set wiring mode TYPE
select transformer ratio for the voltage transformer PT
set date DATE
* set baud rate BAUD
select current transformer ratio CT
set energypulse constant EN CONST
set demand DMD SET
set energyvalues SET ENGY
set clock CLK
clear energyCLR ENGY
clear peak demand CLR DMD
clear SOE CLR SOE
* set DO triggered mode DO CTRL
choose CT direction CT REV
set reactive energyimport kvarh
set active energyexport -kWh
set active energyimport kWh
info INFO
set reactive energyexport -kvarh
set apparent energykVAh
Serial number of device
Date of software update UPDATE
Protocol version PRO VER
Software Version SW-VER
* set address for measuring device ID
* set conguration paritybit CONFIG
choose kVA calcuation method KVA SET
choose power factor convention PF SET
set no. of sliding windows NUM
set demand period PERIOD
set DO1 control mode DO1
set I3 CT polarityI3 REV
set I2 CT polarityI2 REV
set I1 CT polarityI1 REV
set DO2 control mode DO2
* PEM333(-P) only
Button