Jung FMAS816REG Manuale utente

eNet radio switch/push-button actuator 8-gang / blinds actuator 4-gang,
for rail mounting
eNet radio switch/push-button actuator 8-gang / blinds actuator 4-gang,
for rail mounting
Art. No. : FMAS816REG
Operating instructions
1 Safety instructions
Electrical devices may only be mounted and connected by electrically skilled
persons.
Serious injuries, fire or property damage possible. Please read and follow manual fully.
Danger of electric shock. Always disconnect before carrying out work on the devise or
load. In so doing, take all the circuit breakers into account, which support dangerous
voltages to the device and or load.
Danger of electric shock. Device is not suitable for disconnection from supply voltage.
Do not connect any three-phase motors. Device can be damaged.
Danger of electric shock. During installation and cable routing, comply with the
regulations and standards which apply for SELV circuits.
Danger of electric shock on the SELV/PELV installation. Do not connect loads for mains
voltage and SELV/PELV together on a single switch actuator.
For parallel connection of several motors to an output it is essential to observe the
corresponding instructions of the manufacturers, and to use a cut-off relay if necessary.
The motors may be destroyed.
Use only venetian blind motors with mechanical or electronic limit switches. Check the
limit switches for correct adjustment. Observe the specifications of the motor
manufacturers. Device can be damaged.
Fire hazard! Operation exclusively with the power supplies listed under accessories
These instructions are an integral part of the product, and must remain with the end
customer.
2 Device components
Figure 1
(1) Load connection A1...A8
(2) Operating mode switch for outputs A1+A5, A2+A6, A3+A7, A4+A8
1/20
82581933
J0082581933 23.03.2017

(3) Button Prog A1...A8
(4) Status LED A1...A8
(5) Teach Switch for commissioning in the operating mode Venetian blind/rolling shutter
(6) Bus line connection
3 Function
Intended use
- Switching of lighting
- Switching of single-phase fan motors
- Controlling electrically driven Venetian blinds, rolling shutters and awnings
- Operation with suitable eNet radio transmitters
- Operation with power supply RMD and receiver module RMD cover or eNet server (see
accessories)Operation with power supply RMD and receiver module RMD cover or eNet
server (see accessories)
- Installation in distribution boxes on DIN rail according to EN 60715
Product characteristics
- Operating mode switch for switch-over of switching actuator, push-button actuator, blind
actuator, shutter actuator or configuration via eNet server
- Status feedback to radio transmitter
- Scene operation possible
- Outputs switchable with Prog button
- Status indicator of the outputs via LED
Switching operation:
- Switch-on telegram: Device switches on
- Switch-off telegram: Device switches off
Push-button operation:
- Relay contact remains closed as long as ON or OFF telegrams are being received
- The maximum switch-on time is 60 seconds
Operating mode Venetian blind/rolling shutter
- Positioning of the Venetian blind and slats via scene recall
- Position for sun protection and twilight
- Blind/shutter running time can be saved
- Slat change-over time can be saved
- Fabric-stretching for awnings
Can be set with eNet server in switching/push-button operation:
- Operating mode for each output can be set separately
- Flash function
- Run-on time
- Switch-on delay / switch-off delay
- Operation as NO or NC contacts
- Switch-off warning
- Minimum switching repeat time
- Operation locks
- Continuous on, Continuous off
Can be set in the operating mode Venetian blind/rolling shutter with eNet server:
- Change-over-time for direction change
- Running direction invertible
- Operation locks
- Position for sun protection, twilight, lock-out protection and wind alarm
Supplementary functions with eNet Server:
- Fully encrypted radio transmission (AES-CCM) from eNet Server software version 2.0
- Update of the device software
- Reading of error memory
2/20
82581933
J0082581933 23.03.2017
eNet radio switch/push-button actuator 8-gang / blinds actuator 4-gang,
for rail mounting

Behaviour in case of bus voltage failure and return
If the bus voltage fails, the actuator switches off. The response to bus voltage return can be
parameterised with the eNet server.
Default setting operating mode Venetian blind/rolling shutter: no action.
Switching operation/bush-button operation default setting: Off.
4 Operation
iWhen operating with the eNet Server, operation and signalling could vary from what is
described here.
Operation with radio transmitters
Operation is with radio transmitters, please observe the radio transmitter instructions.
Operation with Prog button in switching or push-button operation
oPress button Prog (3) briefly.
The light switches on or off.
Status LED A1..A8 (4) lights up: output is switched on.
Status LED A1..A8 off: output is switched off.
Operation with Prog button in the operating mode Venetian blind/rolling shutter
In this operating mode, two neighbouring outputs are combined respectively into a single
venetian blind output. Both Prog buttons have the same function.
oPress Prog button briefly.
A moving blind/shutter is stopped and a stationary blind/shutter is briefly activated, e.g. for
slat change-over.
The control direction is changed when the button is pressed again.
oPress the Prog button for longer than one second but shorter than four seconds.
The motor moves to the end position.
The control direction is changed when the button is pressed again.
The upper status LED indicates the upward movement and the lower status LED indicates
the downward movement.
5 Information for electrically skilled persons
5.1 Fitting and electrical connection
DANGER!
Electrical shock when live parts are touched.
Electrical shocks can be fatal.
Before working on the device, disconnect the power supply and cover up live
parts in the working environment.
Fitting the device
oMount device on DIN rail. Output terminals must be at the top.
3/20
82581933
J0082581933 23.03.2017
eNet radio switch/push-button actuator 8-gang / blinds actuator 4-gang,
for rail mounting

Connect bus line
Figure 2: Connection diagram of bus line
Labelling / Colour Connection
DC– / GY dark grey Power supply –
DC+ / RD red Power supply +
Bus– / WH white Data cable –
Bus+ / YE yellow Data cable +
As bus line, use e.g. J-Y(St)Y 2x2x0.8
oConnect the device with bus line (figure 2) to the RMD reception module and power supply
(see instructions of RMD reception module and power supply).
CAUTION!
Overloading the device leads to excessive heating.
Damage to the device and the connected cables may result.
Do not exceed the maximum current carrying capacity.
Load neighbouring outputs only until the sum of their output currents is a max.
of 20 A.
4/20
82581933
J0082581933 23.03.2017
eNet radio switch/push-button actuator 8-gang / blinds actuator 4-gang,
for rail mounting

Figure 3: Current carrying capacity of neighbouring outputs
Connecting loads in switching/push-button operation
Figure 4: Connection example of switching loads A1...A4
oConnect loads as shown in the connection example of switching loads (figure 4).
5/20
82581933
J0082581933 23.03.2017
eNet radio switch/push-button actuator 8-gang / blinds actuator 4-gang,
for rail mounting

Connecting loads in operating mode Venetian blind/rolling shutter
Figure 5: Connection example of Venetian blind loads
oConnect loads as shown in the connection example of Venetian blind loads (figure 5).
Presetting the operating mode
CAUTION!
Danger of destruction from wrong operating mode.
Simultaneous current feed in both directions of travel can destroy the device
and connected blind motors.
Before setting the operating mode, check what loads are connected.
One operating mode switch applies to two outputs each.
Figure 6: Operating mode switch
Switch position Function
6/20
82581933
J0082581933 23.03.2017
eNet radio switch/push-button actuator 8-gang / blinds actuator 4-gang,
for rail mounting

PC Operating mode and parameter set with eNet
server.*)
MPush-button operation
KSwitching operation
HtCommission - determine running time, activate
Teach switch
ItCommissioning - determine time for slat
change-over time, activate Teach switch
OBlind operating mode
POperating mode rolling shutter, awning
*) If the operating mode switch is turned from the position PC to another operating mode, the
parameters are set to the default setting. The settings made with the eNet Server will be
lost.
Mains voltage is switched off.
oSet the operating mode switch.
5.2 Commissioning
DANGER!
Electrical shock when live parts are touched.
Electrical shocks can be fatal.
During commissioning, cover the parts carrying voltage on radio transmitters
and actuators and in their surrounding area.
iThe actuator can also be commissioned with eNet server as an alternative to the
commissioning described here.
iPrerequisite for scenes and positioning movements is that the moving times of the
connected blind/shutter in the actuator are saved.
iTo save the running times of several outputs successively, the Teach switch must always
be turned back to position 0.
Saving blind/shutter running time for rolling shutters
The operating mode switch (2) is in the Venetian blind O or rolling shutter Pposition.
oSet Teach switch (5) to output 1, 2, 3 or 4.
oTurn the operating mode switch to the I t position until the blind/shutter reaches the upper
end position.
oTurn operating mode switch to the Ht position.
The blind/shutter moves downwards.
oWhen the lower end position is reached, turn the operating mode switch to the P position.
The running time is saved and the blind/shutter moves to the upper end position.
oTurn back Teach switch to 0 position. Otherwise, it will not be possible to operate the
output anymore.
Saving blind/shutter running time for blind
The operating mode switch (2) is in the Venetian blind O or rolling shutter Pposition.
oSet Teach switch (5) to output 1, 2, 3 or 4.
oTurn the operating mode switch to the I t position until the blind/shutter reaches the upper
end position.
oTurn operating mode switch to the Ht position.
The blind/shutter moves downwards.
7/20
82581933
J0082581933 23.03.2017
eNet radio switch/push-button actuator 8-gang / blinds actuator 4-gang,
for rail mounting

oWhen the lower end position is reached, turn the operating mode switch to the I t
position.
oWhen the slats have been fully changed over, turn the operating mode switch to the O
position.
The running times are saved and the blind/shutter moves to the upper end position.
oTurn back Teach switch to 0 position. Otherwise, it will not be possible to operate the
output anymore.
Saving the awning running time
The operating mode switch (2) is in the Venetian blind O or rolling shutter Pposition.
oSet Teach switch (5) to output 1, 2, 3 or 4.
oTurn the operating mode switch (2) to the I t position until the blind/shutter reaches the
upper end position.
oTurn operating mode switch to the Ht position.
oFor awnings without fabric-stretching function: When the extended lower end position is
reached, turn the operating mode switch to the It position. As soon the fabric is hanging
taut, turn the operating mode switch to the P position.
oFor awnings with their own fabric-stretching function: When the extended lower end
position is reached, turn the operating mode switch to the P position.
The running times are saved and the blind/shutter moves to the upper end position.
oTurn back Teach switch to 0 position. Otherwise, it will not be possible to operate the
output anymore.
Connecting output to radio transmitters
Load is switched off.
oPress button Prog (3) for longer than 4 seconds.
The load switches on.
The status LED (4) flashes after 4 seconds and the load switches off. The device is in
programming mode for approx. 1 minute.
oSwitch radio transmitter to programming mode (see radio transmitter instructions).
oTrigger telegram on the radio transmitter.
The status LED of the corresponding output is illuminated for 5 seconds.
The output is connected to the radio transmitter. The output and radio transmitter exit the
programming mode automatically.
iIf the status LED of the actuator flashes 3 times at 1-second intervals for approx.
5 seconds, then the programming operation was not successful. All the memory locations
in the actuator or radio transmitter are occupied.
iIn switching operation, All On and All Off buttons of a radio transmitter are connected to the
output automatically as soon as the first connection to the radio transmitter takes place.
iScene buttons must be connected separately.
Disconnecting connection to a radio transmitter
oCarry out the same steps as when connecting (see Connecting output to a radio
transmitter).
The status LED (4) flashes quickly for 5 seconds. The output is disconnected from the
radio transmitter. The output and radio transmitter exit the programming mode
automatically.
iIf there several connections or scene buttons for a radio transmitter, all connections must
be disconnected individually.
iAll On and All Off buttons of a radio transmitter are disconnected automatically as soon as
the last connection of the corresponding output to the radio transmitter is disconnected.
Manual disconnection is not possible.
8/20
82581933
J0082581933 23.03.2017
eNet radio switch/push-button actuator 8-gang / blinds actuator 4-gang,
for rail mounting

Resetting the output to the factory setting
All connections to radio transmitters are disconnected and parameters are reset to default
setting. If the operating mode switch is on PC, the rolling shutter operating mode is set.
iThe connections in the radio transmitters are preserved and must be deleted separately.
Load is switched off.
oPress the Prog button for at least 20 seconds.
The load switches on.
The status LED flashes after 4 seconds and the load switches off. The status LED flashes
faster after 20 seconds.
oRelease Prog button and press briefly once again within 10 seconds.
The status LED flashes more slowly for approx. 5 seconds.
The output is reset to default setting.
Resetting the device to the factory setting
oReset all outputs (see Resetting the output to the default setting).
All the status LEDs flash as soon as the last output is reset. The device is reset to default
setting.
6 Appendix
6.1 Technical data
Rated voltage AC 230V~
Mains frequency 50 / 60Hz
Ambient temperature -5 ... +45°C
Switching voltage AC 250V ~
Minimum actuation time in operating mode
Venetian blind 0.1s
Roller shutter 0.3s
Running time 1 ... 600s
Running time default setting 120 sec
Slat adjusting time 0 ... 10s
Switching current per output for AC 230 V ~
Ohmic 16A (AC1)
For switching current >10A connecting cable 2.5mm²
Fluorescent lamps 4AX
Switching current, adjacent load outputs Σ 20A
Current carrying capacity of device max. 80A
Minimum switching current AC 100mA
Contact type µ
Standby power max. 0.5W
Connected load per output
Motors 1000W
Incandescent lamps 2300W
HV halogen lamps 2000W
Electronic transformers 1500W
Inductive transformers 1000VA
HV-LED lamps typical 500W
Compact fl lamp. typical 500W
Fluorescent lamps, uncompensated 920VA
Capacitive load 690VA (560 µF)
Connection of load terminals
single stranded 1.5 ... 4mm²
Finely stranded without conductor sleeve 0.75 ... 4mm²
Finely stranded with conductor sleeve 0.5 ... 2.5mm²
Fitting width 72mm / 4modules
Bus line
Rated voltage DC 12VSELV
9/20
82581933
J0082581933 23.03.2017
eNet radio switch/push-button actuator 8-gang / blinds actuator 4-gang,
for rail mounting

Current consumption 60mA
Connection, Bus device connection terminal
Cable length max. 3m
6.2 Parameter list
The device parameters can be changed with the eNet server:
Device and channels
Parameters Setting options, Basic
setting
Explanations
Function Shutter/blind, light, switching,
unused
Basic setting: Venetian blind
Venetian blind
The channel is integrated for
the "Venetian blind" central
function in the eNet SMART
HOME app.
Light
The channel is integrated for
the "Lighting" central function
in the eNet SMART HOME
app.
Switching
The channel is not integrated
in any central function.
Unused
The channel is not displayed
in the eNet SMART HOME
app and is disabled for use in
the commissioning interface.
Setting is always made in
pairs (1/5, 2/6, 3/7, 4/8).
"Venetian blind" operating
mode
Venetian blind
Awning
Basic setting: Roller shutter
Roller shutter
A rolling shutter or an awning
is controlled for which the
Fabric stretching function is
required.
Venetian blind
A Venetian blind is controlled.
Awning
An awning is controlled for
which the Fabric stretching
function is required.
10/20
82581933
J0082581933 23.03.2017
eNet radio switch/push-button actuator 8-gang / blinds actuator 4-gang,
for rail mounting
Indice
Altri manuali Jung Interruttore

Jung
Jung 1701 SE Manuale utente

Jung
Jung FAS180 Series Manuale utente

Jung
Jung 52921 ST Manuale utente

Jung
Jung 1180 Series Manuale utente

Jung
Jung 10911ST Series Manuale utente

Jung
Jung A3181-1-01 Manuale utente

Jung
Jung 3181-1 Series Manuale utente

Jung
Jung KNX 3281-1 Series Manuale utente

Jung
Jung KNX 4071.0 LED Series Manuale dell'operatore

Jung
Jung 1202 URE Manuale utente

Jung
Jung 1704ESE Manuale utente

Jung
Jung Home Manuale utente

Jung
Jung 1701SE Manuale utente

Jung
Jung 567 S Series Manuale utente

Jung
Jung DAW 360 WW Manuale utente

Jung
Jung 10911STRF Series Manuale utente

Jung
Jung 3281-1 Series Manuale utente

Jung
Jung FMAS10ZS Manuale utente

Jung
Jung FA10EB Manuale utente

Jung
Jung 1704ESE Manuale utente