LINKING - ONE-BY-ONE
“One-by-one” linking consists in associating one child device at a time to the FireVibes system.
This operation is performed either through the FireVibes Studio software or the EWT100 / IWT100 keyboard-screen interface; it CANNOT be
done through XWT100 devices.
1) Create the “virtual model” of the child device (be aware that the Output Module type has to be selected to link a remote indicator) either on
FireVibes Studio or on the EWT100 / IWT100.
2) Trigger the linking procedure either from FireVibes Studio or from the EWT100 / IWT100.
3) Power-up the child device (either “first time use” or “recovery”).
4) Set the child device’s Link / program switch OPPOSITE to “ON”.
5) Wait the end of the “one-by-one” linking procedure.
6) Check on FireVibes Studio or from EWT100 / IWT100 for linking success. Consult their user manual.
FIXING THE BACK COVER
HOW TO REMOVE AND REINSTALL THE FRONT COVER
Remote indicator’s installation requires the device’s top cover to be removed from the its bottom (see picture 3):
1) Screw the grain inwards until it stops
2) Press the tab shown in the picture and gently and carefully remove the cover
Reinstalling the cover consists in performing the operation portrayed in picture 3.
TAMPER DETECTION FEATURE
The opening of the wireless remote indicator’s case is signaled by the control panel as a tampering attempt; the device’s PCB is equipped with
a spring-tactile switch assembly: if the case is closed this spring is kept pressed, but when released (and this occurs if the case is opened) the
remote indicator sends a tamper attempt message to the control panel which provides the signalization of such event.
The signalization of this event is automatically revoked a short time after the case is properly closed again.
RESET
To reset the wireless remote indicator from alarm it is necessary to reset the system from the control panel: alarm indication will deactivate.
Picture 2
Picture 3
INIM ELECTRONICS S.R.L. VIA DEI LAVORATORI 10, FRAZIONE CENTOBUCHI, 63076 MONTEPRANDONE, ITALY www.inim.biz
3
Install and fix the device’s rear cover in the selected position using
the screws provided in the product’s packaging. Fixing holes are
indicated in picture 2.
Press here
to remove
Grub screw
TESTING
In order to test the functionality of the installed wireless indicator proceed as follows:
activate an alarm condition on the control panel (by a call-point or sensor in the in-
stalled system): the control panel will lit the alarm indicator.
After each test the device must be reset from the control panel (see the RESET paragraph).
If the test fails check whether the batteries are charged, if mistakes were done previously or even if the system is activated. If the remote
indicator’s functionality is hopeless, send back the device to your distributor for repair or substitution.
All devices must be tested after installation and, successively, on a periodic basis.
BATTERY FAULTS AND BATTERY SUBSTITUTION PROCEDURE
When one or both batteries are low in charge, a specific fault message is routed to the
control panel. This condition is locally signaled by the module’s status indicator LED
(check table 1).If such event occurs:
1) Remove the front cover.
2) Extract both batteries.
3) Insert both new batteries into their holders, oriented as per polarity marks.
See POWERING UP - DEVICE LINKED TO THE SYSTEM.
4) Reinstall the front cover.
TECHNICAL SPECIFICATION
BATTERY SPECIFICATION
*Battery lifespan depends by environmental conditions, default monitor settings and link quality.
Local safety standards may require you
to test these devices on a regular basis.
When a low battery condition is indicat-
ed, both batteries must be changed
altogether.
Batteries must be brand new.
Do not touch the Link / program switch.
Ensure that the batteries are installed properly,
with their polarities matching the indications on
the device.
WARNINGS AND LIMITATIONS
Our devices use high quality electronic components and plastic materials that are highly resistant to environmental deterioration. However,
after 10 years of continuous operation, it is advisable to replace the devices in order to minimize the risk of reduced performance caused by
external factors. Ensure that this device is only used with compatible control panels.
Detection systems must be checked, serviced and maintained on a regular basis to confirm correct operation. Smoke sensors may respond
differently to various kinds of smoke particles, thus application advice should be sought for special risks. Sensors cannot respond correctly if
barriers exist between them and the fire location and may be affected by special environmental conditions. Refer to and follow national codes
of practice and other internationally recognized fire engineering standards.
Appropriate risk assessment should be carried out initially to determine correct design criteria and updated periodically.
Use only in FireVibes fire detection and alarm systems.
WARRANTY
All devices are supplied with the benefit of a limited 5 years warranty relating to faulty materials or manufacturing defects , effective from the
production date indicated on each product. This warranty is invalidated by mechanical or electrical damage caused in the field by incorrect
handling or usage. Product must be returned via your authorized supplier for repair or replacement together with full information on any prob-
lem identified. Full details on our warranty and product’s returns policy can be obtained upon request.
Specification Value
Communication range with EWT100, IWT100 or XWT100 network
devices 200 m (in open space)
Wireless frequency band(s) of operation 868-868.6 MHz, 868.7-869.2 MHz, 869.4-869.65 MHz, 869.7-870.0 MHz
Number of wireless channels 66
RF output power (max) 14 dBm (25 mW) e.r.p.
Operating temperature range -10 °C to 55 °C
Maximum humidity (non condensing) 95% RH
Environmental application Indoors
Dimensions 80 mm x 80 mm x 32 mm
Weight 60 grams (without batteries)
Table 3
Specification Value
Battery type CR123A (3 V, 1.25 Ah)
Battery lifespan * 5 years
Low battery threshold value (nominal) 2.850 V
Table 2