EMKO ESM-1510 Manuale utente

ESM-1510 DIN Rail Mounting Temperature Controller
- 3 Digits display
J type thermocouple Input or,
K type t
2-Wire PT 100 Input or,
- Selectable heating or cooling function
- NTC Input or,
PTC Input or,
hermocouple Input or,
2-Wire PT 1000 Input (It must be determined in order)
- ON/OFF temperature control
- Selection of operation with hysteresis
- Adjustable temperature offset
- Set value low limit and set value high limit boundaries
- Relay or SSR driver output
- Operation selection of compressor operates continuously, stops
or operates periodically in case of probe defect
- Compressor protection delays
- Password protection for programming mode
Instruction Manual. ENG ESM-1510 02 V02 07/08
ESM-1510 DIN Rail Mounting Type
Digital, ON / OFF Temperature Controller

Instruction manual of ESM-1510 Temperature Controller consists of two main sections.
Explanation of these sections are below. Also, there are other sections which include order
information and technical specifications of the device. All titles and page numbers in instruction
manual are in “ ” section. User can reach to any title with section number.
In this section, physical dimensions of the device, rail mounting, electrical wiring, physical
and electrical installation of the device to the system are explained.
Also in these sections, there are warnings to prevent serious injury while doing the
physical and electrical mounting or using the device.
Explanation of the symbols which are used in these sections are given below.
CONTENTS
Installation:
Operation and Parameters:
In this section user interface of the device, accessing to the parameters, description of the
parameters are explained.
ABOUT INSTRUCTION MANUAL
a
c
i
2
This symbol is used to determine the dangerous situations as a result of an electric
shock. User must pay attention to these warnings definitely.
This symbol is used for safety warnings. User must pay attention to these
warnings.
This symbol is used to determine the important notes about functions and usage of
the device.

1.PREFACE............................................................................................................................................
2.INSTALLATION....................................................................................................................................
3.ELECTRIAL WIRINGS.........................................................................................................................
1.1 GENERAL SPECIFICATIONS
1.2 ORDERING INFORMATION
2.1 GENERAL DESCRIPTION
2.3
2.4
2.5
3.1 TERMINAL LAYOUT AND CONNECTION INSTRUCTIONS
3.5.1 TC (THERMOCOUPLE) CONNECTION
1.3 WARRANTY
1.4 MAINTENANCE
2.2 FRONT VIEW AND DIMENSIONS OF ESM-1510 TEMPERATURE CONTROLLER
ENVIRONMENTAL RATINGS
REMOVING FROM THE RAÝL
3.2 ELECTRICAL WIRING DIAGRAM
3.3 VIEW OF THE DEVICE LABEL
3.5 TEMPERATURE SENSOR INPUT CONNECTION
3.5.2 PTC AND NTC CONNECTION
3.5.3 PT-100 AND PT-1000 CONNECTION
3.6 GALVANIC ISOLATION TEST VALUES OF ESM-1510 TEMPERATURE CONTROLLER
3.7 OUTPUT CONNECTIONS
3.7.1 RELAY OUTPUT CONNECTION
3.7.2 SSR DRIVER OUTPUT CONNECTION
4.2 CHANGING AND SAVING SET VALUE
4.3 PROGRAM PARAMETERS
4.4 WORKING GRAPHICS OF ESM-1510 TEMPERATURE CONTROLLER
4.5 EASY ACCESS DIAGRAM OF PROGRAMMING MODE PARAMETERS
4.6 ENTERING TO THE PROGRAMMING MODE, CHANGING AND SAVING PARAMETERS
4.FRONT PANEL DEFINITION AND ACCESSING TO THE MENUS....................................................
5.FAILURE MESSAGES IN ESM-1510 TEMPERATURE CONTROLLER............................................
6.SPECIFICATIONS................................................................................................................................
INSTALLATION ONTO THE RAIL
3.4 SUPPLY VOLTAGE INPUT CONNECTION OF THE DEVICE
4.1 OBSERVATION OF SOFTWARE REVISION ON THE DISPLAYS
Contents
Page 5
Page 28
Page 18
Page 11
Page 7
Page 27
3

4
Manufacturer Company Name : Emko Elektronik A.S.
Manufacturer Company Address: DOSAB, Karanfil Sokak, No:6, 16369 Bursa, Turkiye
The manufacturer hereby declares that the product conforms to the following standards and
conditions.
Temperature Controller
ESM-1510
ESM-1510
Electrical equipment for measurement, control and laboratory
use
Product Name :
Model Number :
Type Number :
Product Category :
Conforms to the following directives :
73 / 23 / EEC The Low Voltage Directive as amended by 93 / 68 / EEC
89 / 336 / EEC The Electromagnetic Compatibility Directive
EN 61000-6-4:2001 EMC Generic Emission Standard for the Industrial Environment
EN 61000-6-2:2001 EMC Generic Immunity Standard for the Industrial Environment
EN 61010-1:2001 Safety Requirements for electrical equipment for measurement, control and
laboratory use
Has been designed and manufactured according to the following specifications
EU DECLARATION OF CONFORMITY

1.Preface
1.1 General Specifications
ESM-1510
Optional
Standard Control Output
Alarm Output
NTC
PTC
JorKTypeTC
2-wire PT 100
2-wire PT 1000
Output-1
(SSr Driver Output)
Output-1 (Relay Output)
Control Output
Alarm Output
Heating or Cooling
Function
ON/OFF Operation
ESM-1510 series temperature controllers are designed for measuring and controlling
temperature. They can be used in many applications with their On / Off control form, heating and
cooling control form and easy-use properties.
Some application fields which they are used are below:
Glass
Plastic
Petro-Chemistry
Textile
Automative
Machine production industries
Heating
Baking Ovens
Incubators
Storages
Air Conditioning
Application Fields
Applications
Temperature Sensor
Input
Power Supply
Input
Standard
230 V (±15 ) , 50/60HzV%
Optional Supply Input
115 V (±15 ) , 50/60HzV%
24 V (±15 ) , 50/60HzV%
24 V (-15 )
50/60Hz
W%, +10%
5
12 V (±15 ) , 50/60HzW%

1.2 Ordering Information
All order information of ESM-1510
Temperature Controller are given on the
table at left. User may form appropriate
device configuration from information and
codes that at the table and convert it to the
ordering codes.
Firstly, supply voltage then other
specifications must be determined. Please
fill the order code blanks according to your
needs.
Please contact us, if your needs are
out of the standards.
V
Z
Symbol means Vac,
Symbol means Vdc,
Symbol means Vac/dcW
c
6
1.3 Warranty
EMKO Elektronik warrants that the equipment delivered is free from defects in material and
workmanship. This warranty is provided for a period of two years. The warranty period starts from
the delivery date. This warranty is in force if duty and responsibilities which are determined in
warranty document and instruction manual performs by the customer completely.
1.4 Maintenance
Repairs should only be performed by trained and specialized personnel. Cut power to the device
before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of
these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl
alcohol or water to clean the external plastic case.
ABCD E FGHI /
/
UVWZ/
/
000200
1Relay Output ( resistive load 5 A@250 V , 1 NO + 1NC )V
Output-1
E
Supply VoltageA
Input Type
BC Scale(°C)
ESM-1510
24 V ( ± 15% ) 50/60 HzV
3
115 V ( ± 15% ) 50/60 HzV
4
230 V ( ± 15% ) 50/60 HzV
5
12 V ( ± 15% ) 50/60 HzW
6
9Customer
2SSR Driver Output (Maximum 15 mA@5 V )Z
00
12
05
09
J, Fe CuNi IEC584.1(ITS90)
PTC (Note-1) -50°C 150°C
0°C 800°C
-19.9°C 99.9°C
PT 100, IEC751(ITS90)
10 K, NiCr Ni IEC584.1(ITS90)
-50°C 400°C
0°C 999°C
11 PT 100, IEC751(ITS90)
14 -50°C 400°C
PT 1000, IEC751(ITS90)
13 -19.9°C 99.9°C
PT 1000, IEC751(ITS90)
15 PTC (Note-1) -19.9°C 99.9°C
Temp. Sensor which is given with ESM 1510
V
0None
1PTC-M6L40.K1.5 (PTC Air Probe with 1.5 m silicon cable)
2PTCS-M6L30.K1.5.1/8” (PTC Liquid Probe with 1.5 m silicon
cable)
Customer
3NTC-M5L20.K1.5 (NTC Probe, thermoplastic moulded with
1.5 m cable for cooling application)
4NTC-M6L50.K1.5 (NTC Probe, stainless steel housing with
1.5 m cable for cooling application)
9
Note-1 : If input type is selected PTC or NTC (BC = 12, 15, 18, 19 ),
Temperature sensor is given with the device. For this reason,
If input type is selected as PTC, sensor type (V = 0,1 or 2) or
If input type is selected as NTC, sensor type (V = 0,3 or 4) must be
declared in ordering information.
19 -19.9°C 99.9°C
-50°C 100°C
18
NTC (Note-1)
NTC (Note-1)
24 V ( - 15%, + 10% ) 50/60 HzW
2

7
In package ,
- One piece unit
- One piece rail lock apparatus
- One piece instruction manual
A visual inspection of this product for possible damage occured during shipment is
recommended before installation. It is your responsibility to ensure that qualified
mechanical and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit, power
off the system and the electrical connection of the device from the system.
The unit is normally supplied without a power supply switch or a fuse. Use power switch
and fuse as required.
Be sure to use the rated power supply voltage to protect the unit against damage and to
prevent failure.
Keep the power off until all of the wiring is completed so that electric shock and trouble
with the unit can be prevented.
Never attempt to disassemble, modify or repair this unit. Tampering with the unit may
results in malfunction, electric shock or fire.
Do not use the unit in combustible or explosive gaseous atmospheres.
During the equipment is putted in hole on the metal panel while mechanical installation
some metal burrs can cause injury on hands, you must be careful.
Montage of the product on a system must be done with it’s fixing clamps. Do not do the
montage of the device with inappropriate fixing clamp. Be sure that device will not fall
while doing the montage.
It is your responsibility if this equipment is used in a manner not specified in this
instruction manual.
separate
Before beginning installation of this product, please read the instruction
manual and warnings below carefully.
2.Installation
c

2.1 General Description
8
Rail Lock Apparatus
35 mm / 1.38 inch
86 mm / 3.38 inch
2341 5
96
7
8
SV
P
ESM-1510
SET
°C
Temperature Controller
2.2 Front View and Dimensions of ESM-1510 Temperature Controller

9
86 mm / 3.38 inch
59 mm / 2.32 inch
35 mm / 1.38 inch
46.5 mm / 1.83 inch
Operating Temperature :
Max. Operating Humidity :
Altitude :
0to50°C
90 Rh (non-condensing)
Up to 2000 m.
%
Operating Conditions
Forbidden Conditions:
Corrosive atmosphere
Explosive atmosphere
Home applications (The unit is only for industrial applications)
2.3 Environmental Ratings
c

10
2.5 Panel Mounting
2.4 Installation onto the Rail
1
3
cDuring installation onto the rail, care should be taken to avoid injury from
mechanical part of the system. These precautions for the safety of the person
who does the rai mounting.
The unit is designed for rail mounting.
1- Put into the unit upper side of the
rail properly.
2- Pull down the rail lock apparatus
via a screw driver.
3.-Push the unit from the underside
for mounting to the rail.
2.5 Removing from the Rail
c
1
2
3
1- Pull down the rail lock apparatus
via a screw driver.
ull up the unit to remove from the
rail.
2- Pull the unit from the underside to
seperate the rail lock apparatus from
the rail
3.- P
2
Before starting to remove the unit from the rail, power off the unit and the
related system.
Indice
Altri manuali EMKO Controllori

EMKO
EMKO ESM-3711-CL Manuale utente

EMKO
EMKO EDA-3700 Manuale utente

EMKO
EMKO EAOM-36 Series Manuale utente

EMKO
EMKO Trans-midiAUTO.MPU.232... Manuale utente

EMKO
EMKO EAOM-9F ND Manuale utente

EMKO
EMKO PID QUADRO EPLC9600 Manuale utente

EMKO
EMKO esm-4450 Manuale utente

EMKO
EMKO EAOM-6 Manuale utente

EMKO
EMKO ESM-9430 Manuale utente

EMKO
EMKO ESM 30 Series Manuale utente

EMKO
EMKO ESM-3711-CN Manuale utente

EMKO
EMKO ESM-3712-CN Manuale utente

EMKO
EMKO EAOM-210 FLJ Manuale utente

EMKO
EMKO EPC-1 Manuale utente

EMKO
EMKO ESM-3722 Manuale utente

EMKO
EMKO EZM-4950 Manuale utente

EMKO
EMKO ESM-7311-H Manuale utente

EMKO
EMKO EAOM-72F Manuale utente

EMKO
EMKO ESM-3721HT Manuale utente

EMKO
EMKO ESM-3712-H Manuale utente