Diginet RAPIX eHub Manuale utente

Installation
Guide
DGOZ
-
EHUB
-
4G
-
2S
DIGINET.NET.AU
RAPIX ighting Control System - eHub
Designed in Australia to
meet Australian Standards
and installation conditions

RAPIX Lighting Control System RAPIX Lighting Control System - eHub
2
1. Product item
This guide rovides user o eration and roduct s ecification information for the RAPIX Lighting Control System
‘eHub’, item number DGOZ-EHUB-4G-2S.
2. Product package contents
The eHub ackage includes the following:
•1 x eHub
•1 x 12V dc SELV ower su ly.
3. Important notes and safety information
WARNING
– Electric shock may result in serious injury or death. Follow all warnings in this
guide and on the roduct while working in accordance with the latest electrical safety
ractices.
•The eHub does not have a mains su ly connection. DALI Lines o erate on an ELV dc su ly between 9.5V
and 22.5V but must be considered at mains otential due to basic equi ment isolation and cable
segregation between mains and DALI. DALI is Functional Extra Low Voltage (FELV) as defined by standard
IEC61140
•The installer must be suitably qualified and should work in accordance with standard safety rocedures
for mains- owered electrical equi ment
•A ro riate segregation is to be maintained between the SELV/Data cabling and mains/DALI Line cabling
in accordance with local regulations
•There are no user serviceable arts inside the eHub. Do not attem t to disassemble or o erate the device
with any covers removed
•The eHub is intended for indoor use
•Outdoor installations will require the device to be housed in a suitable IP rated enclosure
•Consult the manufacturer’s instructions for Lighting Control Gear and other DALI units that may be
connected to the DALI Lines.
If you require information or assistance regarding the installation, configuration, or o eration of the eHub,
contact Technical Services at Diginet Control Systems. Contact details are rovided on the back cover of this guide
and also at www.diginet.net.au

RAPIX Lighting Control System RAPIX Lighting Control System - eHub
3
4. Product summary and capabilities
The eHub is a RAPIX lighting control system device which connects between in ut eri herals and a DALI line.
The eHub manages in ut eri heral ower requirements, as well as embedded logical functions and DALI
communications for these connected in ut eri herals. The connected in ut eri herals, such as RAPIX modular
switches and PIR sensors, are then able to communicate with a DALI Line.
The unit includes four in uts for connecting to RAPIX smart in ut eri herals, and two additional in ut
connections for occu ancy sensors and/or dry contacts.
The eHub is a com act unit which fits through a standard 90mm downlight ceiling hole and is suitable for locating
in a ceiling void.
The eHub is configured via the Diginet RAPIX software suite.
5. Product features
•Powered via external 12V dc SELV ower su ly
•In ut sockets for quick and easy in ut eri heral connection
•Segregated terminal block for DALI Line connections
•LED indicators for ower, DALI and Ethernet
•Suitable for mounting in a ceiling void
•Fits through a 90mm downlight hole
•Programmed via DALI
•Four in ut connections for RAPIX smart in ut eri herals
•Two in ut connectors for occu ancy sensors and/or dry contacts in ut eri herals
•Actions for connected in ut eri herals are configurable. For exam le, a RAPIX modular switch can be
configured as a toggle dimmer, memory dimmer, long ress fade time, double ta action and many other
configurations
•Su ort for 32 'Zones', Zones being collections of DALI Grou s and/or DALI Short Addresses
•Su ort for u to 16 DALI scenes and (additionally) 16 RAPIX scenes.
6. Mounting the eHub
The eHub is suitable for mounting in a variety of
indoor locations, including above sus ended tile
ceilings and fixed lasterboard ceilings.
The eHub has an ingress rotection rating of IP20 and
as such is not rotected against moisture ingress. It is
therefore not suitable for mounting in an outdoor
environment without being housed in a suitable
weather roof enclosure.
The eHub includes two 6mm mounting holes. These
can be used to anchor the eHub in a suitable location,
ty ically using fixing screws or cable ties.

RAPIX Lighting Control System RAPIX Lighting Control System - eHub
4
7. Inputs and output connections
The eHub connects to the following:
•12V dc SELV ower su ly connection
•A DALI Line, with u to 64 DALI devices (each with a DALI Short Address) connected to the line
•Four connections for RAPIX smart in ut eri herals
•Two in ut eri heral connections for dry contacts and two 12V dc sensors (Note: each pair of dry contact
and 12V dc sensor inputs are internally connected in parallel)
•An Ethernet connection (future use)
8. Indicators
Power Indicator
Indicator
Indicator Meaning
Red
Power available
Red
-
Flash OFF
Received Data from In uts
OFF
eHub not owered
DA I Indicator
Indicator
Indicator Meaning
Green
-
Flash OFF
DALI available
Green
-
Flash ON
DALI not available
Green Fast Flashing ON/OFF
DALI communications
Ethernet Indicator
Indicator
Indicator Meaning
Green ON
Link/Active
Green OFF
No Link
Yellow Flashing
Data activity

RAPIX Lighting Control System RAPIX Lighting Control System - eHub
5
9. Powering connected input peripherals
The eHub su lies ower to all connected in ut eri herals such as RAPIX modular switches and 12V dc sensors.
10. Connections Overview
WARNING
-
DALI Lines
must be considered at 240Vac electrical mains otential due to basic
equi ment isolation and cable segregation between mains and DALI.
Electric shock may result in serious injury or death. Follow all warnings in this guide and on
the roduct while working in accordance with the latest electrical safety ractices.

RAPIX Lighting Control System RAPIX Lighting Control System - eHub
6
11. Connecting 12V dc SE V power supply
The eHub is owered via an external 12V dc SELV ower su ly, su lied with the unit. The ower su ly is
connected as shown below.
A third art
y
12V dc
SELV owered su ly can be used to ower the eHub. Any third arty
ower su ly used with the eHub must be 12V dc regulated and must be ca able of su lying
1.5A @ 12V dc.
12. Connecting to a DA I ine
WARNING
-
DALI Lines
must be considered at 240Vac electrical mains otential due to basic
equi ment isolation and cable segregation between mains and DALI.
Electric shock may result in serious injury or death. Follow all warnings in this guide and on
the roduct while working in accordance with the latest electrical safety ractices.
The eHub can be connected to a single DALI Line, as shown below. Se arate DALI loo -off terminals are also
rovided.
The DALI
L
ine cable has two conductors
and these are not olarity sensitive. DALI Line cabling
must be double insulated and mains rated.
Each DALI Line requires an external
DALI com liant ower su ly to be connected before it
will o erate. A Diginet DALI Power Su ly, item number DG MPS01 ( urchased se arately),
can be connected to each DALI Line to fulfil this requirement.

RAPIX Lighting Control System RAPIX Lighting Control System - eHub
7
13. Connecting RAPIX modular switches
RAPIX modular switches are wall switches for the RAPIX Lighting Control System which fit in standard
Australian wall switch grid lates. RAPIX modular switches function as eHub in ut eri herals.
A
RAPIX modular
master
switch
mounted in a typical Australian one
-
gang wall switch grid plate
RAPIX modular switches are available as ‘masters’ or ‘slaves’.
Master RAPIX modular switches connect directly to the eHub.
Slave RAPIX modular switches connect via master RAPIX modular switches
RAPIX modular switches are configured in RAPIX software to erform a wide range of functions and each modular
switch (both masters and slaves) includes two software configurable LED indicator colours, white and amber.
13.1. Features
•Two configurable LED colours, white and amber
•Fits standard Australian wall late a ertures
•Master RAPIX modular switches connect to the eHub and are owered via the eHub
•Slave RAPIX modular switches connect to a master and are owered via the master
•Ty ical functions include
•Toggle on / off
•Fade lights u or down
•Start or cancel a timer
•Recall a fixed level
•Toggle between off and the current Level
•Issue a scene
All commissioning is carried on via Diginet RAPIX software suite. The configuration is downloaded to the eHub via
a DALI line.
Do not
connect
RAPIX modular switches
to the building/house ac mains su ly.
RAPIX modular switches are control devices which are owered by the eHub via an SELV
connection and must only be connected as described in this guide. That is, master switches are
connected to the eHub, slave switches are connected to master switches.

RAPIX Lighting Control System RAPIX Lighting Control System - eHub
8
13.2. Range
The following RAPIX modular switches can be connected to each of the four smart in ut eri heral connectors on
the eHub.
Diginet Part Number
Description
DGOZ
-
MOSW
-
M
-
PB
RAPIX
m
odular switch
–
Push Button
Master
DGOZ
-
MOSW
-
M
-
RO
RAPIX
m
odular switch
–
Rocker Master
DGOZ
-
MOSW
-
M
-
RE
RAPIX
m
odular switch
–
Rota
ry Master
DGOZ
-
MOSW
-
S
-
PB
RAPIX
m
odular switch
–
Push Button
Slave
DGOZ
-
MOSW
-
S
-
RO
RAPIX
m
odular switch
–
Rocker Slave
DGOZ
-
MOSW
-
S
-
RE
RAPIX
m
odular switch
–
Rotary Slave
Note that RAPIX modular switches are urchased se arately.
14. Connecting RAPIX modular switches to the eHub
Each master RAPIX modular switch is su lied with the following atch leads.
eHub to RJ-45 atch lead
Master RAPIX modular switch to RJ-45 atch lead
These two atch leads are used in conjunction with standard Cat5/Cat5e cable and RJ-45 connectors to connect
master RAPIX modular switches in the eHub. See the ictures and diagram on the following age.

RAPIX Lighting Control System RAPIX Lighting Control System - eHub
9
14.1. RAPIX modular switch eHub patch lead connections
Connection between a m
aster
RAPIX modular
switch and RJ-45 patch lead
Connection between
the
eHub and RJ
-
45 patch lead
14.2. Connections from the eHub to a master RAPIX modular switch
The diagram below shows the connections between the eHub and a master RAPIX modular switch.
The maximum distance between a master RAPIX modular switch and the eHub is 100m.
All m
aster
RAPIX modular switches
(
ush button, rocker and rotary
)
are
connected to the
eHub in the same way as indicated above

RAPIX Lighting Control System RAPIX Lighting Control System - eHub
10
15. Connecting masters to slaves
Slave RAPIX modular switches connect directly to masters. Slaves have an integrated flying lead with a male
connector. Masters have matching female sockets.
Connection between a
master and slave RAPIX
modular switch
15.1. Typical installed connections
Typical connections between master and slave
rotary RAPIX modular switches in a two gang grid
plate
Typical connections between
a
master and
three
slave RAPIX modular switches in a four gang grid
plate
15.2. Maximum number of master / slave connections
The number of slave RAPIX modular switches su orted by each ty e of master are shown in the table below.
N
umber of possible slaves connected
Master type
Slave Push Button
s
or Rocker
s
Slave Rotary
Push Button
U to 5
N/A
Rocker
U to 5
N/A
Rotary
N/A
1
The maximum ermissible distance between th
e master and slaves
RAPIX modular
switches is limited to the re-terminated slave cable length. This re-terminated cable
must not be extended or shortened.