EMKO ESM-3712-H Manuale utente

Instruction Manual. ENG ESM-3712-H 02 V00 03/07
Internal Buzzer
ESM- 77x35 DIN Size Heating Controller
3712-H
ESM- 77 x 35 DIN3712-H Size
Digital, ON / OFF Heating Controller
(SET + ALARM)
- 3 Digits Display
- PTC Input or
J Type Thermocouple Input or,
K Type Thermocouple Input or,
2-wire PT-100 Input or,
2-wire PT-1000 Input (It must be determined in order)
- ON/OFF Control
- Adjustable Temperature Offset
- Temperature Control Output and Alarm Output
- Process and Alarm Set Values Boundaries
- Relay or SSR Driver Output
- Digital Input (Cooking time start/stop input)
- Adjustable Cooking Time (Timer) from Front Panel
- Temperature Control according to the Cooking Time (Timer)
- User can select to start Cooking Time (Timer) when
Temperature reaches to the Set Value
- Temperature Control with Manual Heating Function
- Adjustable Internal Buzzer According to Cooking Time (Timer),
Probe Defect and Alarm Status
-
- Password Protection for Programming Section
Button Protection

2
ABOUT INSTRUCTION MANUAL
Instruction manual of ESM-3712-H Heating Controller consists of two main sections.
Explanation of these sections are below. Also, there are other sections which include order
information and technical specifications of the device. All titles and page numbers in instruction
manual are in “ ” section. User can reach to any title with section number.
In this section, physical dimensions of the device, panel mounting, electrical wiring,
physical and electrical installation of the device to the system are explained.
Also in these sections, there are warnings to prevent serious injury while doing the
physical and electrical mounting or using the device.
Explanation of the symbols which are used in these sections are given below.
CONTENTS
Installation:
Operation and Parameters:
In this section user interface of the device, accessing to the parameters, description of the
parameters are explained.
a
c
i
This symbol is used to determine the dangerous situations as a result of an electric
shock. User must pay attention to these warnings definitely.
This symbol is used for safety warnings. User must pay attention to these
warnings.
This symbol is used to determine the important notes about functions and usage of
the device.

Ýçindekiler
Sayfa 5
Sayfa 34
Sayfa 20
Sayfa 12
Sayfa 7
Sayfa 33
3
1.PREFACE............................................................................................................................................
1.1 GENERAL SPECIFICATIONS
1.2 ORDERING INFORMATION
1.3 WARRANTY
1.4 MAINTENANCE
2.1 GENERAL DESCRIPTION
2.2 FRONT VIEW AND DIMENSIONS OF ESM-3712-H HEATING CONTROLLER
2.3 PANEL CUT-OUT
2.4 ENVIRONMENTAL RATINGS
2.5 PANEL MOUNTING
2.6 INSTALLATION FIXING CLAMP
2.7 REMOVING FROM THE PANEL
3.1 TERMINAL LAYOUT AND CONNECTION INSTRUCTIONS
3.2 ELECTRICAL WIRING DIAGRAM
3.3 VIEW OF THE DEVICE LABEL
3.5 TEMPERATURE SENSOR INPUT CONNECTION
3.5.1 TC (THERMOCOUPLE) CONNECTION
3.5.2 PTC CONNECTION
3.5.3 PT-100 AND PT-1000 CONNECTION
3.6 GALVANIC ISOLATION TEST VALUES OF ESM-3712-H HEATING CONTROLLER
3.7 OUTPUTS CONNECTIONS
3.7.1 PROCESS OUTPUT (RELAY) CONNECTION
3.7.2 PROCESS OUTPUT (SSR DRIVER) CONNECTION
3.7.3 ALARM OUTPUT (RELAY) CONNECTION
3.7.4 ALARM OUTPUT (SSR DRIVER) CONNECTION
4.2 CHANGING AND SAVING PROCESS SET VALUE
4.3 CHANGING AND SAVING COOKING TIME (TIMER) PARAMETER VALUE
4.4 PROGRAMMING MODE PARAMETER LIST
4.5 COOKING TIME (TIMER) ON/OFF OPERATION
4.5.1 COOKING TIME (TIMER) ON/OFF OPERATION WITH COOKING BUTTON
4.5.2 COOKING TIME (TIMER) ON/OFF OPERATION WITH COOKING TIME
START/STOP INPUT
4.6 OPERATION GRAPHICS OF ESM-3712-H HEATING CONTROLLER
4.6.1 OPERATION GRAPHICS OF PROCESS OUTPUT
4.6.2 OPERATION GRAPHICS OF ALARM OUTPUT AND ALARM TYPES
4.7 EASY ACCESS DIAGRAM OF PROGRAMMING MODE PARAMETERS
4.8 ENTERING TO THE PROGRAMMING MODE, CHANGING AND SAVING PARAMETERS
2.INSTALLATION....................................................................................................................................
3.ELECTRICAL WIRINGS......................................................................................................................
4.FRONT PANEL DEFINITION AND ACCESSING TO THE MENUS....................................................
5.FAILURE MESSAGES IN ESM- HEATING CONTROLLER..................................................
6.SPECIFICATIONS................................................................................................................................
3712-H
3.4 SUPPLY VOLTAGE INPUT CONNECTION OF THE DEVICE
4.1 OBSERVATION OF SOFTWARE REVISION ON THE DISPLAY
Contents

4
Manufacturer Company Name :
Manufacturer Company Address:
Emko Elektronik A.S.
DOSAB, Karanfil Sokak, No:6, 16369 Bursa, Turkiye
EU DECLARATION OF CONFORMITY
The manufacturer hereby declares that the product conforms to the following standards and
conditions.
ESM-3712-H
ESM-3712-H
Electrical equipment for measurement, control and laboratory
use
Product Name
Model Number :
Type Number :
Product Category :
Conforms to the following directives :
: Heating Controller
73 / 23 / EEC The Low Voltage Directive as amended by 93 / 68 / EEC
89 / 336 / EEC The Electromagnetic Compatibility Directive
EN 61000-6-4:2001 EMC Generic Emission Standard for the Industrial Environment
EN 61000-6-2:2001 EMC Generic Immunity Standard for the Industrial Environment
EN 61010-1:2001 Safety Requirements for electrical equipment for measurement, control and
laboratory use.
Has been designed and manufactured according to the following specifications

5
ESM-3712-H
Standard
Control Output
PTC
JorKTypeTC
2 Wire PT 100
2 Wire PT 1000
Process Output
(Relay Output)
Temperature Sensor
Input
Power Supply
Input
Standard
24V (-%15,+ ), 50/60Hz
W%10
Cooking Time (Timer)
Start/Stop Input
Digital Input
Alarm Output
Alarm Output
()Relay Output
Heating Function
ON/OFF Operation
Optional
Process Output
(SSR Driver Output)
Alarm Output
(SSR Driver Output)
Heating Function
ON/OFF Operation
1.Preface
ESM-3712-H series Heating Controllers are designed for measuring and controlling
temperature. They can be used in many applications with their easy use, On/ Off control form and
cooking time properties.
Some application fields which they are used are below:
Application Fields
Applications
Glass
Food
Plastic
Heating
Baking Ovens
Incubators
Storages
Etc...
Petro-Chemistry
Textile, Automative
Machine Production Industries
etc...
Air Conditioning
1.1 General Specifications
Control Output
Alarm Output

6
1.2 Ordering Information
All order information of ESM-3712-H
Heating Controller are given on the table at
left. User may form appropriate device
configuration from information and codes
that at the table and convert it to the
ordering codes.
Firstly, supply voltage then other
specifications must be determined. Please
fill the order code blanks according to your
needs.
Please contact us, if your needs are
out of the standards.
V
Z
Vac,
Vdc,
Vdc or Vac can be
applied.
Þ
Þ
ÞW
c
1.3 Warranty
EMKO Elektronik warrants that the equipment delivered is free from defects in material and
workmanship. This warranty is provided for a period of two years. The warranty period starts from
the delivery date. This warranty is in force if duty and responsibilities which are determined in
warranty document and instruction manual performs by the customer completely.
1.4 Maintenance
Repairs should only be performed by trained and specialized personnel. Cut power to the device
before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of
these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl
alcohol or water to clean the external plastic case.
Ordering Information
ABCD E FGHI /
/
UVWZ/
/
000100
Supply VoltageA
05
09
J, Fe CuNi IEC584.1(ITS90)
Input Type
BC Scale(°C)
0°C 800°C
-19.9°C 99.9°C
PT 100, IEC751(ITS90)
ESM-3712-H (77x35 DIN Boyutlu)
24V ( -%15, +%10 ) 50/60HzW
2
10 K, NiCr Ni IEC584.1(ITS90)
-50°C 400°C
0°C 999°C
11 PT 100, IEC751(ITS90)
12 PTC (Note-1) -50°C 150°C
15 PTC (Note-1)
14 -50°C
13
-19.9°C 99.9°C
PT 1000, IEC751(ITS90)
PT 1000, IEC751(ITS90)
400°C
-19.9°C 99.9°C
Temp.Sensor which is given with ESM-3712-H
V
0None
1
2
9Customer
PTC-M6L50.K1.5(PTC Air probe with 1.5 m silicon cable)
PTCS-M6L30.K1.5.1/8”(PTC Liquid probe with 1.5 m silicon cable)
Note-1 : If input type is selected PTC (BC = 12 or BC = 15), PTC
Temperature sensor is given with the device. For this reason,
PTC sensor type ( V ) must be declared in ordering information.
1
E
01
FG
Process Out
Alarm Out
202
Outputs
Process Out
Alarm Out
SSR Driver Output (Max. 10mA@ 24V )Z
SSR Driver Output (Max. 10mA@ 24V )Z
Relay Output (10 @250V at resistive load, 1NO)A V
Relay Output (5 @250V at resistive load, 1NO)A V

7
In package ,
- One piece unit
- Two pieces mounting clamps
- One piece instruction manual
A visual inspection of this product for possible damage occured during shipment is
recommended before installation. It is your responsibility to ensure that qualified
mechanical and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit, power
off the system and the electrical connection of the device from the system.
The unit is normally supplied without a power supply switch or a fuse. Use power switch
and fuse as required.
Be sure to use the rated power supply voltage to protect the unit against damage and to
prevent failure.
Keep the power off until all of the wiring is completed so that electric shock and trouble
with the unit can be prevented.
Never attempt to disassemble, modify or repair this unit. Tampering with the unit may
results in malfunction, electric shock or fire.
Do not use the unit in combustible or explosive gaseous atmospheres.
During the equipment is putted in hole on the metal panel while mechanical installation
some metal burrs can cause injury on hands, you must be careful.
Montage of the product on a system must be done with it’s fixing clamps. Do not do the
montage of the device with inappropriate fixing clamp. Be sure that device will not fall
while doing the montage.
It is your responsibility if this equipment is used in a manner not specified in this
instruction manual.
separate
Before beginning installation of this product, please read the instruction
manual and warnings below carefully.
2.Installation
c

2.1 General Description
2.2 Front View and Dimensions of ESM- i3712-H Heat ng Controller
35mm / 1.38 inch
8
77mm / 3.03 inch
ESM - 3712-H
Mounting Clamp
Front Panel
IP65 Protection
NEMA 4X
Panel Surface
(maximum thickness 15mm / 0.59 inch)

2.3 Panel Cut-Out
110 mm / 4.33 inch (min)
50 mm / 1.97 inch (min)
29mm / 1.14 inch
71mm / 2.79 inch
Maximum 15 0.59 inchmm /
58.5 mm / 2.30 inch
4 mm /0.16 inch
9

c
1
2
10
Operating Temperature :
Max. Operating Humidity :
Altitude :
0to50°C
90 Rh (non-condensing)
Up to 2000m.
%
Operating Conditions
Forbidden Conditions:
Corrosive atmosphere
Explosive atmosphere
Home applications (The unit is only for industrial applications)
2.4 Environmental Ratings
c
2.5 Panel Mounting
1-Before mounting the device in your
panel, make sure that the cut-out is of
the right size.
2-Insert the device through the cut-out.
If the mounting clamps are on the unit,
put out them before inserting the unit to
the panel.
During installation into a metal panel, care should be taken to avoid injury from
metal burrs which might be present. The equipment can loosen from vibration
and become dislodged if installation parts are not properly tightened. These
precautions for the safety of the person who does the panel mounting.
Indice
Altri manuali EMKO Controllori

EMKO
EMKO ESM-3711-CL Manuale utente

EMKO
EMKO ESM-4410 Manuale utente

EMKO
EMKO ESM-4930 Manuale utente

EMKO
EMKO EDA-3700 Manuale utente

EMKO
EMKO ESM-3711-CN Manuale utente

EMKO
EMKO ESM-9995 Manuale utente

EMKO
EMKO esm-4450 Manuale utente

EMKO
EMKO Trans-midiAUTO.MPU.232... Manuale utente

EMKO
EMKO EAOM-210 FLJ Manuale utente

EMKO
EMKO ESM-9430 Manuale utente

EMKO
EMKO ESM 30 Series Manuale utente

EMKO
EMKO ESM-3712-CN Manuale utente

EMKO
EMKO ESM-7311-H Manuale utente

EMKO
EMKO EAOM-9F ND Manuale utente

EMKO
EMKO ESM-3721HT Manuale utente

EMKO
EMKO EAOM-9F ND Manuale utente

EMKO
EMKO EAOM-36 Series Manuale utente

EMKO
EMKO ESM-1510 Manuale utente

EMKO
EMKO PID QUADRO EPLC9600 Manuale utente

EMKO
EMKO EAOM-72F Manuale utente





















