
MECHANICAL INSTALLATION
The instrument is intended for DIN
rail mounting.
For GUIDA DIN installation, follow
the steps described below:
• Move the two spring docking
devices to their standby position
(use a screwdriver to press against
the relative compartments)
• Then mount the controller on the
DIN RAIL, pressing on the spring
docking devices which will go to
the closing position.
SIDE VIEW
REAR VIEW 3D VIEW
TECHNICAL SPECIFICATIONS (EN 60730-2-9)
Classification: electronic automatic control (not safety) device for incorporation
Mounting: Omega DIN rail.
Type of action: 1.C - 1.Y
Pollution class: 2
PTI of materials used for insulation: PTI 250V (device made with class IIIa material)
Overvoltage category: II
Nominal pulse voltage: 2500V
Temperature: Use: –20 … +55°C • Storage: -40 … +85°C
Power supply: SMPS 100-240 Va ±10% 50/60 Hz
Power consumption: 5W max
Fire resistance category: D
Software class: A
RTC battery life: In absence of external power, the clock battery will last 4 days.
FURTHER INFORMATION
TelevisIn Characteristics
Measurement range: NTC: –50.0...+110°C; PTC: –50.0...+150°C; PT1000: –50.0...+400°C (on display with 3 digits + sign)
Accuracy: NTC, PTC: ±0.5% e.o.s. + 1 digit
PT1000: ±1°C (-30°C ... 30°C) e ±1% e.o.s. (-50°C ... 400°C)
0-1V: ±2% e.o.s.
0-5V, 0-10V, 0...20mA, 4...20mA: ±1% e.o.s.
Impedance: 0-1V: 110kΩ; 0-5V: 110kΩ; 0-10V: 21kΩ; 0...20mA: 100Ω; 4...20mA: 100Ω
Resolution: NTC, PTC, PT1000: 0.1°C; 0-1V, 0-5V, 0-10V, 0...20mA, 4...20mA: 0,1
Analogue Inputs: PB1, PB2, PB5: NTC, PTC, PT1000 inputs or configurable DIs
PB3, PB4:
DI, NTC, 0-1V, 0-5V, 0-10V, 0...20mA or 4...20mA configurable inputs
Digital Inputs: DI1, DI2: Multifunctional digital inputs
Digital Outputs: OUT1: SPST relay 2A max 250Va
TelevisOut Characteristics
Digital Outputs: OUT1, OUT2, OUT3: SPST relay 2A max 250Va
OUT4: SPDT relay 2A max 250Va
OC outputs/Digital Inputs: OUT5/DI1: OC Analogue Output or voltage-free Digital Input
OUT6/DI2: OC Analogue Output or voltage-free Digital Input
The two analogue outputs are low voltage (SELV) Open Collector (OC) ones: PWM with
- Precision: 2%;
- Nominal range: 0…16.9Vc(12V~ rectified); closure 12Vc;
- Maximum current: 35mA (min load of 340Ohm @12Vc)
NOTA: ** Outputs OUT5 and OUT6 (typically connected to the device's auxiliary 12Vcoutput) cannot
deliver more than 70mA in total. Any other loads connected to the same 12Vc auxiliary output
must also be taken into account.
Mechanical Characteristics
Container: PC+ABS resin casing, UL94 V-0
Dimensions: 4 DIN-rail
Terminals: removable screw terminals with 2.5mm2cross-section.
Connectors: TTL for MFK / Device Manager connection (via DMI)
RS485 to connect to TelevisSystem/Modbus supervisor.
Humidity: Usage / Storage: 10...90% RH (non-condensing)
Regulations
Electromagnetic compatibility: The device complies with Directive 2004/108/EC
Safety: The device complies with Directive 2006/95/EC
Food Safety: The device complies with standard EN13485 as follows:
- suitable for storage
- application: air
- climate range: A
- measurement class 1 in the range from -25°C to 15°C (*)
(*with Eliwell probes only)
NOTE: The technical specifications stated in this document regarding the measurement (range, accuracy, resolution, etc.)
referstrictly to the instrument and not to any accessories provided, such as the probes.
This means, for example, that the error introduced by the probe must be added to the error of the instrument.