2Specification
MAN103D-V1.3
2. SPECIFICATION
General
Display: LCD which is continuously powered.
Resettable Total: 7 digits with 10mm (0.4") high digits. Resettable
from front panel.
Accumulated Total: Displayed when the ACCUM TOTAL button is
pressed.
Rate: 4½ digits with 8.5mm (0.33") high digits.
K-factor: The pulses per unit of measure (eg. pulses/gallon)
is programmable in the range 0.000001 to
999,999.
Decimal Points: Decimal point positions are fully programmable
for both rate and total.
Timebase: Rate can be displayed in units per second, minute,
hour or day.
Frequency Range: 0.01Hz to 10kHz.
Signal Type: Link settable for sinewave (15mV P-P minimum),
open collector, reed switch, pulse or Namur
proximity switch (DC Power/Alarm Version).
Outputs: Two open collector outputs suitable for driving DC
solenoids or external relays. The outputs can be
programmed to provide high and low flow alarms
or pulse output and low flow alarm.
Switching Power: 200mA. 30VDC maximum.
DC Power Input: 9-28 Volt at 4mA maximum.
Supply Backup: 2 x User replaceable Lithium battery.
Pulse Duration: 1ms if CAL0 = 2 (unscaled pulse output).
If CAL0 = 1 (scaled pulse output) the duration of
the pulse automatically adjusts to the output
frequency:
a. 1ms if output > 50Hz.
b. 10ms if output = 5...50Hz.
c. 100ms if output < 5Hz.